LG Dry Contact Installation Manual page 8

For thermostat
Table of Contents

Advertisement

Setting and using method
n Flow Chart for 'OPER_SW'
-. When not using WIND signal
Use WIND Signal?
NO
Set the switch '0 ~ 7'
YES
Use Thermal function?
NO
Set the switch '0 ~ 3'
YES
Use Operation mode?
NO
Set the switch '0 ~ 1'
Set the switch '2 ~ 3'
Use Dry Contact
Use Dry Contact
Control Priority?
Control Priority?
NO
YES
NO
YES
Switch 0
Switch 1
Switch 2
Switch 3
-. When using WIND signal
Use WIND Signal?
YES
Set the switch '8 ~ F'
YES
Use Thermal function?
NO
Set the switch '8 ~ B'
YES
Use Operation mode?
NO
Set the switch '8 ~ 9'
Set the switch 'A ~ B'
Use Dry Contact
Use Dry Contact
Control Priority?
Control Priority?
NO
YES
NO
YES
Switch 8
Switch 9
Switch A
Switch B
Notes
• When you change a function with remote control without setting Dry_contact control priority the display
condition between remote control and controller can be different.
14 Dry contact for thermostat
Set the switch '4 ~ 7'
YES
Use Operation mode?
NO
Set the switch '4 ~ 5'
Set the switch '6 ~ 7'
Use Dry Contact
Use Dry Contact
Control Priority?
Control Priority?
NO
YES
NO
YES
Switch 4
Switch 5
Switch 6
Switch 7
Set the switch 'C ~ F'
YES
Use Operation mode?
NO
Set the switch 'C ~ D'
Set the switch 'E ~ F'
Use Dry Contact
Use Dry Contact
Control Priority?
Control Priority?
NO
YES
NO
YES
Switch C
Switch D
Switch E
Switch F
n Function table for the selection of 'OPER_SW' and the input
signal
CN_MODE input
OPER_SW
FAN
0
0
0
0
2,3,6,7,A,B,E,F
1
1
1
1
Others
-
CN_WIND input
OPER_SW
Low
0
0
0
0
8,9,A,B,C,D,E,F
1
1
1
1
Others
-
CN_OPER
OPER_SW
Thermal
0
0
4,5,6,7,C,D,E,F
1
1
Others
-
Notes
1) Thermal On : This input will change automatically desired temperature
Desired Temperature 18 °C In cooling mode
Desired Temperature 30 °C In heating mode
No function In FAN mode
Setting and using method
OPER_SW
Function
HEAT
COOL
0
0
NA
0
1
COOL
1
0
HEAT
1
1
NA
0
0
FAN
0
1
NA
1
0
NA
1
1
NA
-
-
NA
Function
Middle
High
0
0
NA
0
1
High
1
0
Middle
1
1
NA
0
0
Low
0
1
NA
1
0
NA
1
1
NA
-
-
NA
Function
Operation
0
Thermal Off + Stop
1
Thermal Off + Run
0
Thermal On + Stop
1
Thermal On + Run
-
NA
Installation manual 15