GR-2110/ST
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMY DURATION
ILLUMINATION SOURCE
ILLUMINATION (230V AC / emergency)
VEWING DISTANCE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used indoors (ta 40 C) where emergency
light is needed.
Each luminaire must be permanently connected to mains power
supply. In normal operation the illumination LEDs are lit as well
as the green indicating charge LEDs when the battery is
charging. In case of a mains power supply failure, the luminaire
enters in emergency mode and will light automatically. When the
mains power supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation instructions on page
3.
Battery Charging
The battery charging procedure is controlled by the processor,
thus maintaining its best possible preservation, as it extends its
duration.
Battery Cut-off
The luminaire enters this mode when the mains power supply
fails and battery has lost all its energy. During this operation the
luminaire enters the idle state and battery consumption is
negligible, in order to be protected from deep discharge.
Manual Operational Test
This test can be done by pressing the test
button. The light source and the emergency circuit of the device
are monitored for 3 sec. The manual test can be conducted only
if the mains power supply and the battery are connected. During
this test period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations of the manual test and is
conducted automatically every 15 days. In order to be
performed, the mains power supply and the battery should be
connected.
Automatic Autonomy Test
The Automatic Autonomy Test measures the device's back up
operation and emergency duration. This test is conducted
Page 1 from 4
SELF TESTING MAINTAINED EMERGENCY LUMINARY
GR-2100/ST/M
3.6V/600mAh
Battery and charge Fault indication LEDs, TEST button
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
(for LED MODULE Specs. see page 2)
220-240V AC/50-60Hz
3.3W / 3.6VA
16 h
1.5 h
12 White LEDs
100lm / 100lm
22m
IP30
5 to 40 C
up to 95%
ABS/PC,PC
292 x 111 x 54 mm
463gr.
3 years (1 year for the battery)
automatically every 6 months. In order to be performed, the
mains power supply and the battery should be connected and
fully charged. If the battery is not fully charged, the test is
postponed until the battery is completely charged. If during this
test, the autonomy is less than nominal, the battery fault led turns
on continuously and the battery must be replaced.
Emergency Operation
The autonomy duration of battery during emergency mode is at
least 90 or 180 minutes, depending on the model. During
emergency mode, a light source test is also performed.
Resetting Errors
Push the Test button for more than 10 seconds, to delete all the
indicated LED errors. Then the device enters regular operation
mode.
Indication LED status (with connected mains power supply).
Charge (Green LED)
Blink: Battery is charging.
On: Good charge condition.
Οff: No battery (No charging current
or disconnected battery).
Fault (Red LED)
Οn : Faulty LED strip (must be replaced) or emergency circuit
(must be checked by an authorized personnel).
Blink (With Charge LED ON): Autonomy or low battery problem
(the battery must be replaced).
Οff: LED strip and battery ok.
Connection to module
This luminaire can be connected to any of the following modules:
Remote module, address module, wireless module and fault
relay module. If you connect it to a module that supports inhibit
or rest mode, you should know that these commands can be
cancelled only during normal mode (ie. not in emergency). For
installation refer to step 5 of the istallation procedure in page 3.
Also refer to the user's manual of each module for additional
information.
GR-2110/ST/M
3.6V/1.5Ah
24 h
3 h
o
544gr.
923211006_09_001
Need help?
Do you have a question about the GR-2110/ST and is the answer not in the manual?
Questions and answers