Do you have a question about the KNGcooling module and is the answer not in the manual?
Questions and answers
Summary of Contents for REMKO KNGcooling module
Page 1
Installation instructions REMKO cooling module Cooling module for the WSP heat pump range 0261-2020-03 Edition 1, en_GB Read the instructions prior to performing any task!
Page 2
Read these operating instructions carefully before commis- sioning / using this device! These instructions are an integral part of the system and must always be kept near or on the device. Subject to modifications; No liability accepted for errors or mis- prints! Translation of the original installation instructions...
Table of contents Safety and usage instructions......................4 1.1 General safety notes........................4 1.2 Identification of notes........................4 1.3 Personnel qualifications........................4 1.4 Dangers of failure to observe the safety notes................4 1.5 Safety-conscious working....................... 4 1.6 Safety instructions for the operator....................5 1.7 Safety notes for installation and inspection tasks................
REMKO cooling module Safety and usage instructions CAUTION! This combination of symbol and signal word 1.1 General safety notes warns of a potentially hazardous situation, which if not avoided may cause injury or mate- Carefully read the operating manual before com- rial and environmental damage.
1.9 Intended use Depending on its type and design, the cooling module as an accessory is only suitable for the intended use on REMKO WSP heat pumps. Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia- bility for damages arising from non-intended use.
For warranty claims to be considered, it is essential that the ordering party or its representative com- plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned. The warranty conditions are detailed in the "Gen- eral business and delivery conditions".
Technical data 2.1 Unit data Unit type Cooling mode Brine/water, System or water/water Medium flow rate water (according to EN 14511, at ∆t 5 K) 0.95 Min./max. operating temperature °C 7/95 Max. operating pressure Power supply V/Ph/Hz 230/1~/50 Brine-side pressure loss kPa/bar 140/0.14 Heating side pressure loss...
REMKO cooling module 2.3 Unit dimensions Ø22 (WSP 80/110) Ø28 (WSP 140/180) Ø 54x100 G 1" (WSP 80/110) G 1 ¼ " (WSP 140/180) Fig. 2: Unit dimensions (all measurements in mm) We reserve the right to modify the dimensions and design as part of the ongoing technical development...
2: WSP heat pump The REMKO cooling module [1] is designed for Fig. 4: Method of operation cooling mode for the REMKO WSP heat pump [2]. A: Brine outlet It is suitable for passive cooling, e.g. via a surface B: Brine inlet...
Proceed as follows to install the cooling module on the two cover caps [1] from the top next to a REMKO WSP heat pump: the hydraulic connections. If there is still air in the cooling module after filling and rinsing the...
Page 13
Removing the actuator In order to replace the entire changeover valve, the hydraulic connection for the valve [1] that is to be Proceed as follows to replace the actuator: replaced must be closed and bled accordingly. After bleeding, you can loosen the three valve [1] Pull the safety split pin below the actuator out screw connections.
The heating/cooling system provided by the customer must be protected to prevent the General notes temperature falling below the dew point (con- densation water). The REMKO dew point mon- itor with corresponding probes can be used for this. Cooling without a REMKO room temperature/ A separate interpretation of nominal flow rate humidity probe is not permitted.
Page 15
Hydraulic diagram for the WSP heat pump Functions: Heating or cooling and hot water This hydraulic cycle diagram serves solely to assist in planning activities; the customer-provided hydraulic system on site must be planned and installed by the installation contractor! Heat pump with cooling module Electronic overflow protection valve Heat source...
Activating / deactivating passive cooling The settings for the passive cooling can be made A12 L at expert level. To do so, touch the REMKO logo in the upper right corner of the display. User level Fig. 5: Valve electrical wiring ¯...
Make sure that all valves of the source system and send it to REMKO by post or e-mail within and the distributors are open to guarantee the eight days. In addition, the following requirements free medium flow rate.
Commissioning Care and maintenance Control panel and information on commis- Regular care and maintenance assure fault-free sioning operation and long service life for the heat pump system. NOTICE! Care Before commissioning, the complete system The heat pump must be kept free of dirt and hydraulics must be flushed and filled in accord- other deposits.
REMKO cooling module Temporary shutdown NOTICE! The system may not be switched off at the mains Country-specific laws may differ from Regula- power supply even if the heat pump is not used for tion (EC) 842/2006. The respective national heating purposes over an extended period (e.g.
General view of unit and spare parts Exploded view of the unit Spare parts list Designation EDP no. Heat exchanger Actuator for 3-way valve 1120912 Hydraulic bottom part 1" 1120912-1 SMT PT1000 brine return flow probe 1120930...
Need help?
Do you have a question about the KNGcooling module and is the answer not in the manual?
Questions and answers