Specifications And Features - US drives AC REGEN RGB-0200-0030-N1 Instruction Manual

Regenerative dc common bus supply
Table of Contents

Advertisement

SPECIFICATIONS AND FEATURES

Electrical Specifications:
Rated Input Voltage:
Frequency Tolerance:
Number of Phases:
Efficiency:
Max. Short Circuit Current Rating:
Noise Immunity:
Environmental Specifications:
Ambient Temperature:
Storage Temperature:
Altitude:
Humidity:
Vibration:
Physical attributes:
Mounting:
Nema Rating:
Construction:
Control I/O:
2 Digital Inputs:
2 Digital Outputs:
1 meter output:
24Vdc source:
max.
Protective Features:
Peak output current monitoring to protect against line-to-line shorts and line-to-ground shorts.
Ground fault monitoring.
Heatsink over-temperature monitoring.
AC line & DC bus over-voltage protection.
AC line & DC bus under-voltage protection.
Control power supply power ride-thru.
Internal power supply monitoring.
AC phase loss detection.
Standard Regen Features
Latest generation IBGT.
Nema type 1 (IP20) as standard for all models.
55C ambient with standard Nema type 1 (IP20) enclosure.
High voltage ratings: 250Vac+10% , 500Vac+10% models, and 600Vac+10% models
Input line suppression: Metal oxide varistors for line-to-line and line-to-ground voltage surge protection.
No programming or hardware jumper for all voltages.
REGENERATIVE DC COMMON BUS SUPPLY
200-250Vac, 380-500Vac, 500-600Vac
-10% of minimum, +10% of maximum.
47-63 Hz
3
99% or greater
200,000A rms symmetrical, 600 volts (when used with AC input line fuses
specified in tables 1 to 3).
IEEE C62.41-1991 Category B (Formerly known as IEEE 587) - 6000V tests
EN50082-1, 2 Generic Immunity Standards
IEC 1000-4-2 ( IEC 801-2 )
IEC 1000-4-3 ( IEC 801-3 )
IEC 1000-4-4 ( IEC 801-4 )
IEC 1000-4-5 ( IEC 801-5 )
IEC 1000-4-6 ( IEC 801-6 )
IEC 1000-4-8 ( IEC 801-8 )
-10C to 55C (14F to 131F) Nema type 1 enclosed.
-40C to 70C (-40F to 158F) Nema type 1 enclosed.
Sea level to 3000 Feet [1000m] without derating.
95% relative humidity non-condensing.
2
9.8m/sec
(1.0G) peak.
Though hole or panel mount.
Type 1 (IP20) as standard, Type 12 (IP54) optional.
Steel construction (reduces E.M.I.)
Regen Enable & Regen Reset
Form C dry contacts rated 115Vac @ 5A; 30Vdc @ 3.5A.
Use with 100A movement analog meter.
Use to power operator pushbuttons and US Drives option boards: 24Vdc @ 100 mA
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents