1.ODQ.1A JETMASTER QUADRO OUTDOOR WOOD FIRE & BBQ COOKING GRILL INSTALLATION INSTRUCTIONS TYPICAL IN-BUILT MASONRY BLOCK ALL INSTRUCTIONS TO COMPLY WITH AS/NZS2918:2001 This appliance has been tested to AS/NZS 2918:2001 - by Spectrum Laboratory (Report 0580) Masonry Definition: Solid Concrete, Concrete Block, Brick, Hebel Block/Panel Consult The Fireplace Ltd or your local agent for any variation of the installation specified below IMPORTANT: Read all instructions carefully before starting installation.
Please note that these dimensions (based on 75mm ACC Block margins) are the absolute minimum sizes - widths (A & C) maybe increased if desired. IMPORTANT: Jetmaster firebox is raised 500mm and must be seated on top of a 75mm hebel sheet which is placed on top of a steel structure or masonry blocks. A TIMBER BASE IS NOT ACCEPTABLE The appliance, gather, flue and hebel panel weighs approx 400kg.
RECESS = 100mm It is important to ensure the Jetmaster firebox is seated at the required finished floor protector level. DO NOT COVER AIR VENTS WITH MESH - as this reduces air flow, use specific external air vent covers that provide sufficient air.
Page 4
1.ODQ.3D CHIMNEY CHASE VENTILATION Air Ventilation Through Chimney Chase Air Ventilation Through Top Flashing Fig. 6 Fig. 5 Oversized casing cover is necessary 120mm Spigot flashing to suit 120mm flue pipe casing minimum minimum Drip Drip Non combustible material Line Line Hebel Block or 12mm Promatect H board or...
1.ODQ.3E MINIMUM FLOOR PROTECTOR Table 2 Floor Protecter Raised 500mm 1400 1000 1400 Floor Level Dimensions in mm If the appliance is installed at floor level the appliance and hearth must be installed as outlined in AS/NZS 2918:2001. C1.3.3.3.(c). The base of the firebox and floor protector must * A minimum 75mm thickness refers only to Hebel Block.