2. Remove the line
connecting to the
motor.
3.Remove the
motor、Remove the
motor from the
support
4.Remove the
centrifugal fan
5.Replace the
motor with a new
one.
Multi Variable Air Conditioners Indoor Unit for North America
125
●Use a screwdriver to unscrew the
electric box cover.
●Remove from the master board the
line connecting to the motor and
remove the tie.
●Use a screwdriver to unscrew the
motor、volute casing subassembly
and joint slack。
●Loosen the fasteners of the
motor ,remove the motor from the
support
●Remove the volute casing
subassembly as well
●Remove the volute casing
●Use a hexagon to unscrew the
centrifugal fan,remove it from motor
axle
●Assemble units based on the
reverse order of this procedure and
power on the units for test.