A - C L A S S
GulfStream
DESIGN AND INSTALLATION MANUAL
FOR THE ROOF TERMINAL FLUE KIT
FOR PITCHED AND FLAT ROOFS
ROOF TERMINAL FLUE KIT G.C. NO .................
benchmark
TM
THE GAS SAFETY (INSTALLATION AND USE)
The code of practice for the installation,
REGULATIONS -
commissioning & servicing of central heating systems
In your own interest and that of safety, it is
law that all gas appliances are installed by
competent persons and in accordance with the
above regulations.

Advertisement

loading
Need help?

Need help?

Do you have a question about the A-CLASS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Gulfstream A-CLASS Series

  • Page 1 A - C L A S S GulfStream DESIGN AND INSTALLATION MANUAL FOR THE ROOF TERMINAL FLUE KIT FOR PITCHED AND FLAT ROOFS ROOF TERMINAL FLUE KIT G.C. NO ....benchmark THE GAS SAFETY (INSTALLATION AND USE) The code of practice for the installation, REGULATIONS - commissioning &...
  • Page 2 Page 2...
  • Page 3 Sale, which are set out at the rear of this manual. In the interest of continuously improving the GulfStream range, Gledhill Water Storage Ltd reserve the right to modify the product without notice, and in these circumstances this document, which is accurate at the time of printing, should be disregarded.
  • Page 4: Flue Components

    flue is installed. It is also important that the flue terminal is located as near as practical to the GulfStream A-CLASS appliance and the route of the flue is checked and clear of any roof trusses or other obstructions in the roofspace.
  • Page 5 R00F TERMINAL FLUE KIT 3.0 DESIGN/ TECHNICAL y t i i r c The standard pitched roof terminal flue kit, c i r (stock code no. AFG006) is based on the c i r 60/100mm concentric flue system components shown opposite. c i r The standard kit should cover the majority c i r...
  • Page 6 ROOF TERMINAL FLUE KIT 3.0 DESIGN/TECHNICAL Two examples of how to calculate the Roof equivalent flue length for the typical 60mm diameter flue system installations shown opposite , using the Table below, is as follows. 1. Concentric flue pipe length 4.0m x 2 = 8.0m 3.0m Equivalent length of fittings...
  • Page 7 The appliance location itself should have been chosen to comply with the relevant A-CLASS requirements of the GulfStream Design Installation and Servicing Instructions. When terminating the flue adjacent to an opening in a pitched or flat roof these must be positioned in accordance with the requirements shown opposite.
  • Page 8: Installation

    ROOF TERMINAL FLUE KIT 4.0 INSTALLATION Make sure the appliance is in the correct position before commencing installation of the air/flue pipes. The flue pipes must be assembled with the plain end of pipe (or fitting) nearest the appliance and the socket end furthest from the appliance.
  • Page 9 ROOF TERMINAL FLUE KIT 4.0 INSTALLATION The roof terminal should be installed as follows - see sketches opposite; 1. Check the flue terminal for any damage Flat roof flashing Universal pitched roof flashing 2. Taking the roofing into account check the type of weather collar is correct.
  • Page 10 ROOF TERMINAL FLUE KIT 4.0 INSTALLATION The standard flue kit should be installed as follows ; 1. Push the concentric boiler conversion box firmly into the sockets provided on the appliance ensuring the flue and air inlet are not exchanged. (The connections are labelled and when installed correctly the flue pipe socket on the appliance will be directly below the flue pipe connection on the adaptor), see diagram...
  • Page 11 �������� ��� ������ �������� ���� �������� ���� ���������� �� ���� � �������� ����� �� �� ���� �� �������� ���� ��� ���������� ����� ������ ����� ��� �� ������ ������ �� �� ����� �� ��� �� ��� ���� �� ������� �� ���� ���� �� �������� ������� ��������...
  • Page 12 ��� �� ��� ����� ���� ��� ��������� ����� ���� ��� �� ��� ����� ��� ��� ����� ��������� �� ��� ��������� ���� ��� ����� ��� ��������� �� ������� ����� �� � �� ����� �������� �� �������� �� ������ ��� ������� ��� ��������� ����� ��������� ��������...