Time overcurrent relays
Hide thumbs Also See for IAC77B:

Advertisement

0. 5-4.00
2. 0-16.0
10.0-80.0
20. 0-160. 0
* Highe r curre nts may be appli ed for short er lengt hs of time in accor dance
formula I
** S
Series connected, P = Parallel connected
=
TARGET SEAL-IN UNIT
Ratings for the target seal-in unit are shown in Table VII.
If the tripping current exceeds 30 amperes, an auxiliary relay should be used, the connections being
such that the tripping current does not pass through the contacts or the target and seal-in coils of the
protective relay.
CONTACTS
The current-closing rating of the contacts is 30 amperes for voltages not exceeding 250 volts.
current-carrying rating is limited by the ratings of the seal-in unit.
Burdens for the time overcurrent unit are given in Table VIII.
GEK-34055
TABLE VI
RANGE
CONTINUOUS
RATING
s
0.5-2.00
0.75
p
1. 0-4. 00
1. 5
s
2. 0-8. 00
3. 0
p
4. 0-16. 00
6. 0
s
10. 0-40. 0
15. 0
p
20. 0-80. 0
25. 0
s
20. 0-80.0
25. 0
!
p
40.0-160.0
25.0
=
where T is the time in seconds that the c urrent flows.
,
TABLE VII
10% (OHMS)
D.C. RESISTANCE
+
MIN. OPERATING (AMPERES )+0- 25%
CARRY CONT. (AMPERES)
CARRY 30 AMPS FOR (SEC. )
CARRY 10 AMPS FOR lSEC. l
60 HZ IMPEDANCE (OHMS)
* ONE
SECOND
25.0
50. 0
130. 0
260. 0
400. 0
600. 0
600. 0
600. 0
7
0.13
0. 2
2. 0
0. 3
3. 0
0.03
4. 0
30. 0
0. 25
52. 0
0. 53
BURDENS
6
K
625
2500
16900
67600
160000
360000
360000
360000
with the
f
The