LG AUUW09GA0 Engineering Product Data Book page 101

Table of Contents

Advertisement

Single CAC
Outdoor Unit
9. Electric Characteristics
Outdoor Unit
Combined Indoor Unit
Model names
Model Name
ATNH09GRLE2
ABNW09GL2A2
AUUW09GA0
[UU09W UL0]
AVNH09GELA2
AQNH09GALA0
ATNH12GRLE2
ABNH12GL2A2
AUUW12GA0
[UU12W UL0]
AVNH12GELA2
AQNH12GALA0
ATNW18GQLA0
ABNW18GM1A0
AUUW18GAE
ABNH18GL2A2
[UU18W UE4]
UVNH18GJLA2
AQNH18GALA0
ATNW24GPLA0
ABNW24GM1A0
AUUW24GAE
[UU24W U44]
ABNH24GL3A2
UVNH24GJLA2
ATNW30GPLA0
ABNW30GM1A0
AUUW30GAE
[UU30W U44]
UVNH30GJLA2
AJNW30GVLA0
ATNH36GNLE2
ABNW36GM2A0
AUUW366D2
[UU36W UO2]
UVNH36GKLA2
AJNW36GVLA1
Note
1. Voltage supplied to the unit terminals should be within the minimum and
maximum range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM and IFM are measured as the outdoor unit test condition.
6. Select the wire size based on the MCA.
7. MFA is used to select the circuit breaker and ground fault circuit
interrupter, and recommended circuit breaker type is ELCB(Earth Leakage
Circuit Breaker).
94
Unit
Phase
No. of
Hz
Unit
Volts
[CT09 NR2]
[CB09L N22]
[CV09 NE2]
[CQ09 NA0]
[CT12 NR2]
[CB12L N22]
[CV12 NE2]
[CQ12 NA0]
[CT18 NQ4]
[CM18 N14]
[CB18 N22]
[CV18 NJ2]
1
1
50
[CQ18 NA0]
220-240
[CT24 NP4]
[CM24 N14]
[CB24L N32]
[CV24 NJ2]
[UT30 NP4]
[UM30 N14]
[UV30 NJ2]
[UJ30 NV2]
[UT36 NN2]
[UM36 N24]
[UV36 NK2]
[UJ36 NV3]
Power
Voltage
MCA MFA MSC
range
6.9
15
-
7.3
15
-
6.9
15
-
7.1
15
-
7.9
15
-
8.3
15
-
7.9
15
-
8.1
15
-
16.2
20
-
16.2
20
-
16.6
20
-
16.2
20
-
Min. : 198
16.5
20
-
Max. : 264
22.3
30
-
22.2
30
-
22.7
30
-
22.3
30
-
22.3
30
-
22.5
30
-
22.3
30
-
22.3
30
-
22.4
40
-
23.1
40
-
22.5
40
-
22.4
40
-
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes (A)
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Standard Inverter
Comp
OFM
RLA
kW
FLA
5.00
0.043
0.25
0.020
5.00
0.043
0.25
0.095
5.00
0.043
0.25
0.030
5.00
0.043
0.25
0.020
5.80
0.043
0.25
0.020
5.80
0.043
0.25
0.095
5.80
0.043
0.25
0.040
5.80
0.043
0.25
0.030
12.40
0.085
0.33
0.040
12.40
0.085
0.33
0.080
12.40
0.085
0.33
0.120
12.40
0.085
0.33
0.050
12.40
0.085
0.33
0.040
17.00
0.124
0.48
0.060
17.00
0.124
0.48
0.090
17.00
0.124
0.48
0.150
17.00
0.124
0.48
0.060
17.00
0.124
0.48
0.080
17.00
0.124
0.48
0.150
17.00
0.124
0.48
0.060
17.00
0.124
0.48
0.160
16.93
0.171
0.65
0.140
16.93
0.171
0.65
0.210
16.93
0.171
0.65
0.090
16.93
0.171
0.65
0.160
IFM
kW
FLA
0.40
0.80
0.40
0.60
0.40
0.80
0.40
0.60
0.40
0.40
0.80
0.40
0.70
0.60
0.50
1.00
0.60
0.60
0.80
0.60
0.60
0.60
1.30
0.70
0.60

Hide quick links: