Landis & Gyr MAXsys E850 Elite Accuracy Testing
Landis & Gyr MAXsys E850 Elite Accuracy Testing

Landis & Gyr MAXsys E850 Elite Accuracy Testing

Advertisement

The accuracy testing for the Elite meter is done through the transmit "LED" of the optical port
on the face of the meter. The optical port is located on the lower left hand side of the meter face
and the left "LED" is the transmit LED and is located on the left side of the port. The LED has 9
modes of operation. Optical communications (type 7 protocol), Watt hour, Var hour,
Compensated Watt hours Comp. 1, Compensated Var hours Comp. 1, Compensated Watt hours
Comp. 2, Compensated Var hours Comp. 2, Compensated Watt hours Comp. 3 and Compensated
Var hours Comp. 3. The modes can be changed using MAXcom under the test mode screen. The
meter does not need to be put into test mode to change the LED modes. The mode of operation
can be seen on the meter display using the menu system. The user would enter the menu system
using the buttons (E) on the face of the meter. They would then select "communications" from
the list of menu items. This will take the user to a sub menu where they can select the optical
port. To select the optical port the user will select the "more ports" option that will bring up
another menu with "optical port". After selecting "optical port" the screen will display the "Cal
Pulse" mode .
When testing for meter accuracy it is recommended that no test should be run for less than 30
seconds. The 30 second test is recommended to reduce timing errors between the test equipment
and the meter. The following examples are for a Form9S, 120 volt meter with a Kh of 1.0 being
tested a rated voltage and a test current of 2.5 and 0.25 amps.
Full Load
10 Rev.
Power Factor 05 Rev.
Light Load
02 Rev.
When testing TLC accuracy the values meter is normally tested at the rated secondary value of
the instrument transformer.
The following examples are for a Form 9S, 120 volt meter with a Kh of 1.0 that is connect to
instrument transformers, VTR=7200:120 and CTR=1200:5. The tests are normally run at rate
voltage (120 volts) and a test current of % and 0.5 amps.
Full Load
20 Rev.
Power Factor 10 Rev.
Light Load
04 Rev.
Accuracy Testing
MAXsys Elite Meter
40 seconds
40 seconds
80 seconds
40 seconds
40 seconds
80 seconds

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MAXsys E850 Elite and is the answer not in the manual?

Questions and answers

Summary of Contents for Landis & Gyr MAXsys E850 Elite

  • Page 1 Accuracy Testing MAXsys Elite Meter The accuracy testing for the Elite meter is done through the transmit “LED” of the optical port on the face of the meter. The optical port is located on the lower left hand side of the meter face and the left “LED”...
  • Page 2 TEST MODE When the meter is placed into test mode the meter will stop incrementing all of the register this includes Energy, demand and instantaneous values. The output relays will be turned off and the data recorder will not record data while the meter is in test mode. Only values from table 36 (test display) will be active.
  • Page 3 Test Mode Screen 8. The test “Subinterval Time” (length of demand subinterval), “Number OF Subintervals (number of subintervals per demand interval)”, “Number Of Intervals” (number of demand interval for test to run) and “Limit Minutes” (the amount of time the meter will remain in test mode without activity) the entrees cannot be changed after the meter has been programmed.
  • Page 4 15. Click “Get Results 16. You can run another test be clicking “Start Test”. a. This will clear the old test data and the test will start. 17. When you have completed your testing. a. Remove the testing equipment. 18. Take the meter out of test mode by clicking “Exit” (The meter cannot be running a test when you try and exit test mode), always stop the test before exiting the test mode.
  • Page 5 8. An alternate method for starting the test would be to power the meter down and the power the meter up. On power-up the meter will start the test. This method was provide so a number of meters (gang testing) could start there test at the same time. 9.