ADIR Semi – Automatic 2"-3" filters TDS
Installation and maintenance instructions
Box contents
•
Main filter body – picture 1
•
Flush valve 2" FF – picture 2
•
Flush valve 1/2" FM – picture 3
•
Pressure indicator kit – picture 4
Pressure indicator.
o
6 mm tube length 20cms (long).
o
6 mm tube length 15cms (short).
o
2 Female threaded couplers 6 mm
o
2 connectors 1/4"M to 6 mm elbow
o
1 connector 1/4"F to 6 mm elbow
o
1 connector 1/4"F to 6 mm adaptor
o
Assembly
•
Connect the 2" flush valve to the bottom of the filter cup,
(no need to use Teflon, valve is self-seal).
Make sure handle open position is away from filter cup.
•
Connect the ½" flush valve to the flush screen outlet, (no
need to use Teflon, valve is self-seal).
•
Pressure indicator:
Connect two 1/4"F couplers to filter body top
o
outlets.
Connect two elbow 1/4"M to the couplers.
Connect elbow 1/4"F to the bottom of the
o
indicator.
Connect 1/4"F adaptor to side of the indicator.
o
Press fit the indicator to the slots on the filter
o
body.
Connect long 20cms tube from Filter inlet port to
o
indicator bottom (marked "+").
Connect long 15cms tube from Filter outlet port
o
to indicator side (marked "-").
Hydraulic fitting may require Teflon to seal.
o
•
Filter is ready for installation – picture 5
Installation
•
Filter can be installed in vertical position or at 90° to the
pipe, (Flush valve pointing down or to the side).
•
Ensure proper flow direction as clearly marked on the
filter.
•
Make sure both flush valves are closed.
•
It is recommended to install a shut off valve before the
filter for maintenance.
•
Filter is ready for first operation
1
Picture 1
Picture 5
A
950mm
B
795mm
C
235mm
Picture 2
Picture 3
Picture 4