Page 2
RAISING INDIVIDUAL, FAMILY, AND COMMUNITY STANDARDS WHILE REVOLUTIONIZING THE AGRICULTURAL INDUSTRY. FOR THE MOST UP TO DATE SERVICE INFORMATION VISIT: www.StaheliWest.com/customer FOR SERVICE ASSISTANCE, CONTACT YOUR LOCAL DEALER...
Page 3
2010-2014 DewPoint 6110 Troubleshooting Guide This manual is intended to be used with software version 2.6 or later installed on the DewPoint 6110 machine See DewPoint 6210 Owners Manual • • Operator Training Operation • • Warranty Information Winterization •...
Contents Informational Fault 201: Turn Burner Switch ON ........... 44 Fault 202: Operating Pressure Control Components Location List ............... VI Switch (OPLS) is tripped ..........44 Diagram 1 Full Machine ..............1 Fault 203: Boiler Water Level is high ..........45 Diagram 2 Boiler Components ............
Page 5
Contents Fault 402: Faulty PLC Input Card ............59 Test 106: Intermittent Pilot Flame Test ..........78 Fault 403: Boiler water level higher than Test 108: HPLS Calibration [15 PSI] ..........79 set point / Boiler overflowing ......... 60 Test 109: OPLS Calibration [14.5 PSI] ..........80 Fault 404a: Bottom rear work lights will not turn on ......
Diagram 9 Hot Water Circulation Mixed Water Isolation Valve Cold Water Feed Water Boiler Drain Circulation Feed Water Drain Valve Valve Isolation Valve Actuator Supply Water Isolation Valve Supply Water Feed Water Circulation Supply Water Filter (T-Strainer) Pump Fill Valve Pump *All valves are shown in normal operating positions...
Diagram 10 Water Temperature Switch Glow Plugs Air Filter Radiator Oil Cap Generator End Oil Filter Oil Dipstick Fuel Fuel / Water Oil Pressure Solenoid Separator Switch...
Sensors *Same fill color = interchangeable Normal Sensor Function/Range Trip/Alarm Options Pin Out Range 4-20mA Disable in Settings > Alarm Supply Water Level 0-1000 gallons Below 200 gallons Status Screen 4-20mA Disable in Settings > Alarm Fuel Supply Level 0-300 gallons Below 30 gallons Status Screen Disable in Settings >...
Page 24
Sensors *Same fill color = interchangeable Normal Sensor Function/Range Trip/Alarm Options Pin Out Range 4-20mA Selectable and differential More than 2 PSI Steam PSI 1 -14.7 to 30 PSI 6-13 PSI limit adjustable in Settings differential > Boiler Pressure Screen 4-20mA Selectable and differential More than 2 PSI...
Page 25
Sensors *Same fill color = interchangeable Normal Sensor Function/Range Trip/Alarm Options Pin Out Range Low Fire 80 PSI Fuel Nozzle PSI Gauge 0-400 PSI High Fire 160-190 PSI 4-20mA Black Wire = 24v White Wire = 4-20mA Disable in Settings > Alarm Status Screen Flue Temperature 0-1000°...
Burner Nozzle Sizes Choosing the right size burner nozzle can significantly improve a machine’s performance. The higher the elevation, the smaller the nozzle size should be. The number refers to how many gallons per hour the nozzle sprays Less More Steam Output Suggested Case by Case...
Actuators Top Front Steam Valve Actuator Top Rear Steam Valve Actuator 1. GND Bottom Front Steam Valve Actuator 2. 4-20mA Actuators are interchangeable Bottom Rear Steam Valve Actuator 3. GND Connections are interchangeable Feed Water Valve Actuator 4. 12v Blow Down Valve Actuator A.
Fuses Panel 2 Panel 2 Component Top Front Steam Valve Top Rear Steam Valve Bottom Front Steam Valve Bottom Rear Steam Valve Steam/Water Purge Feed Water Valve BlowDown Valve Panel 3 Panel 3 Component 12v to Actuators, Work Lights 12v to Power Regulator 12v to Generator Start/Stop 12v to 24v Power Regulator 24v to F6...
Circuit Breakers Main Circuit Breaker The Main Circuit Breaker is located on the pas- senger side of the generator behind the generator controller. The breaker needs to be turned ON to be able to operate the machine. 2010 2011-2013 2014 Panel 1 Circuit Breakers Panel 2 Circuit Breakers Feed...
Faults Fault 1: No Purge Card The Honeywell Burner Controller is not detecting a Purge Card (Panel 1) Causes Troubleshooting Fixes • No Purge Card Installed • Check for Purge Card • Install Purge Card • Bad Purge Card • Replace with new Purge Card •...
Faults Fault 15: Flame Detected (Standby) Indicates that a flame has been detected when there should not be a flame Causes Troubleshooting Fixes • Put out the flame • Check for burning/smoldering debris inside • Flame in Boiler • Remove flame source the boiler •...
Faults Fault 17: Main Flame Fail Indicates that the flame detector cannot detect flame during run mode (low fire/high fire) Causes Troubleshooting Fixes • Replace Flame Detector (check other causes • Faulty Flame Detector • Perform “Test 101” before buying a new component) •...
Faults Fault 18: Flame Detected (Pre-Purge) Indicates that a flame has been detected when there should not be a flame Causes Troubleshooting Fixes • Put out the flame • Check for burning/smoldering debris inside • Flame in Boiler • Remove flame source the boiler •...
Faults Fault 19: Main Flame Ign Indicates flame was lost during the first 10 seconds of the RUN state Causes Troubleshooting Fixes • Replace Flame Detector (check other causes • Faulty Flame Detector • Perform “Test 101” before buying a new component) •...
Faults Fault 20: Low Fire SW Off / Purge Hold T18 Low Fire Switch (See Fault 223) Indicates that the Louver is not closing during the purge cycle or that the signal from the Low Fire Switch is not reaching the Honey- well Burner Controller Causes Troubleshooting...
Faults Fault 28: Pilot Flame Fail (Page 1 of 2) Indicates a failure in either the ignition system or the safety system that detects the pilot flame IMPORTANT: Perform “Test 101” first to determine whether or not a pilot flame is present Causes Troubleshooting Fixes...
Page 46
Faults Fault 28: Pilot Flame Fail (Page 2 of 2) Indicates a failure in either the ignition system or the safety system that detects the pilot flame IMPORTANT: Perform “Test 101” first to determine whether or not a pilot flame is present Causes Troubleshooting Fixes...
Faults Fault 29: Lockout ILK (Airflow Switch / VFD) (Page 1 of 2) Indicates that the VFD/fan motor did not turn on or the airflow switch did not detect the fan air moving Causes Troubleshooting Fixes • Clean out aluminum tubes •...
Faults Fault 29: Lockout ILK (Airflow Switch / VFD) (Page 2 of 2) Indicates that the VFD/fan motor did not turn on or the airflow switch did not detect the fan air moving • Adjust the load to between: %25 - %50 •...
Faults Fault 200: High Pressure Limit Switch (HPLS) is tripped The High Pressure Limit Switch shuts off the burner anytime it is tripped; it trips anytime boiler pressure is over 15 PSI Causes Troubleshooting Fixes • Have you performed a wet layup recently •...
Faults Fault 201: Turn Burner Switch ON Indicates that the burner is not getting 120v power Causes Troubleshooting Fixes • Burner Door Switch is “OFF” • Turn the switch to “ON” • Circuit Breaker B6 is tripped (Panel 1) • Reset the circuit breaker •...
Faults Fault 203: Boiler Water Level is high • See Fault 303: Boiler water level higher than set point / Boiler overflowing Fault 204: Pilot Propane Level is low Indicates that the propane level count is down to 5 remaining lights (this can often be inaccurate) Causes Troubleshooting Fixes...
Faults Fault 207: Pressure Differential Alarm Indicates that the two steam pressure sensors are reading more than 2 PSI (default setting) apart from each other *Bad steam pressure sensors can damage input cards and PLC’s, they can also cause max readings for all inputs on card 1 on the PLC ** If the PLC or input card are replaced before a possible faulty steam pressure sensor is replaced, the steam pressure sensor can damage the newly replaced components.
Faults Fault 208: Flue Temp is High Indicates flue temperature is above 600° F *Bad Flue temperature sensors can damage input cards and PLC’s, they can also cause max readings for all inputs on card 1 on the PLC ** If the PLC or input card are replaced before a possible faulty flue temp sensor is replaced, the faulty flue temp sensor can damage the newly replaced components.
Faults Fault 209: Feed Water and Boiler Water Temp. Differential limit has Exceeded Indicates that the difference in temperature between the feed water temperature sensor and the boiler water temperature sensor is more than 150° F Causes Troubleshooting Fixes • Flush Y-Strainer by opening for 3 seconds under steam pressure •...
Faults Fault 210: Ambient Temperature is High Indicates that the ambient temperature is above the alarm set-point (default 100° F) Causes Troubleshooting Fixes • Reconsider using the DewPoint at these temperatures • Compare reading to actual ambient tem- • Ambient temperature is high perature •...
Faults Fault 214: Data Logging Failed: Replace USB Drive Indicates that the screen can no longer detect the USB flash drive that should be installed at the bottom of the touch screen. This fault will not prevent operation of the machine, but sensor trending will not record. Press “Confirm” to continue operation Causes Troubleshooting Fixes...
Faults Fault 225: Burner Modbus signal failure The Mod Bus connection is the way that the Honeywell Burner Controller communicates with the PLC. If the connection is lost, the burner will not function properly. The machine can still operate with Fault 225 active. However, the following features will not display properly: Flame Detector indi- cators, Burner State, Burner Faults, Burner Reset (Burner Reset can only be done in Menu >...
Faults Fault 232: Generator Status (Page 1 of 2) Indicates Generator has failed and shut off for safety Causes Indicates Fixes • Main fuel shutoff valve closed • Open main fuel shutoff valve located beneath the front left fuel tank •...
Page 59
Faults Fault 232: Generator Status (Page 2 of 2) Indicates Generator has failed and shut off for safety Causes Indicates Fixes • Check engine coolant level • High Engine Temperature • Engine Temperature is above normal • Check belt, fan, and radiator •...
Faults Fault 239: Initiate Hold: AC Frequency / Noise Indicates that the Burner Controller has restarted. The Burner has shutoff and will automatically re-fire. This Fault displays if this condition happens twice in 1 hour. If this problem persists, the Burn- er Controller may need to be replaced.
Faults Fault 244: Operating Pressure Control Relay SR-5 did not annunciate Indicates that the Operating Pressure Control Relay SR-5 did not annunciate. Burner will not operate Causes Troubleshooting Fixes • Faulty SR-5 Relay: Part #781-1C-120A • Swap relay with 120v spare in Panel 1 •...
Faults Fault 249: Check Network Cable or Fault 214: Missing USB Drive (PLC-015: DEV001 No Device Found) Indicates that the network connection between the PLC and the touch screen has been lost Causes Troubleshooting Fixes • Plug the network cable securely into the •...
Faults Fault 400: Low Water 1 or 2 tripped (Page 1 of 2) (Indicates boiler water level is too low for safe operation) Verify that the boiler water sight glass matches the boiler water level on the touch screen Causes Troubleshooting Fixes •...
Page 64
Faults Fault 400: Low Water 1 or 2 tripped (Page 2 of 2) (Indicates boiler water level is too low for safe operation) Verify that the boiler water sight glass matches the boiler water level on the touch screen Causes Troubleshooting Fixes •...
Faults Fault 401: Boiler not filling / slowly filling with water (See Fault 400) Causes Troubleshooting Fixes • No water in the supply tanks • See Fault 206 • Supply Water Filter (T-Strainer) is plugged • Remove and inspect the screen for debris •...
Faults Fault 403: Boiler water level higher than set point / Boiler overflowing Causes Troubleshooting Fixes • Have you performed a wet layup recently • Wet Layup (Wet Layup fills the boiler completely full of • Drain water from boiler to desired level water) •...
Faults Fault 404.A: Bottom rear work lights will not turn on (All work lights not working 2010-2012 machines) Tractor controls the bottom rear work lights Causes Troubleshooting Fixes • Trailer light harness disconnected • Check light harness • Plug the harness in •...
Faults Fault 405: Touch Screen controller will not turn on Causes Troubleshooting Fixes • Low battery voltage • Start the generator • Charge/replace battery • Blown fuse F4, F5, F10, F12 (Panel 3) • Fuse should light up with a red LED if blown •...
Faults Fault 407: Burner Smoking (Page 1 of 2) Indicates burner air : fuel ratio is not working properly. A puff of smoke every 10 seconds is normal for the 6110 (Black smoke = not enough air / too much fuel) (White smoke = too much air / not enough fuel) Causes Troubleshooting Fixes...
Faults Fault 407: Burner Smoking (Page 2 of 2) Indicates burner air : fuel ratio is not working properly. A puff of smoke every 10 seconds is normal for the 6110 (Black smoke = not enough air / too much fuel) (White smoke = too much air / not enough fuel) •...
Faults Fault 409: Loss of steam pressure during operation Causes Troubleshooting Fixes • Burner fire shutting off because steam • Test in “Manual Mode” to see if steam • Replace steam purge actuator purge valve is not opening to maintain target purge Actuator moves when turned “ON”...
Faults Fault 411: Circulation Pump not running Causes Troubleshooting Fixes • Water level must be above Low Water 1 & 2 • Water level is not high enough • Low boiler water level (See Fault 400) for the circulation pump to run •...
Faults Fault 412: Water in Steam / Bales have Water splotches / Sudden Loss of Steam Pressure and Water Level Indicates poor water quality Causes Troubleshooting Fixes • Supply Water PPM not set correctly on the • Enter correct PPM Setting on boot up screen •...
Faults Fault 416: Fuel Nozzle Pressure is low in High Fire Fuel nozzle pressure is below 160-190 PSI in high fire Causes Troubleshooting Fixes • Low fire fuel regulator is out of adjustment • Low fire fuel pressure should be 80-90 PSI •...
Faults Fault 419: Purge Hold: T19 High Fire Switch (Waiting for Louver to Open) Indicates that the burner louver actuator did not open the louver for purge (Fault 14 indicates the same failure. Fault 14 can take up to 5 minutes to occur) Causes Troubleshooting...
Faults Fault 421: Generator will not start from Touch Screen Causes Troubleshooting Fixes • Temporary fix: Start/Stop the generator manually from the generator controller by • Start/Stop the generator manually from the pressing “Auto” then “Manual Start” • Slightly drained battery generator controller by pressing “Auto”...
Faults Fault 423: Touch Screen Problems: Frozen, won’t respond to touch... Causes Troubleshooting Fixes • Replace USB flash drive • Is the screen locking up / displaying one of • Faulty USB flash drive the messages below? (8gb or smaller) Error message: EA9 An attempt was made to access \Hard Disk\Log\..
Faults Fault 425: Burner not going into high fire / Stuck in low fire Causes Troubleshooting Fixes • Burner will not go into high fire until boiler • Let the water warm up to more than 180° F water temperature is above 180° F •...
Faults Fault 426: Failed PTO Bearing(s) Indicates poor driveline quality Causes Troubleshooting Fixes • Not greasing bearings every 50 hours • If there is play/movement in the PTO shaft, • Bad PTO shaft angles this indicates that your bearings have failed. •...
Test 101: Flame Detector Testing Procedures Burner Controller 1. Ensure Control Power is on (Green “POWER” LED) -Generator must be running -Control Power must be enabled on the touch screen 2. Remove Flame Detector 3. Point the flame detector at a light source and confirm the red “FLAME” Purge Card LED lights up on the Burner Controller 4.
Page 83
Test 104: Ignition Transformer Test (2014 machines only) Note: 2013 and older machines; watch for the spark through the sight-glass 1. Disconnect the ignition cable from the transformer 2. Hold the ignition cable eyelet 3/8” - 1/2” away from the ignition transformer post 3.
Test 105.b: Igniter Electrode Orientation & Gap (Page 2 of 2) Propane: 2014 machines) Remove the burner gun assembly (See Test 117) 1. Locate the electrode spark centering hole (end of the burner gun assembly) 2. Position the electrode where the tip is flush with the outside of the propane tube 3.
Test 108: HPLS Calibration [15 PSI] 1. With the boiler full of water, hook up an air hose to the boiler to simulate pressure 2. With the multimeter set to measure ohms, connect your pins to the terminals on SR-3 and SR-4 as shown in #2 3.
Test 109: OPLS Calibration [14.5 PSI] 1. With the boiler full of water, hook up an air hose to the boiler to simulate pressure 2. With the multimeter set to measure ohms, connect your pins to the terminals on SR-4 and SR-5 as shown in #2 3.
Page 87
Test 110.b: Boiler Water Level Sensor Testing (Page 2 of 2; Old style sensor) 1. Disconnect power to the signal conditioner by removing the two-place green terminal strip fro the conditioner (Panel 3) 2. Check to see if the sensor is working 3.
Test 111: Valve Repair Before you begin, turn the valve to the fully closed position. Be careful not to damage the surfaces on the valve where the seats will need to seal. 1. Remove the retainer nut from the end of the valve and remove the outer seat and the ball (ball must be in the closed position before it can be re- moved) 2.
Test 112: Pump Service NOTICE: The highly polished and lapped faces of this seal are easily damaged. Read instructions and handle the seal with care. Some models are equipped with an impeller screw, which has a left hand thread. Before unscrewing the impeller, remove the impeller screw. REMOVAL OF OLD SEAL INSTALLATION OF FLOATING SEAT (Figure 5C) INSTALLATION OF ROTATING PART OF SEAL UNIT...
Test 113: Input Card Testing (See Fault 302) • Go to Menu > Diagnostics > Inputs Outputs > Analog Inputs and inspect channels 1-8 on cards 1 & 2 for normal readings. A faulty input card will often max out the readings on one or more channels. •...
Test 114: Program the VFD (See Fault 29) (Only some 2014 machines) • Programming the VFD requires entering the password and adjusting 5 parameters: (P05 = 2, P06 = 3, P19 = 15, P20 = 30, P31 = 60) 1. With the Generator running: Press “Mode” on the VFD 2.
Test 115: Louver Actuator adjusting (See Fault 14) 1. Remove the louver actuator cover by removing the cover screw 2. Press in and lock the “louver locking pin” to free the louver 3. Remove the spanning wrench tool 4. Using the spanning wrench tool adjust the blue home position cam to “zero”. Jam the spanning wrench against the louver actuator housing and use the freed louver linkage arm to adjust the cam (use this method for the red cam also) 5.
Test 116: Tune the burner (Page 1 of 3) 1. Remove flame detector and burner cover 2. Clean the fan with compressed air and reinstall the burner cover and flame detector 3. Check louver position (Should be about 1/4 inch open; adjust the top bolt as needed) 4.
Page 94
Test 116: Tune the burner (Page 2 of 3) 9. Once the burner advances to Low Fire, follow the four steps below 1- Set the Fuel pump PSI to 280-300 PSI using a flat head screwdriver (Use the physical gauge next to the pump and the digital gauge on the touch screen) a.
Page 95
Test 116: Tune the burner (Page 3 of 3) 11. Press “High Tune” and wait (Boiler needs to reach 180 degrees Fahrenheit before entering High Fire) 12. Once the boiler reaches 180 degrees Fahrenheit: 1- Adjust the fuel pump pressure to 280-300 PSI 2- Make sure the air louver is 100% open 3- The burner should burn clean when properly tuned (no white/black smoke) 13.
Test 117: Remove the burner gun assembly 1. Mark the burner gun assembly depth 2. Loosen sight tube locking bolt; remove the flame detector, cover bolts, nozzle PSI sensor M12 plug, fuel lines and (propane line 2014’s) 3. Lift up then out to remove the cover 4.
Test 118: Update to new boiler water level sensor (Page 1 of 2) (Update Kit Part # 10344) 1. Remove the old boiler water level sensor 2. Install the new boiler water level sensor using the adapter flange, gasket and bolts 3.
Page 98
Test 118: Update to new boiler water level sensor (Page 2 of 2) (Update Kit Part # 10344) 9. (2010-2013 DewPoint machines) Release the 8th Purple and Red wires and tuck them into the panduit cable hider (they will no longer be used) 10.
Test 119: Flue tube cleaning (Page 1 of 3) Tools needed: Safety goggles, dust mask, shop vac, paint suit, 1.5” flue tube brush (Part # 10178) attached to a 7 foot rod, socket set... 1. Drain the boiler: open the main boiler drain valve 2.
Page 100
Test 119: Flue tube cleaning (Page 2 of 3) 9. Disconnect the flue temp sensor wire harness and remove the flue temp sensor (use the nut, not the head) 10. Remove the rear door cover nuts (and door temp sensor and bracket) 11.
Page 101
Test 119: Flue tube cleaning (Page 3 of 3) 14. Prepare to brush the flue tubes by attaching the flue tube cleaning brush (Part # 10178) to a 7 foot rod 15. When bushing, be careful not damage the front turn box insulation with the brush as it pushes through the end of the tube 16.
If there are 15 white terminal strip, remove the last three green/oragne jumpers Note: This update should be done to all 2010-2013 DewPoint 6110 machines. These extra jumpers are sending 24v power to disconnected sensors and can cause fuses to blow...
Test 121: Generator End Troubleshooting (Page 1 of 2) Causes Troubleshooting Fixes • Faulty exciter wires • See Test A • Replace generator • Faulty motor stator • See Test B • Replace generator • Faulty voltage regulator • See Test C •...
Page 104
Test 121: Generator End Troubleshooting (Page 2 of 2) B: Main Stator Test 1. Turn off the main circuit breaker 2. Remove the top 4 screws of the generator cover with a 8mm wrench. 3. Remove the white and green wires from T2 4.
Test 123: Maxed out sensor readings Test 123.A: Faulty Sensor / Faulty Wire Harness Test (Multimeter Required) 1. Open Panel 2 (Touch screen should be off) 2. Find the Analog Input terminal strip shown in the picture below 3. Make sure the multimeter is set to measure Ω (Ohms) / Continuity 4.
Page 107
Test 123.B: Faulty Sensor Test (No Multimeter Required) 1. Go to Menu > Diagnostics > Inputs Outputs > Analog Inputs 2. Watch touch screen as you unplug the affected sensors one by one to see if there is a change (A change in the sensor reading may take up to 30 seconds) 3.
Test 124: All sensors offline / fuse keeps blowing Test 124.A: Faulty Wire Harness Test (Multimeter Required) 1. Open Panel 2 (Touch screen should be off) 2. Find the Analog Input terminal strip shown in the picture below 3. Make sure the multimeter is set to measure Ω (Ohms) / Continuity 4.
Page 109
Test 124.B: Faulty Sensor Test (No Multimeter Required) 1. Unplug all sensors 2. Replace the blown fuse (Panel 3) (if the fuse blows immediately when you turn on the touch screen, go to Test 124.A) 3. Watch touch screen as you plug the sensors in one by one Menu > Diagnostics > Inputs Outputs > Analog Inputs 4.
Checklists DAILY EVERY 50 HOURS Grease PTO bearings PRE-OPERATION Check battery and recharge Grease PTO anti-rotating shields Drain water separator Check engine coolant and oil levels Clean radiator fins Check water separator Clean/Replace inner and outer air filters Clean supply water filter (T-strainer) Clean igniter assembly Drain 30-40 gallons of water from boiler Clean flame detector lens...
Checklists EVERY 250 HOURS / YEARLY EVERY 500 HOURS Perform 50 hour maintenance Perform 50 hour maintenance Grease fan motor (1 pump) (DO NOT OVER GREASE) Perform 250 hour maintenance Grease and lubricate axles Grease brake cam supports Check/Adjust engine speed so that frequency is 61-62.5hz Grease brake levers Check/Adjust cooling fan v-belt Grease steering rod joints...
MAINTENANCE SCHEDULE See DewPoint 6210 Owners Manual • Operator Training • • • De-Winterization Safety Information Operation • • • • Warranty Information Pre-Operation Requirements Winterization Maintenance Instructions System Check Item Daily 1000 1500 2000 Grease PTO anti-rotating shields Grease and lubricate axles and PTO bearings Grease fan motor (1 pump) (DO NOT OVER GREASE) Grease/Lube Grease brake cam supports...
Page 114
System Check Item Daily 1000 1500 2000 Clean Burner Fan Clean supply water filter (T-strainer) Drain 30-40 gallons of water from boiler Purge hot water through the “Y” strainer for 2-3 seconds Remove crop debris from enclosed areas Purge steam through baler hardware nozzles to clear debris Inspect gauges, sensors, and sight glasses Clean igniter assembly Clean flame detector lens...
Page 115
System Check Item Daily 1000 1500 2000 Check torque on wheel nuts (325-370 lb-ft) x(1st) Check/Adjust steering hinge gap x(1st) Rotate tires (front to rear) Check/Adjust wheel bearing gap x(1st) Check brake gasket Frame/Axles Check/Adjust brake lever stroke Check torque on shock absorber end screw (295-330 lb-ft) Check torque on steering control cylinder fastening screw (295-330 lb-ft) Check torque on brake cylinder support screw (130-160 lb-ft) Check torque on steering rod end screw (295-330 lb-ft)
Page 116
Keys to Success Preparation Operation Water Ideal baling moisture, with Always use boiler water treat- Read the “Owner’s Manual” steam, is 11% - 15% ment chemical in boiler water. Always use appropriate water Always make sure hydraulic Never exceed 135° F (57° C) treatment equipment (Softener, brakes are hooked up and internal bale temperature.
Need help?
Do you have a question about the DewPoint 6110 and is the answer not in the manual?
Questions and answers