Technical description
Application:
Heating and cooling systems with variable flow.
Function:
Differential pressure control over the load.
DA 56: Installation in return pipe.
DAF 56: Installation in inlet pipe.
Pressure class:
PN 25 or PN 6 (DN 00 and 25)
Max. differential pressure:
600 kPa = 6 bar
Temperature:
Max. working temperature: 40°C
Min. working temperature: -0°C
Setting range:
Differential pressure adjustable in ranges 5-30, 0-60,
0-00 and 60-50 kPa.
DA 56, DAF 56
Differential pressure controller
Media:
Water and neutral fluids, water-glycol mixtures.
Material:
Valve body: Ductile iron EN-GJS-400-8LT
Diaphragms and gaskets: EPDM
Adjustment ring: DN 5-50 Ryton plastic,
DN 65-25 R St 37-2 steel.
Surface treatment:
Electrophoretic painting.
Marking:
TA, DN, PN, GGG 40.3, Kvs, Dp and flow direction arrow.
Flanges:
DN 5-50 (optional): According to EN-092-2:997, type 6.
DN 65-25: According to EN-092-2:997, type 2.
6-0-5 XX
2007.07


Advertisement

loading

Summary of Contents for TA DA 516

  • Page 1 Surface treatment: Electrophoretic painting. Max. differential pressure: 600 kPa = 6 bar Marking: TA, DN, PN, GGG 40.3, Kvs, Dp and flow direction arrow. Temperature: Max. working temperature: 40°C Flanges: Min. working temperature: -0°C DN 5-50 (optional): According to EN-092-2:997, type 6.
  • Page 2 DA 516 5-30 kPa DN 15-50 TA No PN 25 52 763-020 5/20 ØD 52 763-025 25/32 G /4 52 763-040 40/50 L, L1* 10-60 kPa TA No PN 25 52 76-020 5/20 52 76-025 25/32 G /4 52 76-040...
  • Page 3 DA 516 DN 65-125 5-30 kPa TA No PN 16 52 763-490 52 763-49 ØD PN 25 52 763-065 52 763-080 52 763-090 52 763-09 10-60 kPa TA No PN 16 52 76-490 52 76-49 PN 25 52 76-065 52 76-080...
  • Page 4 DAF 516 5-30 kPa DN 15-50 TA No PN 25 52 763-20 5/20 ØD 52 763-25 25/32 G /4 52 763-40 40/50 L, L1* 10-60 kPa TA No PN 25 52 76-20 5/20 52 76-25 25/32 G /4 52 76-40...
  • Page 5 DAF 516 DN 65-125 5-30 kPa TA No PN 16 52 763-590 52 763-59 ØD PN 25 52 763-65 52 763-80 52 763-90 52 763-9 10-60 kPa TA No PN 16 52 76-590 52 76-59 PN 25 52 76-65 52 76-80...
  • Page 6 Connections for DN 15-50 With female thread TA No 52 759-05 G/2 52 759-020 G3/4 52 759-025 G /4 52 759-032 G /4 G /4 52 759-040 G /2 52 759-050 64,5 With male thread TA No 52 759-5 G/2...
  • Page 7: Operating Function

    If the measuring point is mounted on DA 56 the differential pressure over the load can be measured by using the balancing instrument TA-CBI or measuring instrument TA-CMI. Installation of balancing valve STAD (STAF) is recommended to enable flow measurement, commissioning and troubleshooting with TA-CBI/TA-CMI.
  • Page 8 Setting DN 15-50 . Unscrew the fixing screw (4) - Allen key 2 mm - on setting wheel (). 2. Turn the setting wheel clockwise to increase the differential pressure and vice versa. 3. On the setting wheel there is a mark which shows how much Dp changes at one turn of the setting wheel.