Eco CB 85 CH Installation, Service And User Manual

Wall hung high efficiency central heating boiler
Table of Contents

Advertisement

Installation, service and user manual
Wall hung high efficiency central heating boiler
CB 85 CH
CB 105 CH
CB 125 CH
CB 155 CH
Original manual
E93.1605.901

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CB 85 CH and is the answer not in the manual?

Questions and answers

Summary of Contents for Eco CB 85 CH

  • Page 1 Installation, service and user manual Wall hung high efficiency central heating boiler CB 85 CH CB 105 CH CB 125 CH CB 155 CH Original manual E93.1605.901...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS INTRODUCTION ..........................7 ........................7 BBREVIATIONS SAFETY GUIDELINES ......................... 7 TECHNICAL DATA CB BOILERS ....................... 8 ...................... 8 UNCTIONAL INTRODUCTION ....................8 OCATION OF VERSION NUMBERS 3.2.1 Technical specifications datasheet ................9 ................... 11 SPECIFICATIONS DATASHEET DIMENSIONS &...
  • Page 4 ..........................32 OOM AIR 9.5.1 Air contamination ......................32 ....... 33 ROPER VENT INSTALLATION AND TYPE OF GAS VENT OR VENT CONNECTOR ..............34 OILER CATEGORIES TYPES OF FLUE GAS SYSTEMS ........................37 CERTIFIED ............37 IPE HEIGHTS AND MUTUAL DISTANCES ON A FLAT ROOF 9.10 .................
  • Page 5 12.9 ..................76 EMAND FOR OMESTIC ATER 12.9.1 No Domestic Hot Water; DHW mode 0 ..............76 12.9.2 DHW Storage with sensor; DHW mode 1 ..............76 12.9.3 DHW Storage with thermostat; DHW mode 2 ............77 12.9.4 Instantaneous water heating with plated heat exchanger; DHW mode 3 ....77 12.9.5 Anti-legionella protection ....................
  • Page 6 22 Spare parts ............................122 22.1 CB 85, CB105 CB 125 E ................ 122 XPLODED VIEW 22.2 CB 155 E ....................... 124 XPLODED VIEW 22.2.1 Part numbers CB 85-155 ..................126 23 USER’S PART..........................129 23.1 ........................129 BBREVIATIONS 23.2 .
  • Page 7: Introduction

     The user (see chapter 22). Eco Heating Systems Groningen B.V. is not accountable for any damage caused by incorrect following these instructions. For service and repair purposes use only original Eco Heating Systems Groningen B.V. spare parts. All documentation produced by the manufacturer is subject to copyright law.
  • Page 8: Technical Data Cb Boilers

    3 TECHNICAL DATA CB BOILERS 3.1 Functional introduction The CB boilers are central heating boilers with a maximum high efficiency. Such a performance can be reached by, amongst other things, using a special heat exchanger made of stainless steel. This allows the flue gases to cool down below the condensation point, and so release extra heat.
  • Page 9: Technical Specifications Datasheet

    3.2.1 ECHNICAL SPECIFICATIONS DATASHEET GENERAL Product identification number: 0063CT3633 Gas Appliance Type B23(P), C13, C33, C43, C53, C63, C83, C93 Type boiler CB 85 CH CB 105 CH CB 125 CH CB 155 CH Classification II2EL3P II2ELL3P II2ELL3P II2ELL3P Dimensions (h x w x d)
  • Page 10 Type boiler CB 85 CH CB 105 CH CB 125 CH CB 155 CH EMISSION Values min-max: 7.9 – 8.4 7.9 – 8.4 7.9 – 8.4 7.9 – 8.4 flue gas G25.3 8.4 – 8.2 8.4 – 8.2 8.4 – 8.2 8.4 –...
  • Page 11: Erp Specifications Datasheet

    3.3 ERP specifications datasheet Technical parameters according to the European ERP (Energy Related Products) legislation: Type Boiler: CB 85 CH CB 105 CH CB 125 CH CB 155 CH Condensing boiler: low temperature boiler: B11 boiler: Cogeneration space heater: Combination heater:...
  • Page 12: Dimensions & Connections

    4 DIMENSIONS & CONNECTIONS 4.1 CB-85-CH and CB-105-CH CB-85-CH & CB-105-CH Twin pipe CB-85-CH & CB-105-CH Concentric EHS.T0200.50321 EHS.T0200.50311 Connections Twin Pipe Concentric BSP 1” Flow BSP 1” Return Condensate Flexible hose Ø 25/21 mm BSP ¾” 100 mm 100-150 mm Flue gas 100 mm 100-150 mm...
  • Page 13: Cb-125-Ch

    4.2 CB-125-CH CB-125-CH Twin pipe CB-125-CH Concentric EHS.T0200.50211 EHS.T0200.50221 Connections Twin Pipe Concentric BSP 1” Flow BSP 1” Return Condensate Flexible hose Ø 25/21 mm BSP ¾” 100 mm 100-150 mm Flue gas 100 mm 100-150 mm Air inlet E93.1605.901 CB CH manual...
  • Page 14: Cb-155-Ch

    4.3 CB-155-CH CB-155-CH Twin pipe Connections Twin Pipe BSP 1¼” Flow BSP 1¼” Return Condensate Flexible hose Ø 25/21 mm BSP 1” 150 mm Flue gas EHS.T0200.50111 150 mm Air inlet E93.1605.901 CB CH manual...
  • Page 15: Accessories And Unpacking

    5 ACCESSORIES AND UNPACKING 5.1 Accessories Depending on the selected controlling behaviour for the central heating system and/or the optional use of a calo- rifier, the following items can be supplied with the boiler. Ask your supplier for the specifications. Item Part Nº.
  • Page 16: Installation Of The Cb

    6 INSTALLATION OF THE CB 6.1 Installation clearances On all sides of the boiler at least 5 cm of clearance must be applied to walls or wall units, 30 cm above the top side of the boiler and 25 cm from the bottom/pump of the boiler. Clearances to wall, ceiling and floor in cm A: Front B: Top...
  • Page 17: Mounting The Boiler

    The boiler must be positioned and installed by a skilled installer in accordance with all applicable standards and regulations. Commissioning of the boiler must be done by a skilled service/commissioning engineer, who is trained for this type of boiler. 6.3 Mounting the boiler Before mounting and installing the boiler the following connections must be considered: •...
  • Page 18: Connections

    7 CONNECTIONS 7.1 Boiler connections 1 – Flow (Hot water out) 2 – Return (Cold water in) 3 – Gas 4 – Condensate trap cleaning point 5 – Condensate drain 6 – Automatic air vent. 3 4 5 6 Strain on the gas valve and fittings may result in vibration, premature component failure and leakage and may result in a fire, explosion, property damage or serious injury.
  • Page 19: Flow And Return Connections

    The condensate trap must al- ways be filled to the edge with water, before replacing to the unit. 7.3 Flow and return connections Use T-pieces for externally mounting the pres- sure relief valve and the boiler bleed valve for BOILER servicing the boiler.
  • Page 20: Bypass

    7.7 Bypass The boiler has no internal bypass. When many thermostatic valves are being used, the system must have a by- pass to allow an adequate flow when all thermostatic valves are closed. Instead of a bypass also a low-loss header can be used for this function.
  • Page 21: Water Quality

    7.11 Water quality The pH value is reached with the steady condi- Contaminant Maximum allowable level Units tions. These steady conditions will occur, when 7.5 to 9.5 after filling the heating system (pH around 7) Total hardness 50 to 150 CaCO with fresh water, the water will lose its air be- 3.5 to 10.5...
  • Page 22: Chemical Water Treatment

    Maximum glycol concentration is 50%, read the suppliers instruction carefully. Because of the higher viscosity of the glycol mixture, increase pump head by 20% at 40% glycol. For use with glycol, select a pump with glycol seals. Because of the lower heat capacity of the glycol mixture, power will be reduced by approximately 10% at 40% glycol.
  • Page 23: Flush The System With Fresh Water

    7.14 Flush the system with fresh water The water of the boiler and heating circuit must be free of any particles, debris and pollution. Therefore, the complete installation must always be thoroughly flushed with clean water before installing and using the boiler(s). 7.15 Plastic piping in the heating system When plastic pipes with no oxygen barrier e.g.
  • Page 24: Automatic Feed Valve Systems

    The following scheme below shows the behaviour of the 3-way valve and general pump during one whole cycle of De-Air sequence with a DAir_Repeation_OnOff set to 2. Relevant variables: Specific Parameters Level (Default) Value Range De-Air Config 2: Installer 0: 24 hr pump Configuration for the De-Air function 1: De-Air 2: Disabled...
  • Page 25: Installation Examples

    7.19 Installation examples 7.19.1 E XAMPLE OF A LOW RESISTANCE HEATING CIRCUIT valve BOILER air separator dirt separator strainer (water filter) HEATING ZONE pressure relief valve condensate trap pump automatic air vent expansion vessel 7.19.2 E XAMPLE OF A NORMAL SINGLE BOILER HEATING CIRCUIT WITH LOW LOSS HEADER PREFERABLE valve BOILER...
  • Page 26: Example Of A Multiple Boiler Heating Circuit With Low Loss Header

    7.19.3 E XAMPLE OF A MULTIPLE BOILER HEATING CIRCUIT WITH LOW LOSS HEADER NON RETURN VALVE BOILER BOILER (low resistance type) NOT SPRING LOADED HEATING ZONE Boiler pump Heating pump Flow/ system temperature sensor E93.1605.901 CB CH manual...
  • Page 27: Pump Characteristics

    8 PUMP CHARACTERISTICS 8.1 Hydraulic graphs Boiler heat exchanger resistance graph CB 85 HYDRAULIC GRAPH UPML25-105 PWM 10,0 FLOW [m ΔT=20K ΔT=25K BOILER PUMP INSTALLATION CB 105 HYDRAULIC GRAPH UPML25-105 PWM 10,0 FLOW [m ΔT=20K ΔT=25K BOILER PUMP INSTALLATION E93.1605.901 CB CH manual...
  • Page 28: Modulating Pump For Ch Demand

    CB 125 HYDRAULIC GRAPH UPMXL GEO 25-125 130 PWM 10,0 FLOW [m ΔT=20K ΔT=25K BOILER PUMP INSTALLATION CB 155 HYDRAULIC GRAPH UPMXXL 32-120 180 PWM 10,0 FLOW [m ΔT=20K ΔT=25K BOILER PUMP INSTALLATION 8.2 Modulating pump for CH demand The controller supports PWM modulation for the general pump. The boiler pump is modulated when there is a demand for CH.
  • Page 29: Modulating Pump Modes

    8.3 Modulating pump modes There are several modulating pump modes implemented in the software. By selecting a different modulating pump mode, the pump behaviour can be changed. The following modulating pump modes are available. Modulating pump mode Details Disabled No pump modulation; the PWM duty cycle is always 0%. Delta temperature modulation Calculated duty cycle to create a delta temperature between the T_Supply and T_Return sensor.
  • Page 30: Flue Gas And Air Supply System

    Manuals for parts supplied can be found at: WARNING: www.mg-flues.com/instructions/ and http://burgerhout.nl/documenten/handleidingen/ Undermentioned manuals for parts supplied by ECO HS are applicable: - Regulations regarding flue gas systems PP(s) - Installation instructions clamps: Checklist - Installation instructions Skyline 3000 - Installation instruction Multiline PP (Cascade) Never use aluminium containing flue gas pipes in these boilers.
  • Page 31: Polypropylene

    A few examples of flue gas material suitable for ECO boilers: CE String for Plastic PPs: EN14471 T120 P1 W 2 O(30) I C/E L CE String for Stainless Steel: EN1856-1 T250 P1 W V2-L50040 O (50) When selecting flue gas systems, be aware that the minimum requirements are met. So only select flue gas materials having the same or better properties than this table.
  • Page 32: Combustion Air Quality

    9.4.1 OMBUSTION AIR QUALITY Combustion air must be free of contaminants. For example: chlorine, ammonia and/or alkali agents, dust, sand and pollen. Remind that installing a boiler near a swimming pool, a washing machine, laundry or chemical plants does expose combustion air to these contaminants. 9.4.2 IR SUPPLY THROUGH HUMID AREAS When the supply duct will be placed in a boiler room with moist air (for example: greenhouses), a double walled...
  • Page 33: Proper Vent Installation And Type Of Gas Vent Or Vent Connector

    Corrosive Contaminants and Sources Products to avoid: Spray cans containing chloro/fluorocarbons Permanent wave solutions Chlorinated waxes/cleaners Chlorine-based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry...
  • Page 34: Boiler Categories - Types Of Flue Gas Systems

    9.7 Boiler categories - types of flue gas systems. For C43 and cascade see manuals at the suppliers website: http://www.ecohs.nl/ Type according EN 15502-2-1: 2012 Performance Description B23(P) * Roof terminal flue outlet Open * Without draught diverter Air supply from * Boiler room air supply.
  • Page 35 Closed Type C43. A type C4 appliance incorporating a Air inlet Flue outlet Air supply fan upstream of the combustion cham- from outside ber/heat exchanger. EHS.D0500.5010.400 Closed *Separate air supply duct Flue Outlet Air supply *Separate flue gas discharge duct. from outside * Air supply inlet and flue gas outlet at different air pressure zones.But not at opposite walls.
  • Page 36 Closed * Separate air supply duct from external wall. Flue outlet Air supply * Flue gas discharge through individual or from outside shared flue ducting built into the building. * Air supply inlet and flue gas outlet at different air pressure zones. Air inlet * Condensate is not allowed to go to the boiler.
  • Page 37: C63 Certified

    9.8 C63 certified If a heater is C63 certified, the flue gas and air supply parts must have a separate CE marking according the building products regulations. The parts must be able to handle the condensate forming (W) and transport, overpressure (P1) and must have a minimum temperature class of T120.
  • Page 38: Flue Gas And Air Supply Resistance Table

    9.10 Flue gas and air supply resistance table In the next section, for five typical flue gas outlet & air inlet configurations the maximum lengths of the straight pipes will be calculated. First all component resistance values are given in the next table: PARALLEL CB 85 CB 105...
  • Page 39: Typical Examples

    Concentric pipe for flue gas/air supply (wall-mounted) Separate air supply duct & flue duct in different pressure zone NOTICE: specific resistance values of ECO-HS flue gas and air intake parts are used for these examples. Other suppliers can have deviating values! 9.11.1 E...
  • Page 40: Example B: Twin Pipe System With Concentric Roof Terminal

    The total resistance is more than 200 Pa. This flue gas / air supply system is NOT functional. NOTE: ECO specific resistance values are used in this example. Flue and air pipes of other suppliers can have other values E93.1605.901 CB CH manual...
  • Page 41 Examples A (C63) and B (C33) maximum pipe lengths Concentric roof terminal Flue outlet Air inlet concentric/ parallel adaptor Example B Example A Example A (C63) boiler type → CB 85 CB 105 CB 125 CB 155 Diameter air pipe [mm] Diameter flue pipe [mm]...
  • Page 42: Example C: Single Flue Gas Outlet. Air Supply From Boiler Room

    The total resistance is less than 200 Pa. This flue gas / air supply system is functional. NOTE: ECO specific resistance values are used in this example. Flue and air pipes of other suppliers can have other values Example C (B23, B23P) boiler type →...
  • Page 43: Example D: Concentric Flue Gas/Air Supply Pipe (Roof-Mounted)

    The total resistance is more than 200 Pa. This flue gas / air supply system is NOT functional. NOTE: ECO specific resistance values are used in this example. Flue and air pipes of other suppliers can have other values 9.11.5...
  • Page 44 Examples D and E maximum pipe lengths Example D (C33) boiler type → CB 85 CB 105 CB 125 CB 155 Diameter concentric pipe [mm] 100/150 POSSIBLE POSSIBLE POSSIBLE Concentric roof terminal [mm] 100/150 use less use less use less Maximum pipe length bends and/or bends and/or...
  • Page 45: Example F: Separate Air Supply Duct & Flue Duct In Different Pressure Zone (C53)

    9.11.6 F: S & (C53) XAMPLE EPARATE AIR SUPPLY DUCT FLUE DUCT IN DIFFERENT PRESSURE ZONE Calculation example with given lengths: checking resistance Boiler type: CB 105 Diameter: 100 mm. Pa total quantity Straight tube m total 24.0 Bend 45° 18.0 Bend 90°...
  • Page 46: Common Flue Cascading

    10 COMMON FLUE CASCADING 10.1 Appliance The CB boilers are suitable for a zero pressure system ac- cording to table below. TABLE (Valid for parts supplied by M&G). minimum - maximum vertical length in m. Type of Number of DN200/200 DN200/250 DN200/300 boiler...
  • Page 47: Safety Measures Common Flue Systems

    10.2 Safety measures Common Flue Systems In case CB boilers are installed with a common flue system and the combustion air is drawn directly from the room, safety measures have to be taken Indicated hazard The CB boilers are equipped with a Non-return valve to prevent recirculation of flue gas of a running boiler through one or more boilers which are not running and are connected with a common flue system.
  • Page 48 Fuse Phase 230 Vac Zero Wire used to activate other detectors 230Vac Relay detector Relay detector Boiler 4 Boiler 1 Boilerl 3 Boiler 2 Boiler 1 = Managing Boiler 2 = Depending 1 Boiler 3 = Depending 2 Boiler 4 = Depending 3 Connect N.C.
  • Page 49: Existing Common Venting Guidelines

    10.3 Existing common venting guidelines Do not common vent the CB boiler with the vent pipe of any other boiler or appliance. However, when an exist- ing boiler is removed from an existing common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
  • Page 50: Electrical Installation

    11 ELECTRICAL INSTALLATION 11.1 General • For operation, the boiler needs a power supply of 230 VAC 50Hz. • The boiler main supply connection is phase/neutral sensitive. • The wiring for the connections can be entered at the bottom of the boiler through the cable glands. •...
  • Page 51: Explanation Of The Low Voltage Connections

    11.4 Explanation of the low voltage connections. OUTDOOR SENSOR If an outdoor temperature sensor is connected, the boiler will control the supply water temperature by using a calculated setting based on outdoor reset curve, which is related to the outdoor temperature. SYSTEM SENSOR If a low loss header is used, this sensor measures the flow temperature at the system side.
  • Page 52: Explanation Of The High Voltage Connections

    11.5 Explanation of the high voltage connections. 1-2-3-PE DIVERTER VALVE DHW indirect tank If an indirect domestic hot water tank is installed, a 3-way valve or a pump (P2) can be used to divert hot water to the heating coil of the tank. This 3-way valve will open, or pump will power on, when the indirect tank has a heat demand.
  • Page 53: Ladder/Logic Diagram

    11.6 Ladder/Logic Diagram E93.1605.901 CB CH manual...
  • Page 54: Electrical Schematics

    11.7 Electrical schematics E93.1605.901 CB CH manual...
  • Page 55 E93.1605.901 CB CH manual...
  • Page 56: Sensor Availability

    11.8 Sensor availability The following table shows the sensor availability for all CH and DHW control modes. Sensors not mentioned in the table are optionally available for other functions CH Mode T_Supply T_Return T_DHW T_Outdoor 0-10 Volt Water Flow DHW RT Switch M = Mandatory, O = Optional, --- = Disabled.
  • Page 57: Programmable In- And Outputs

    11.10 Programmable in- and outputs It is possible to re-program some in- and outputs to other functions. To do this use list below and go to: Menu\settings\boiler settings\"1122" (installer password)\boiler parameters boiler parameter name default description terminal (117) Prog. Input 2. DHW flow switch LV 16-17 (118)
  • Page 58: Burner Controller And Display

    12 BURNER CONTROLLER AND DISPLAY. 12.1 Display and buttons 09:03 On / off switch. Switches electrical power to the boiler Connector for computer cable Reset lockout error Main Menu Escape / Return to the status overview Right Enter a menu item or confirm selection in Status overview (when directly setting Actual setpoint or DHW setpoint) Left Return to previous menu item or Status overview...
  • Page 59: Screens And Settings

    12.2 Screens and settings. This screen is active during power up and will remain active until communication with the Main Control (the AL- BUS) has been established. After communication has been established the following Status overview appears: The Status overview has the three different sections that show specific information: Header Middle section Footer...
  • Page 60: Set Actual Ch Setpoint/Dhw Setpoint Directly Via The Status Overview

    Footer Shows Error/Warning messages when an Error or Warning is set in the Main Control, otherwise a quick menu is displayed where the user can quickly edit setpoints and enable/disable CH or DHW. Quick Menu / Parameter Description Value / Unit CH Control Enable/disable Central Heating 0: User...
  • Page 61: Entering The Menu

    12.2.2 E NTERING THE MENU Enter the menu by pressing the MENU button once. The header in the display shows you are inside the main menu. While scrolling through the menu you will see that the selected menu item is shown in a white rectangle. Central Heating (CH) Domestic Hot Water (DHW) Information...
  • Page 62: Protected Menu Items

    12.2.3 P ROTECTED MENU ITEMS Some menu items are protected and only accessible via a password* The following password screen will then appear: Users are only allowed to change parameters not needing a password. Installers have to use the password 1122 to change parameters protected by a password.
  • Page 63: Language Settings

    12.2.5 L ANGUAGE SETTINGS The display supports the following languages:    Chinese German Romanian    Croatian Greek Russian    Czech Hungarian Slovak    Dutch Italian Slovene    English Polish Spanish ...
  • Page 64: Error Logging

    12.4 Error logging. Error logging is available. This functionality is linked to the Real-Time Clock functionality. Errors will be logged for a stand-alone system or for a complete cascade system (based on the cascade settings). The PB display will monitor the error codes it receives from the boiler(s) and if an error code is a new error code the error will be stored in the error log.
  • Page 65: Service Reminder

    12.5 Service reminder The Service reminder will remind the owner/user of the appliance to service the appliance at a specified "Ser- vice_Interval", factory set on 2000 burn hours. When service is not done within this time, a service reminder will be shown on the screen: "Service is required!", alternating with the normal status display.
  • Page 66: General

    12.6 General The burner controller is designed to function as a standalone control unit for intermittent operation on heating ap- pliances with a premix (modulating) burner and a pneumatic air-gas system. Fuses Mains input 1 x 5AT, 230V Flame establishing period 2 seconds 5 seconds Safety time...
  • Page 67: Ignition Cycle

    12.7 Ignition cycle During the ignition cycle multiple safety checks are active The table below shows the states of the burner ignition cycle, as shown in the diagram above: Burner state Actions  INIT Controller initialization  RESET Software reset (and initialization) ...
  • Page 68: Control Functions

    During the ignition cycle multiple safety checks are active: False flame detection If flame is detected at the end of the pre-spark period (Pre_Ignit) a lockout error will occur. Re-ignition If at the end of the safety period no flame is detected the control will go to Post_Purge to remove any unburned gas.
  • Page 69: On Board Hmi And Led Colors

    12.7.2 O N BOARD COLORS On the burner controller a basic on-board Human Interface (HMI) is available which consists of a push button and a 2 color (red/green) LED. These are used to indicate basic status information about the control. Status LED Reset button 900MN...
  • Page 70: Control Functions

    12.8 Control functions Dependent on the required functions of the appliance and connected sensors and components, several operation modes for Central Heating (CH) and Domestic Hot Water (DHW) can be selected. 12.8.1 R ; CH 0 (D OOM THERMOSTAT ONLY MODE EFAULT SETTING For this mode the CH mode must be set to 0 and no outdoor sensor is needed.
  • Page 71: With An Outdoor Temperature Reset And Thermostat; Ch Mode 1

    12.8.2 CH ; CH WITH AN OUTDOOR TEMPERATURE RESET AND THERMOSTAT MODE If the parameter CH_Mode is set to 1, the “Outdoor temperature reset with room thermostat” mode is selected. This mode will only function when an outdoor temperature sensor is connected. If the outdoor sensor is connected, the boiler automatically uses Reset_Curve_Boiler_Maximum.
  • Page 72 Setpoint adjustment It is possible to adjust the calculated setpoint with parameter CH_Setpoint_Diff. The calculated setpoint can be increased or decreased with a maximum of 10 ºC (18 °F). The CH setpoint limits (Reset_Curve_Boiler_Minimum and Reset_Curve_Boiler_Maximum) are respected while adjusting the setpoint. Apart from the calculated setpoint the functionality is the same as described in §...
  • Page 73: With Constant Circulation System Outdoor Reset; Ch Mode 2

    12.8.3 CH ; CH WITH CONSTANT CIRCULATION SYSTEM OUTDOOR RESET MODE When CH_Mode is set to 2, full weather compensator is chosen. For this mode an outdoor sensor has to be connected. The CH_Setpoint is calculated on the same way as described in § 12.7.2 "CH with an outdoor tem- perature reset and thermostat;...
  • Page 74: Central Heating With Analogue Input Control Of Setpoint; Ch Mode 4

    12.8.5 C ; CH ENTRAL EATING WITH ANALOGUE INPUT CONTROL OF SETPOINT MODE CH mode is set to 4. In this mode of operation, the boiler CH setpoint is controlled by an analogue input signal provided by a remote means such as a Building Management System or a system controller. The analogue input 0-10 VDC is used to adjust the boiler setpoint between the CH_Setpoint_Min and the CH_Setpoint_Max settings.
  • Page 75: With Analogue Input Control Of Power Output; Ch Mode 5

    12.8.6 ; CH WITH ANALOGUE INPUT CONTROL OF POWER OUTPUT MODE In this mode of operation, the boiler power (boiler input) is controlled by an analogue input signal provided by a remote means such as a Building Management System or a system controller. The analogue input 0-10 VDC is used to adjust the boiler power output between the minimum boiler input and the maximum boiler input settings.
  • Page 76: Demand For Domestic Hot Water

    12.9 Demand for Domestic Hot Water 12.9.1 N ; DHW OMESTIC ATER MODE No domestic hot water is available. The T_DHW_Out sensor does not need to be connected. 12.9.2 DHW S ; DHW TORAGE WITH SENSOR MODE Mode 1: DHW is prepared by warming up a store. Either a DHW pump or 3-way valve can be used to switch to DHW mode.
  • Page 77: Dhw Storage With Thermostat; Dhw Mode 2

    12.9.3 DHW S ; DHW TORAGE WITH THERMOSTAT MODE In this mode DHW is prepared by warming up an indirect tank. Either a DHW pump or 3-way valve can be used to switch to DHW mode. The temperature of the DHW in the indirect tank is regulated by a thermostat/aquastat (instead of a sensor), which should provide only an open/closed signal to the controller.
  • Page 78 When DHW Mode 1 is selected the boiler setpoint will be at Anti_Legionella_Setpoint plus DHW_Store_Supply_Extra, If the supply temperature drops below the Boiler_Setpoint the boiler is started as well. The boiler is PID controlled towards the Boiler_Setpoint. When the supply temperature rises above Boiler_Setpoint plus DHW_Supp_Hysterese_Up the boiler is switched OFF.
  • Page 79: Display Menu Structure Summary

    12.9.6 D ISPLAY MENU STRUCTURE SUMMARY Access Description: Menu structure Display: level 1. Central Heating (CH) User Enter the Central Heating (CH) menu 2. Domestic Hot Water (DHW) User Enter the Domestic Hot Water (DHW) menu 3. Information User Enter the Information menu 4.
  • Page 80 3.2 Boiler status min. max. Default unit Access Description: level Flow Temperature °C User Actual supply flow temperature Flow 2 Temperature °C User Actual supply 2 flow temperature Return Temperature DHW Temperature °C User Actual DHW temperature DCW Temperature °C User Actual DCW temperature Outside Temperature...
  • Page 81 4.1 General settings min. max. Default unit Access Description: level 4.1.1 Language User Enter the Language menu 4.1.2 Unit Type User Enter the Unit Type menu 4.1.3 Date & Time User Enter the Date & Time menu 4.1.4 Cascade Mode User Enter the Cascade Mode menu 4.1.5 Other Settings...
  • Page 82 4.1.4 Cascade mode min. max. Default unit Access Description: level Full Full Full Installer Select full cascade mode for more data for max 8 boilers Basic Installer Select basic cascade mode for 9 to 16 boilers 4.1.5 Other settings min. max.
  • Page 83 4.2.1 Boiler parameters min. max. Default unit Access Description: Dis- play level CH mode Installer Set the CH mode CH Setpoint Installer Set the CH setpoint ⁰C Calc. Setp. Offset Installer Set the offset for CH mode 1 / 2 ⁰C calculated setpoint Boiler Pump Overrun...
  • Page 84 Installer factor DHW On Off Period sec. Installer Set the on/off modulation period PreHeat mode Installer Set the PreHeat Eco mode PreHeat Eco Setpoint ⁰C Installer Set the PreHeat Eco setpoint DHW Max. Limit Installer Limiting DHW setpoint max. ⁰C DHW Min.
  • Page 85 4.2.2 Module Cascade Set- min. max. Default unit Access Description: Dis- tings level play Burner Address Stand Installer Set the cascade burner address alone Permit Emergency Mode Yes/N Installer Enable/disable the cascade emer- gency mode Emergency Setpoint °C Installer Set the emergency mode setpoint Delay Per Start Next Mod.
  • Page 86 4.2.3 Boiler Cascade Settings min. max. Default unit Access Description: Dis- level play Boiler Address stand Installer Set the cascade boiler address alone Permit Emergency Mode Yes/No Installer Enable/disable the cascade emergency mode Emergency Setpoint °C Installer Set the emergency mode set- point Delay Per Start Next Blr 1275...
  • Page 87: Temperature Protection

    13 TEMPERATURE PROTECTION The difference between Supply temperature and Return Temperature is continuously monitored. A too big differ- ence can indicate a defective pump or a clogged heat exchanger. To protect the boiler, the burner controller re- duces the input when the temperature difference ΔT becomes too high: At maximum boiler input ΔT is limited to 35°C (63 °F) - (Hx_Diff_DeltaT_Min ) In between 35°C (63 °F) and 43 °C (77 °F) boiler input modulates between minimum and maxi- mum.
  • Page 88: Error Information

    14 ERROR INFORMATION. Errors can be divided in three groups: • Manual reset locking errors (can only be reset by the reset button). • Blocking errors (will disappear when error is gone) • Warnings (will disappear when the warning is gone, not stored in the BCU) The boiler pump will continue to run during most locking and blocking error codes.
  • Page 89: Lockout Codes

    14.3 Lockout codes Lockout Error Description Cause Solving code E2PROM_READ_ERRO wrongly programmed reset BCU or replace BCU and Internal software error BCU or PB or display unit Five unsuccessful ignition no gas, wrongly check gas supply and adjust IGNIT_ERROR attempts in a row adjusted gas valve gas valve, reset BCU short circuit in coil of the...
  • Page 90 Lockout Error Description Cause Solving code wrongly programmed reset BCU or replace BCU and STACK_ERROR Internal software error BCU or PB or display unit wrongly programmed reset BCU or replace BCU and INSTRUCTION_ ERROR Internal software error BCU or PB or display unit wrongly programmed reset BCU or replace BCU and...
  • Page 91: Blocking Codes

    14.4 Blocking codes Lockout Error Description Cause Solving code WD_ERROR_RAM Internal software error wrongly programmed reset PCB or replace PCB and PCB or PB or display unit WD_ERROR_ROM Internal software error wrongly programmed reset PCB or replace PCB and PCB or PB or display unit WD_ERROR_STACK Internal software error...
  • Page 92 Lockout Error Description Cause Solving code FLUE_OPEN Flue sensor open malfunctioning flue check connection to PCB or sensor or not con- check resistance NTC sensor nected OUTDOOR_OPEN Outdoor sensor open malfunctioning outdoor check connection to PCB or sensor or not con- check resistance NTC sensor or nected or wrong CH- change CH-mode...
  • Page 93: Warnings

    14.5 Warnings Error no. Error Description Cause Solving CC_LOSS_COM- Cascade System: Managing cas- connection between cas- Check wiring between boiler or MUNICATION cade control lost communication caded boilers is interrupted distance between boilers is to with one of the depending. or wiring is broken APP_SELEC- Unknown appliance model se-...
  • Page 94: Cascading

    15 CASCADING 15.1 System setup NOTE: for proper functioning of the system, some settings have to be changed, see § 15.4.2 "Emergency mode". The boiler controller can control multiple boilers in a cascade setup. A system sensor is necessary to measure the cascade system supply temperature. The sensor is connected to the boiler controller.
  • Page 95: Boiler Cascade Communication Setup

    Select correct CH mode on managing boiler only Parameter: Menu - Settings - Boiler settings - Boiler parameters - Parameter 1 (CH mode) CH mode 0 – Central Heating demand with thermostat control CH mode 1 – Central Heating with an outdoor temperature reset and thermostat control CH mode 2 –...
  • Page 96: Setting Of The Cascade Parameters

    The managing boiler of the cascade system is connected to the AL-BUS connection on terminals 20-21 This connection also provides the power for the communication bus. The depending boilers are all parallel con- nected to the managing boiler communication bus. The bus power is provided by the managing boiler on terminals 20-21, switch S1 must be set in the OFF position (all controls).
  • Page 97: Cascade - Heating Only Managing Boiler

    15.3.3 C – H ASCADE EATING ONLY ANAGING BOILER When a boiler is set as "Managing" (parameter 184: "Burner address"), the controller of this boiler will drive the cascade. The CH mode of this managing boiler applies to all other boilers. It is only required to set the CH mode on the managing boiler.
  • Page 98: Cascade - Boiler Rotation

    15.3.6 C – B ASCADE OILER ROTATION The boiler rotation function can change the start/stop sequence for the cascade boilers. The parameter Boiler_Rotation_Interval sets the number of days after which the sequence is updated. When Boiler_Rotation_Interval is set to 0 boiler rotation is disabled. When the parameter Burner_Rotation_Interval is updated the boiler rotation days left will be initialized to the new Burner_Rotation_Interval setting.
  • Page 99: Emergency Mode

    15.4.2 E MERGENCY MODE Managing boiler error When the managing boiler is in error mode, the depending boilers can go into the "Emergency_Mode", if enabled. In emergency mode the system setpoint is set to the temperature of the Emergency_Setpoint and all cascaded boilers start burning on this setpoint.
  • Page 100: System Test

    16 SYSTEM TEST. For testing the system at fixed power rates, a system test can be activated via the Installer menu. Via the system test the boiler can be started without CH or DHW being present. The system test has priority. The following modes are available: Description System test mode...
  • Page 101: Commissioning The Boiler

    17 COMMISSIONING THE BOILER 17.1 First: flushing the boiler with water After installation of the boiler the first step, before commissioning, is to flush the boiler and the whole heating installation with fresh water to remove pollution, debris and other materials that might cause a blocking. This must also be done with heating installations, where only the boiler is replaced.
  • Page 102: Mounting Condensate Trap

    17.4 Mounting Condensate Trap When mounting the bottom part of the condensate trap, before commissioning the boiler and/or after maintenance, it must ALWAYS be completely filled with water. This is a safety measure: the water in the condensate trap keeps the flue gases from leaking out of the heat exchanger via the condensate drain.
  • Page 103: Adjusting And Setting The Boiler

    18 ADJUSTING AND SETTING THE BOILER Before carrying out any adjusting of the burner, carefully read this complete chapter. The initial lighting of the appliance must be performed by a licensed Gas Technician. Fail- ure to follow these instructions may result in property damage, serious injury or death. As soon as the appliance has been fully installed (with regard to hydraulics, filling and de- WARNING aeration of installation, gas, flue gas, air intake, wiring etc.) according to the preliminary...
  • Page 104: Setting Screws Venturi- And Gas Valves: Drawings

    18.1.2 S ETTING SCREWS VENTURI AND GAS VALVES DRAWINGS Location of the setting screws: Gas pressure High Fire: nipple [3] screw [2] Low Fire: screw [1] High Fire: venturi adjustment screw: use hex key 4 mm (5/32 Allen wrench) High Fire: screw [2] Low Fire: gas valve adjustment screw: Torx T40.
  • Page 105: Adjustment Procedures

    18.2 Adjustment procedures Procedure 1: adjust at High Fire Carry out the next steps: . → "Central Heating/ Information/ Settings/ System Test" 1. From status screen, press MENU 2. Press UP/DOWN ↑↓ to select "System Test" Press CONFIRM 3. Password needed to continue →...
  • Page 106: Conversion From Natural Gas To Propane

    Before starting conversion: close the gas supply and switch off the electrical power! WARNING! Use only parts/conversion kits obtained from Required parts: (Installation Manual “Accessories”) Eco Heating Systems Groningen B.V. and intended to Propane orifice CB 85 and CB 105 be used with this particular boiler. Propane orifice CB 125 Every conversion kit is provided with instructions how to assemble the kit to the boiler.
  • Page 107 3. Set parameter 92 and 93 The fan speed has to be changed in the software of the boiler according to the tables below:. Boiler type fan speed high fire Fan speed low fire parameter 92 parameter 93 CB 85 6500 1850 Internal...
  • Page 108: Start Up Checklist

    Serial number sales@ecohs.nl or send a copy Installation date to address: Cascade installation (Y/N) (YES/NO) Eco Heating Systems. Number of boilers P.O. Box 5145 Type of boilers in cascade 9700 GC Groningen The Netherlands Venting information Direct vent or using combustion air from indoor?
  • Page 109 Water circulation & temperature regulation (for DHW) Piping diameter Total length of straight pipe between boiler & tank Number of elbows Number of tees Temperature rise between inlet and outlet after 5 min. cold-start operating max. power °C / °F Water temperature setpoint Test of Water Flow Switch (DHW)? (Yes/NO)
  • Page 110: Inspection, Maintenance And Service

    19 INSPECTION, MAINTENANCE AND SERVICE. 19.1 General For a good, safe and long-time operation of the boiler and to maintain warranty it is mandatory to carry out in- spection, maintenance and service on the boiler at least once a year and/or after 2000 burning hours maximum, whichever comes first.
  • Page 111 Water leakage The water pressure of the heating installation must be more than 1.0 bar (21 psi) and at a maximum of 6.0 bar (87 psi) in normal operation. When the water pressure drops below the minimum occasionally, there might be a water leak.
  • Page 112 Burner Check the burner surface to see if it has damages, signs of rust and/or cracks. When the burner surface is dam- aged the burner must be replaced. The burner can be cleaned by using a soft (non-metallic) brush. The dust can be removed with a vacuum cleaner or pressurized air.
  • Page 113 Fiber braid replacement If the high temp braided rope is damaged and needs to be changed, it has to be replaced by new braids using the method described below. The high temp braided rope is maintained by silicone glue. - Remove electrodes. - Remove the braids by sliding under the periphery a thin tool to loosen the braids and remove it.
  • Page 114 Insulation The insulation of the heat exchanger (located on the rear wall inside the heat exchanger and burner door) must be inspected. If this insulation disc shows any signs of (water) damage or degradation it must be exchanged. Also check if there are any indications in the burner room of a high condensate level (caused by a blocked condensate trap) that might have wetted the rear wall insulation.
  • Page 115 Install the new insulation: - put two dots of glue silicone, temperature-resistant (Loctite 5366 or Ot- toseal S17), according to the location indicated. - make sure that the burner is in proper condition, remove any possible insulation residues on the burner - put a plastic protection skirt around the burner to protect the insulation from the burner.
  • Page 116: Mounting The Burner Door

    Gas/air ratio With every service check and/or maintenance of the boiler always check the gas/air ratio by measuring the CO percentage (flue gas) at the maximum and minimum load of the boiler. If necessary, adjust these values. See for information chapter “Adjusting and setting the boiler” chapter 18. Pump (supplied separated from the boiler) Check the electrical parts and the motor of the pump for a correct functioning.
  • Page 117: Maintenance Checklist

    19.3 Maintenance Checklist Allowing the boiler to operate with a dirty combustion chamber will hurt operation. Failure to clean the heat exchanger as required by the manual and dictated by the operating location could result in boiler failure, property damage, personal injury, or death. WARNING Such product failures ARE NOT covered under warranty Periodic maintenance must be performed once a year by a qualified service technician to assure that all the...
  • Page 118: Installation Examples

    21 INSTALLATION EXAMPLES The following schematics present several examples of heating installations: All schematics are purely functional. Safety components, bypass, control devices and so on must be added conform all ap- plicable standards and regulations. WARNING 21.1 System Example 1 Low Voltage Connections BOILER Name...
  • Page 119: System Example 3

    21.3 System Example 3 Low Voltage Connections BOILER Name Wire terminal HEATING Room thermostat 12-13 ZONE outdoor temperature sensor flow temperature sensor low loss header High Voltage Connections boiler pump 4-PE-5 System heating pump 6-PE-7 21.4 System Example 4 Low Voltage Connections Name Wire terminal BOILER...
  • Page 120: System Example 5

    21.5 System Example 5 Low Voltage Connections BOILER Name Wire terminal HEATING Room thermostat 12-13 ZONE flow temperature sensor outdoor temperature sensor Tank thermostat or sensor low loss header DHW indirect Tank non-return valve (low resistance type) High Voltage Connections boiler pump 4-PE-5 HWS primary pump...
  • Page 121: System Example 7

    21.7 System Example 7 BOILER 1 BOILER 2 BOILER 3 BOILER 4 managing depending 1 depending 2 depending 3 HEATING ZONE Low Voltage Connections Name Wire terminal Room thermostat 12-13 outdoor temperature sensor flow temperature sensor Tank thermostat or sensor DHW indirect Tank non-return valve (low resistance type) low loss header...
  • Page 122: Spare Parts

    22 SPARE PARTS 22.1 CB 85, CB105 and CB 125 Exploded view E93.1605.901 CB CH manual...
  • Page 123 E93.1605.901 CB CH manual...
  • Page 124: Cb 155 Exploded View

    22.2 CB 155 Exploded view E93.1605.901 CB CH manual...
  • Page 125 E93.1605.901 CB CH manual...
  • Page 126: Part Numbers Cb 85-155

    22.2.1 P CB 85-155 ART NUMBERS Description * Part number: CB 85 CB 105 CB 125 CB155 Set. Universal maintenance kit CB 85, 105, 125 2 S000.500.001 Set. Universal maintenance kit CB 155 2 S000.500.003 Set. Electronics holder S000.500.002 Set. Anchoring bar CB 85 S000.500.007 Set.
  • Page 127 Description Part number: CB 85 CB 105 CB 125 CB 155 Spring plunger 8mm S006.500.006 EPDM sealing for EBM 957 S006.500.007 Offset piece CB 85 S008.500.001 Offset piece CB 105 S008.500.010 Offset piece CB 125 S008.500.006 Seat check valve CB 85, 105, 125 S008.500.002 Seat check valve CB 155 S008.500.013...
  • Page 128 Description Part number: CB 85 CB 105 CB 125 CB155 Gasket malleable coupling CB 85, 105, 125 S032.500.005 Gasket malleable coupling CB 155 S032.500.018 Gasket Condensate drain/bottom plate S032.500.006 EPDM seal 15x5 self adhesive L=5m S032.500.007 Silicone seal 13x5 self adhesive L=10m S032.500.008 EPDM seal 15x6 self adhesive L=5m S032.500.009...
  • Page 129: User's Part

    23 USER’S PART. This section is written for the user Eco Heating Systems is not accountable for any damage caused by incorrect following these instructions. For service and repair purposes use only original Eco Heating Systems spare parts. All documentation produced by the manufacturer is subject to copyright law.
  • Page 130: Display And Buttons

    23.5 Display and buttons On / off switch. Switches electrical power to the boiler Connector for computer cable Reset lockout error Main Menu Escape / Return to the status overview Right Enter a menu item or confirm selection in Status overview (when directly setting Actual setpoint or DHW setpoint) Left Return to previous menu item or Status overview...
  • Page 131: Screens And Settings

    23.6 Screens and settings This screen is active during power up and will remain active until communication with the Main Control (the AL-BUS) has been established. After communication has been established the following Status overview appears: The Status overview has the three different sections that show specific information: Header Middle section Footer...
  • Page 132: Starting The Boiler

    Footer Shows Error/Warning messages when an Error or Warning is set in the Main Control, otherwise a quick menu is displayed where the user can quickly edit setpoints and enable/disable CH or DHW. Quick Menu / Parameter Description Value / User Unit level...
  • Page 133: Changing The Setpoint And/Or Enabling Ch/Dhw

    23.8 Changing the Setpoint and/or Enabling CH/DHW. This can be done directly via the Status overview (as shown above) or via the MENU. When CH is active, you can adjust the Actual setpoint directly on the bottom of the Status overview. When DHW is active, you can adjust the DHW setpoint directly on the bottom of the Status overview.
  • Page 134: The Menu (Button)

    23.9 The MENU (Button). Enter the menu by pressing the MENU button once. The header in the screen shows you are inside the main menu. Whilst scrolling through the menu you will see that the selected menu item is shown in a white rectangle. At the right, there will be an icon shown, depending on the selected item.
  • Page 135: Central Heating (Ch)

    23.11.1 C (CH) ENTRAL EATING Menu / Parameter Description Value / Unit CH Setpoint Set the CH setpoint °C/°F Outdoor reset Enter the Outdoor Reset menu 23.11.2 D (DHW) OMESTIC ATER Menu / Parameter Description Value / Unit DHW Setpoint Set the DHW setpoint °C/°F DHW Store Setpoint...
  • Page 136: Service

    23.11.8 S ERVICE Menu / Parameter Description Value / Unit Service history Display the service history Burn hours since last service Display the burn hours since last service hrs. Burn hours till service Display the hours remaining until next service hrs.
  • Page 137: Cascade Mode

    23.11.16 C ASCADE MODE Menu / Parameter Description Value / Unit Full Select full cascade mode Basic Select basic cascade mode Note: for proper functioning of the cascade system, some settings have to be changed, see § 15.4.2 "Emergency mode" 23.11.17 O THER ETTINGS...
  • Page 138: Service Reminder

    23.14 Service reminder The Service reminder will remind the owner/user of the appliance to service the appliance at a specified "Service_Interval", factory set on 2000 burn hours. When service is not done within this time, a service reminder will be shown on the screen: "Service is required!", alternating with the normal status display. NOTE: with the message "Service is required"...
  • Page 140 Your distributor: Eco Heating Systems Groningen B.V. P.O. Box 5145 9700 GC Groningen Rigaweg 10 9723 TH Groningen The Netherlands +31 (0)50 5470470 sales@ecohs.nl www.ecohs.nl...

This manual is also suitable for:

Cb 105 chCb 125 chCb 155 ch

Table of Contents