Low voltage variants can be supplied, coded by the following suffixes:
• 12VAC
12V - (ac supply) operation
• 12VDC
12V - (dc supply) operation
• 24VAC
24V - (ac supply) operation
• 24VDC
24V - (dc supply) operation
Variants with bespoke timings can be manufactured to special order.
Trouble shooting
The lamp switches off about 1 minute after it switches on.
• Unit has not been calibrated
• Too much artificial light is entering the DUSK Switch.
The lamp switches on too early in the evening.
• Move the Lux adjuster further towards clockwise.
The lamp switches on too late in the evening.
• Move the lux adjuster further anticlockwise.
If the LED fails to illuminate (after calibration) either RED or Green and the
load switches on (after a minute), the current ambient lux is lower than the
minimum 10 Lux (at the cell) and the switch cannot be inhibited off.
• Site the DUSW in a position that sees more natural light.
Precautions and Warranty
This product conforms to BS EN 60669-2-1 and BS EN 55015.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp circuit breaker and voltage surge protection.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: sales@danlers.co.uk
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
11/12/15
Dusk Switch
DUSW with Intelligent photocell
DANLERS DUSW is IP66 rated and can be surface mounted onto an
external wall. It will switch outdoor lights on at dusk and switch them off after
a chosen time delay or when it becomes light again, repeating each day.
The light level at which the lamp will switch on and off is set by a lux adjuster.
DUSW has a new 'intelligent' calibration process which will remove the site
specific addition of artificial light from any decision to switch the lights on/off."
Loading
The switch should only be connected to a 230V 50Hz AC supply. These PIR
switches can switch up to:
6 amps (1500W) of resistive loads.
6 amps (1500W) of fluorescent loads.
3 amps (750W) of electronic and wire wound transformer loads.
2 amps (500W) of CFL, 2D lamps, LED Drivers and LED lamps and fittings.
1 amp (250W) of fans
Minimum load 2W resistive, suitable for most energy saving lamps, LEDs and
emergency fittings.
Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. The switch should be sited such that it can receive more daylight than
artificial light. Ensure that any artificial lights are not too close to the switch or
shining into it.
3. The switch must be mounted via the four pre-formed holes only, no
additional holes should be drilled through the enclosure. The spindle must
point downwards, with room below to adjust it.
4. Make sure the power is isolated from the circuit.
5. The detector should be connected as shown in diagram D.
L - Live in, N - Neutral in, SL - Switched Line out.
6. IMPORTANT - Replace terminal cover.
7. Once the wiring has been completed and verified, switch on the supply and
test the operation.
INS972 DUSW
Installation notes

Advertisement

loading

Summary of Contents for DANLERS Dusk Switch

  • Page 1 24V - (ac supply) operation • 24VDC 24V - (dc supply) operation DANLERS DUSW is IP66 rated and can be surface mounted onto an external wall. It will switch outdoor lights on at dusk and switch them off after Variants with bespoke timings can be manufactured to special order. a chosen time delay or when it becomes light again, repeating each day.
  • Page 2 DUSW Time/Lux set-up range limit / is OUT of range of the product, (1000 LUX maximum on the cell ) The time for which the lamp will stay on for can be adjusted from 2 to 16 hours as and the lights MAY / WILL cycle. shown in diagram C. To check the spindle is set correctly - quick press the MODE Note: As the lux pspindle is moved anticlockwise it may be that the LED goes from fixed green button (less than 4 seconds). A RED LED will flash the number of times relating to fixed red before it goes off. This informs the user that the current LUX control point in addition to the position of the spindle as follows: to the artificial LUX is either in range or out of range. When moving the pot anticlockwise, if the LED goes RED before it goes out then the LUX control point needs to be adjusted lower 1 flash - Light level only (timer disabled) 6 flashes - 10 hours OR the unit repositioned with respect to the controlled load, so that it is NOT seeing as much 2 flashes - 2 hours 7 flashes - 12 hours artificial light and then recalibrated. 3 flashes - 4 hours 8 flashes - 14 hours 9. After calibration: (With the load inhibited off). When the ambient lux has reduced 4 flashes - 6 hours 9 flashes - 16 hours to the level you require the lamps to switch on, assuming the LED is fixed green 5 flashes - 8 hours (pot fully clockwise), move the pot anticlockwise until the LED goes off. This LUX Calibration is recommended to take place when ambient light levels are low needs to be done in small increments by adjusting the pot and moving well out (preferably at night or with daylight excluded as far as possible, from the calibration the way of the LUX cell. Ensure the LED is still off when full natural daylight is measurement). Set up of the switching level on the lux switch should take place seen by the cell at that particular time. i.e. not shaded by the commissioning when the ambient lux is “as required” from natural daylight. “body”. After 1 minute the load should switch on. When set up and calibrated DUSW will inhibit the artificial lights from switching ON, if the ambient measured lux is greater than the user set threshold. If the B: Lux adjustment A:Time/Lux adjusters (inside casing) artificial lights are ON and the LUX then rises greater than the set threshold...