Do you have a question about the PENTACARE-V12 Series and is the answer not in the manual?
Questions and answers
Summary of Contents for Minotair PENTACARE-V12 Series
Page 1
Serial Number: Purchase date: Reseller: Reseller’s Tel: COMPACT AIR TREATMENT UNIT PENTACARE-V12 SERIES PLEASE READ THIS MANUAL CAREFULLY AND KEEP IT FOR FUTURE REFERENCE...
Page 2
Recovery Ventilators. Not to mention that, unlike the MINOTAIR, none of these products can heat, cool or dehumidify by themselves. Only the MINOTAIR can claim to be truly multifunctional. The MINOTAIR is easy to operate with its digital control, designed to focus on the factors directly affecting comfort and air quality.
Personal Safety ............................16 Regulations ..............................16 Device Inspection ............................ 16 Choosing where to install the MINOTAIR .................... 16 Choosing an Installation Method ......................17 Connection to a Forced Air Ventilation System – Simplified Method ........17 Connection to a Forced Air Ventilation System – Extraction at the Source ....... 18 Connection to an Independent System of Ventilation Ducts ..........
The following list is meant to clarify expectations following commissioning of the MINOTAIR in accordance with the instructions set forth in this manual. Keep in mind that the MINOTAIR should be installed and maintained in accordance with this manual to ensure optimal performance for many years.
XTERNAL VERVIEW The MINOTAIR’s housing is 100 % aluminum, which makes it lighter and easier to handle. Furthermore, aluminum is a long-term guarantee against corrosion which, otherwise, would end up weakening the housing structure since it is always in contact with humidity and condensates.
PERATING ODES The MINOTAIR is the only system of its kind to combine a motorized damper with two constant airflow fans. The motorized damper can switch between two positions, which allow the MINOTAIR to function as either an air exchanger (ventilation) or a heat pump (recirculation).
Follow professional safety standards and all local regulations. EGULATIONS • WARNING! The MINOTAIR should be installed in accordance with the local building codes that are in effect. In absence of such requirements, it is advisable to check with local authorities having jurisdiction in your area. EVICE NSPECTION •...
However, stale air and moisture will be extracted directly at the source through dedicated ducts to ensure better humidity management. • This option is only possible if the MINOTAIR can be installed in the same room where the forced-air system ventilator is located. •...
Page 22
If enough space is available, it is always preferable to choose main ducts of 8” (200 mm) to use the MINOTAIR to its full. The maximum airflow of the main ducts will then be required to be adjusted between 220 cfm and 250 cfm (105 l/s and 120 l/s) in the microcontroller’s ventilation menu.
If this is not possible, it is nonetheless advisable that at least the first 6 feet (2 m) of the supply ductwork starting from the Minotair be insulated. CAUTION! During cooling and dehumidification operations, condensation could form on the outside walls of the unit and the supply ducts, which could cause water damage.
Whenever possible, the slope of the conduits connecting to the outside hoods should have a slight slope either towards the outside or the Minotair to drain out condensates that may form if the airflow passing through the conduits is very humid.
Close all windows and doors, and turn off all exhaust devices such as range hood, dryer and bathroom fans. o Set the controller to the maximum airflow allowed, and set the MINOTAIR to "air exchanger" mode. o Connect each plastic tube to the fresh air from outside and stale air to outside respectively.
120 lb. (55 kg). • The MINOTAIR must be suspended using the four specially designed hooks. Use the polypropylene webbing straps (supplied) to tie the device.
The other end of the pipe must end its course in the floor drain or a condensate pump. Using a bucket is not recommended, because the MINOTAIR will fill it quickly on humid days, which will then cause spills on the floor.
80 cfm (40 l/s), in Air Exchanger mode. Verify that the static pressure reported by the MINOTAIR is greater than or equal to 0.1 inch of water column (25 Pa) (refer to the “ventilation” menu). If it is not (i.e., the pressure is equal to 0.0 inches of water column (0 Pa)), you will need to install a register key (Figure 9 and Figure 10) and adjust it until the static pressure indicates 0.1 inch of water column (25 Pa).
PTION • It is possible to connect a heat pump to the MINOTAIR. In this case, there must be a 120 VAC relay (not supplied) that will connect in parallel with the reversing valve (Terminal NO2 on the microcontroller) located inside the MINOTAIR which will then act as "O" terminal or "B"...
Bathrooms can be equipped with timers to activate ventilation in air exchanger mode when needed. • The MINOTAIR timers can be turned on for periods of 10, 20 or 30 minutes. They can remain continuously turned on by simply pressing their button for 3 seconds. •...
NSTALLATION PTION • In addition to the digital control integrated in the microcontroller, it is possible to connect up to two wallmount digital controls per MINOTAIR unit for even more convenience. Figure 20 – Wall Mount Digital Control ELECTING THE OCATION •...
MINOTAIR that can be used to cut power during repair or maintenance activities (Figure 25). • No other device can share the same circuit as the MINOTAIR. If a condensate pump is required, it must be connected to a different circuit. Figure 25 – Connecting the device.
IGITAL ONTROL ASICS The MINOTAIR is controlled through a digital control featuring a backlit display and 6 buttons. The interface is designed around a house theme. CREEN Figure 26 – MINOTAIR digital control main screen Inside the house Device status {on ( ), off ( ...
EQUENCE Like most computers, every time you power on the MINOTAIR or after a power outage, the MINOTAIR initiates a boot sequence that lasts approximately 30 seconds. During this period, the digital control is not in operation and the screen may be blank or display messages like “No Link”.
N AND Press A to turn on the device. Ventilation will start (Figure 30). NOTE: The MINOTAIR does not display temperature or humidity when it is turned off. The MINOTAIR’s ventilation must be in operation for this information to show.
The MINOTAIR includes several settings that are accessible from the main menu screen. You can access the main menu by pressing the “Setpoint” P button for 3 seconds. 1. V ENTILATION ETTINGS Press the P button for 3 seconds to display the main menu. Then, using the U and D arrows, navigate to the “Ventilation”...
90% to 110 %. Set the exhaust fan airflow to make it lower or higher than the intake fan airflow in order to balance the airflows with greater accuracy. See "Balancing the MINOTAIR" for more information. NOTE: This is an advanced setting and only ventilation professionals equipped with proper measuring equipment should adjust it.
To do this, run the forced-air system ventilator at full speed while running the MINOTAIR at its lowest speed, i.e. 80 cfm (40 l/s), and verify that the static pressure reported by the MINOTAIR is greater than or equal to 0.1 W.C. (25 Pa).
Figure 44 – Examples of options to adjust auxiliary (central) heating units. The MINOTAIR can control auxiliary heating units such as electric and gas furnaces and heat pumps as long as they can be controlled through a 24 VAC signal.
NO. This MINOTAIR does not control any auxiliary cooling unit. o YES. This MINOTAIR will send a signal to the “Y” cooling terminal on the terminal board and will let the auxiliary unit manage its own speed switching, if applicable.
Figure 47 – Examples of options to adjust outside temperature calibration. Figure 48 – Examples of options to calibrate the inside temperature sensor. The MINOTAIR uses sensors to measure outside and indoor temperatures. However, since the sensors are integrated into the device, their temperature readings may differ from what the sensors would have measured if they had been located outside the house (for outside temperature) or in a living space like the living room (for indoor temperature).
3.4.2 Figure 52 - Examples of options to adjust humidifier settings. 3.4 This MINOTAIR controls a humidifier? o YES. This MINOTAIR controls a humidifier and will call for humidity when needed. o NO. The MINOTAIR does not control any humidifier.
SETTINGS SCREEN CONT The daily profile screen enables you to preprogram the MINOTAIR to operate according to a predefined arrangement depending on the day of the week and the time of day. Figure 55 - Examples of options to adjust daily profile settings.
5.1.1 Figure 57 – Examples of options to adjust filter settings. 5.1 Prefilters. The MINOTAIR must be equipped with manufacturer-approved MERV 8 (G4) prefilters to ensure proper functioning. Two prefilters protect the MINOTAIR from dust, which can quickly clog its coils and fan blades. The prefilters must be replaced every three months.
5.2 HEPA Filter. The MINOTAIR is equipped with a High Efficiency MERV 15 (F9) filter, which can eliminate up to 95% of dust and micro-organisms as small as 0.3µm. HEPA filters are recommended for asthma patients. These filters must be replaced every 12 months.
12hr. Displays the time in 12hr format (AM and PM). • Account for daylight saving time? o YES. The MINOTAIR will automatically adjust the time at 2 am on the second Sunday of March, and again at 2 am on the first Sunday of November.
“change filters” indicator. NOTE: During an alarm, the MINOTAIR will try to solve the problem by itself. If it succeeds, it will automatically reset the alarm and add it to the log. If it is not successful after a maximum of five attempts, it will display the alarm to bring it to the attention of the owner.
AINTENANCE The MINOTAIR is a powerful device, but it requires a certain amount of maintenance on a regular basis. Regular maintenance of this device will ensure optimal and worry-free working conditions. Furthermore, failure to perform this maintenance will render the device’s warranty null and void.
IMITED ARRANTY Dedicated to offering the highest quality products, MINOTAIR Ventilation Inc., the “Manufacturer”, is pleased to offer a 5-year limited warranty on parts. The “Warranty” applies to the CATU-V12 and PentaCare V-12 Compact Air Treatment Unit, the “Product”. •...
Need help?
Do you have a question about the PENTACARE-V12 Series and is the answer not in the manual?
Questions and answers