Download Print this page
Titus TA1 Installation, Operation And Maintenance Manual

Titus TA1 Installation, Operation And Maintenance Manual

Advertisement

Quick Links

Installation, Operation, and Maintenance Manual
General Information
Power Requirements
TITUS TA1/TA2 controllers operate on 24 VAC power. Power
required to operate the controller and actuator is 7 VA plus any ou tput
loads for fan relays, heating contactors, and control valves (assume
10 VA each). Always switch control voltage off prior to disconnecting
any wires from the controller to prevent possible damage to control
components.
Damper Control
TITUS TA1/TA2 controllers provide pressure independent VAV
control for terminal primary air valves. Primary airflow volume is
monitored by means of a multipoint center-averaging velocity sensor
located in the inlet duct. Differential pressure is measured by an on-
board platinum ceramic trans ducer. Dampers are always shipped full
open and move counter-clockwise (CCW ) to close. The primary
damper opens and closes to vary air volume to match cooling
demand. Changes in static pressure will result in damper position
changes for a given flow volume. In automatic changeover(ACO)
sequences, the primary damper also moves to match heating
demand. If the primary fan system is off and th e terminal is calibrated
to control a minimum flow limit other than 0 cfm, the damper will drive
full open. Flow limit adjustments are made using a digital DC
voltmeter at the thermostat (As shown in Figure 1).
Live Supply Volume Readout
A voltage output corresponding to actual primary air volume may be
monitored at the thermostat to assist in balancing and troubleshooting
these units. This output signal follows the same cfm vs DC voltage
calibration curve that is shown on Page 2. The same thermostat
calibration cable (TITUS P/N 100310-01) that is used to make airflow
limit adjustments is also used to read primary air volume on the
outermost meter taps. (As shown in Figure 2)
Supply Air Temperature Sensing
A duct-mounted thermistor is used t o m e a s u r e p r i m a r y a i r
temperature in sequences involving automatic changeover (ACO) or
morning warm-up (MW U). It is fastened to the inlet duct with a
sheetmetal screw and wired to terminals 'X' and 'Y' on the controller.
Alternatively, autochangeover and morning warm-up may be trigger ed
by a contact closure. When controller terminals 'X' and 'Y' are shorted
together, the unit will operate in the heating or morning warm-up
mode. When there is an op en circuit between 'X' and 'Y', the unit will
operate in the cooling mode.
Night Setback/Unoccupied Signal
Units ordered with optional night setback (NSB) sequences employ a
differential pressure switch (As shown in Figure 3) to sense loss of
primary duct static pressure. By this method, these units change
operating mode when the air handler fan is de-energized.
Alternatively, night setback operation may be triggered by a 24 VAC
signal (10 mA) from a source external to the unit. Whenever 24 VAC
is applied to controller terminals '-NS B' and 'NSB', unit will operate in
night setback mode.
Installation Manual
TA1/TA2 Controller
ANA-IOM-1.0
Figure 1.
MAX/AUX
MIN
INCR
INCR
HEATING
TITUS SYSTEMS
V
50
70
METER
TAPS
Cooling Supply Volume
Meter Taps
Figure 2.
Figure 3.
6-15-02
MIN
MAX
INCR
INCR
COOLING
90
V
METER
TAPS
Pressure Switch

Advertisement

loading
Need help?

Need help?

Do you have a question about the TA1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Titus TA1

  • Page 1 This output signal follows the same cfm vs DC voltage calibration curve that is shown on Page 2. The same thermostat calibration cable (TITUS P/N 100310-01) that is used to make airflow METER METER...
  • Page 2 1167 1436 1891 3015 3839 8x14 2106 8x18 2498 40(16x24) 7176 TA1 Controller Voltage vs. Airflow Curves 1000 1200 1400 Airflow (CFM) Figure 4. TA1 Controller Voltage vs. Airflow Curves 8x14 8x18 16x24 1000 1500 2000 2500 3 000 3 500 4000 4500 5000 5500 6000 6500 7000 7500 8000 Airflow (CFM) Figure 5.
  • Page 3 Night Setback Temperature Adjustment Adjustment of setback temperature is made by means of a plug-in resistor (As shown in Figure 6). All TA1 controls provide a 47k ohm resistor that provides an approximate 10° F setback in heating. Other 1/4 watt resistors FLOW THRU SENSOR .188 DIA.
  • Page 4 ANA-IOM-4.0 6-15-02 Single Duct Terminal Units Without Reheat voltmeter reads VDC corresponding to desired minimum flow volume from Page 2. Move thermostat slider full left. Adjust Thermostat Calibration Procedure ‘COOLING MAX’ until voltmeter reads VDC corresponding to Move thermostat slider full right. Adjust ‘COOLING MIN’ until desired maximum flow volume from Page 2.
  • Page 5: Troubleshooting Procedures

    ANA-IOM-5.0 6-15-02 Check-Out Procedure (Day/Occupied Mode) Troubleshooting Procedures Fan should be energized regardless of slider position o n series NOTE: TURN OFF POWER BEFORE MAKING ANY WIRING fan-powered units (ATQS/AFLS). Move thermostat slider full CHANGES TO THE UNIT FOR TROUBLE SHOOTING right to energize fan on parallel fan-powered units (ATQP/ AFLP).
  • Page 6 ANA-IOM-6.0 6-15-02 Description Vendor Part # TITUS Part # Controllers and Actuators TITUS TA1 Controller (5 outputs - handles all applications) CSE-5111 10303201 TITUS TA2 Controller (2 outputs) CSE-5112 10303301 TITUS Actuator, 24V MEP-5001 10268101 Room Thermostats and Accessories Cooling Only (AESV/AECV/AQCV/ATQS/ATQP/AFLS/AFLP)

This manual is also suitable for:

Ta2