Specifications - ADC DMPS-10CE User Manual

Adc telecommunications power supply user manual dmps-10ce
Table of Contents

Advertisement

ADCP-50-404 • Issue 2 • November 1998
Ripple voltage* is held to the following limits:
+5 Vdc, at or below 50 Millivolts, Peak-to-Peak
+12 Vdc, at or below 120 Millivolts, Peak-to-Peak
–12 Vdc, at or below 120 Millivolts, Peak-to-Peak
* Measured with a device having a 50 MHz bandwidth.

4. SPECIFICATIONS

PARAMETER
Input
Voltage
Current
Frequency
Fusing (On rear of basic unit)
Output Each Module
Voltage
Current
Physical
Chassis
Expansion Module
Environmental
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Electromagnetic Compatibility
Page 4
© 1998, ADC Telecommunications, Inc.
SPECIFICATION
190/240 Vac
2 Amps Maximum (4 Modules)
48 to 62 Hz
220 Vac: 4-Amp, Dual, Time Delay
+5 Vdc ± 5%
+12 Vdc ± 10%
–12 Vdc ± 10%
4.5 Amp DC Max. @ +5 V
1.0 Amp DC Max. @ +12 V
0.5 Amp DC Max. @ –12 V



3.5
19
11 inches (8.9


3.5
3.9
9.22 inches (8.9




0
to 50
C (32
to 122
F)



–40
to +70
C (–40
to 158
10 to 80% non-condensing
5 to 90% non-condensing
Meets CISPR22 Class B radiated and conducted emissions.

48.3
27.94 cm)


9.91
23.5 cm)

F)