Electrical Installation and Operating Instructions -
Safety 
1.0  
Before  installing,  check  the  Model  Number  and  verify  compatibility  to  the  process  media  and 
temperature  in  contact  with  the  wetted  parts.    Incompatible  media  and  /  or  operation  at 
temperature extremes  can cause premature degradation of materials which could result in safety 
risk to personnel.   
Verify  the  selected  pressure  range  (differential  pressure  and  working  pressure)  and  the  switch 
ratings are within specification for your application. 
Warning!  
The Model 140 product utilizes a diaphragm design which isolates the high process from the low 
process.    For  over  pressure  conditions  (High  over  Low  and  Low  over  High)  the  diaphragm  is 
supported  at  the  end  of  travel  for  the  rated  working  pressure  of  the  gauge.    However,  it  is 
recommended that if large pressure spikes exist, some sort of pressure limiting device should be 
installed for protection.  
Warning! 
precautionary measures when removing and transporting the product.
Warning! 
process connection are leak tight. Leakage within a pressure tight (ie NEMA 4X) enclosure could 
cause a pressure buildup within the enclosure and cause a burst scenario. 
Intended use 
1.1
 
The  indicating  /  non‐indicating  differential  pressure  switches  or  transmitter  are  used  for  monitoring 
differential pressures in industrial applications.  
The manufacturer shall not be liable for any claims if the product is used in applications contrary to the 
intended use. 
Personnel 
1.2
 
Personnel installing and putting this instrumentation into service shall be suitably trained and qualified in 
accordance with local codes, practices and regulations.  
Labeling / Marking 
1.3
 
The following Electrical Configurations bear this mark and comply with the relevant European Directives 
identified on the declaration of conformity:  A, B, E, F, T, W 
The  following  electrical  configurations  bear  1  or  both  of  these  third  party  listing  agency  marks  for 
product evaluated to both US and Canadian Standards:  E, F, W 
 
®
Instrument
  Perform all electrical adjustments with power removed.   
Remaining media may result in a risk to personnel, environment etc.  Use sufficient 
If installing product within another enclosure that is pressure tight, please verify all 
6 5 0 0   d o b r y   d r   s t e r l i n g   h e i g h t s ,   m i     4 8 3 1 4
Bulletin No: Elec IM140/18A
Supersedes Elec IM 140/16B
Model 140
 
 
 

Advertisement

loading
Need help?

Need help?

Do you have a question about the 140 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mid-West 140

  • Page 1 ® Bulletin No: Elec IM140/18A Mid-West Instrument Supersedes Elec IM 140/16B Model 140 Electrical Installation and Operating Instructions - Safety  1.0   Before  installing,  check  the  Model  Number  and  verify  compatibility  to  the  process  media  and  temperature  in  contact  with  the  wetted  parts.    Incompatible  media  and  /  or  operation  at ...
  • Page 2: General Specifications

    Model 140 Electrical Installation and Operating Instructions -  General Specifications          Non‐electrical  Limits         Parameter  Limits(Std)  (Hazardous Locations)   1500 (Br Non End)  3000 (AL)* Non Haz‐Loc  3000(Al/SS Non End)    Working Pressure(PSI)  1500 (Br)  Non Haz‐Loc     2000 (AL/SS End Conn.)  3000 (SS)* Non Haz‐Loc  1625 (Al/SS Nace)  Proof Pressure  4X Rated Working Pressure  ‐40° to 200° F (Switches)  Temperature    -20 F to 150 F (Transmitter) Differential Pressure Range ...
  • Page 3: Product Description

    The  rotation  of  the  follower  magnet  causes  the  pointer to track the movement of the internal magnet and indicate the differential pressure on the dial  scale. The switches are also magnetically operated and are located outside of the pressure housing.  The  switches  are  mechanically  adjustable  allowing  the  customer  to  set  the  switch  within  a  defined  adjustment span of the range of the instrument.  Transmitter  The  Model  140  indicating  /  non‐indicating  differential  pressure  transmitter  is  a  2  wire  loop  powered  microprocessor based 4‐20 ma transmitter.   The magnetic angle sensor & electronics senses the angle  (relative to the transmitter sensor) of the magnet which moves linearly in the bore.  Each transmitter is  individually calibrated to the gauge using  an 11 point calibration linearization technique.  This method  results in a <2% full scale accuracy for the upper 80% of the range.   ...
  • Page 4: Installation

    Model 140 Electrical Installation and Operating Instructions -   4.0    Installation:  Mechanical Connections  ¼”  FNPT  are  provided  standard,  however  check  your  paperwork  to  confirm  the  connections  ordered.   There  are  2  connections  identified  on  the  gauge  body  as  “Hi”  and  “Lo”  for  High  pressure  and  Low ...
  • Page 5 Model 140 Electrical Installation and Operating Instructions -     Pipe Mounting  Pipe  mounting  brackets  are  not  available  for  any  Electrical  Configurations  in  the  reverse  port  configuration.    Typical 2” Pipe Mounting          5.24 6.22       1.16   2.81  ...
  • Page 6 Model 140 Electrical Installation and Operating Instructions -       45°    Ø3.00 (76.2)  Typical 2 ½” Panel Mount  3.30    Ø3.50 (88.9)      3.39  Ø0.19 (4.7)  (4 HOLES)        Ø5.30 (134.6)    1.10 Typical 4 ½” Panel Mount   Ø5.63 (143.0) BOLT CIRCLE       Ø0.19 (4.7) (4 HOLES) 5.30...
  • Page 7 Model 140 Electrical Installation and Operating Instructions -        Electrical:   Warning:   Electrical  connections  should  be  performed  by  qualified  personnel  and  meet  the  representative country's national electrical code.  Warning:  Failure to connect to the protective conductor terminal may result in a shock hazard.  Warning:  Perform  all  switch  adjustments  with  power  removed.  Use  an  ohmmeter  or  equivalent  to ...
  • Page 8 Model 140 Electrical Installation and Operating Instructions -   The reed switch(es) are located inside the  enclosure, on the top of the pressure housing (standard port) , and  are connected to a 7 position terminal strip.  An opening is provided at the rear of the enclosure for a 1/2"  flexible weather‐proof cable or conduit connector (supplied by customer) (A & B Electrical Configuration) or a  ½”  FNPT  conduit  interface  (E  &  F  Electrical  Configuration).    Upon  request  the  hole  may  be  sized  to  accommodate a PG‐11 cable gland connector.     To  access  the  terminal  strip  remove  the  switch  enclosure  cover  by  removing  the  (4)  screws.    Insert  wires ...
  • Page 9 Model 140 Electrical Installation and Operating Instructions - Intended use:   The Model 142 Transmitter is intended for use in  General Purpose Locations (T electrical configuration) or  Division 2 hazardous locations (W electrical configuration).  In both cases the enclosure carries a NEMA 4X  IP65 environmental rating.    Description:  The transmitter assembly if CE marked is also compliant with EMC Directive 2004/108/EC.  The transmitter   has a factory programmed low‐pass filter. The filter is set to approximately 1 second.  This can be increased  or decreased upon customer request at the time of order.    Note: The transmitter circuitry senses the position of a magnet.  Any magnetic object located near the gauge  may affect transmitter accuracy.  The transmitter if necessary can be zeroed by jumpering pin 2 to Gnd pin 1 momentarily for 2 seconds (with  the unit powered). In most cases this will never be necessary as the transmitter is programmed to generate a  4ma output for the first 4% of the FSR .    Warning:    If zeroing in the Hazardous Location environment use a switch approved for that location.    Caution:    Do  not  zero  the  transmitter  with  pressure  applied.    Otherwise  your  product  will  have  a ...
  • Page 10 Model 140 Electrical Installation and Operating Instructions -   Warning:  When wiring to the terminal strip, make sure all wire strands are contained within  the terminal connection.  The maximum loop resistance is 1000 ohms (@ 28Vdc Input).  Use the following formula to determine the  maximum loop resistance at other input voltages:  ((Vs – 8) *1000)/ 20)   (Transmitter) Electrical Configuration W:   The  W  Electrical  Configuration  is  3   party  certified  for  Class  I,    Division  II,  Groups  A,  B,  C,  &  D,  Class  II,  Groups  F  &  G  hazardous  environments.      The  CSA  mark  identifies  the  product  has  been  tested  to  the ...
  • Page 11 Model 140 Electrical Installation and Operating Instructions -  Dimensions (cont.)  Electrical Configuration: E or F    Electrical Configuration: A or B  NEMA 4X METAL ENLOSURE CLASS I, DIV. 2, GROUPS A, B,  NEMA 4X 2 ½ INCH DIAL  C,D CLASS II, DIV 2, GROUPS F & G                          2 ½” DIAL        Electrical Configuration: A or B    NEMA 4X 4 ½ INCH DIAL             ...
  • Page 12 Model 140 Electrical Installation and Operating Instructions -   7.0 Troubleshooting  A.    Gauge accuracy and set point problems:    i. Verify your process connections are plumbed properly    ii. Verify gauge is not in an electromagnetic / magnetic environment.  i.e.; close proximity to high current  power lines.    iii. Verify the pointer has fluid movement as pressure increases.  No movement may indicate a blown  diaphragm.    iv. All others contact the factory for assistance.    B    Switch doesn't function    i. Make sure that the switch load does not exceed the specified wattage rating of the switch. (steady‐state  and transient). Contact factory for assistance for excessive loads, otherwise proceed to the next step.    ii. Perform a continuity check of the switch contacts by trying to actuate the switch using an external     magnet. An operational  switch usually indicates a problem with the gauge.  If not operational proceed ...
  • Page 13 Model 140 Electrical Installation and Operating Instructions -   Pressure Equipment Directive :  The Pressure Equipment Directive has been determined to be non‐applicable for CE marking for Group 1  applications below 200 bar or Group 2 applications below 1000 bar..  These products are manufactured in  accordance with article 3, paragraph 3 of the directive, “sound engineering practice”.  They fall below  category I for non‐hazardous gases, hazardous liquids, & non‐hazardous liquids.  This product also falls below  category I for hazardous gases at or below 200 bar.     EMC Directive(2004/108/EC):  Optionally, transmitters (Electrical Configurations T & W) may be CE marked for compliance with the EMC  Directive 2004/108/EC.  The transmitter design has been evaluated to and passed the following “EN”  Standards as they relate to the EMC directive.    EN 61326:2013 Environment Industrial, Electrical Equipment for measurement, Control and Laboratory use, EMC requirements from which: EN55011:2009 + A1:2010 Emission, Class B...