ENERGYSTORE Remote Area Power Systems Installation, Operation and Maintenance ENERGYSTORE SOLAR Australia: 1300 365 959 New Zealand: 09 257 2883...
Page 2
ENERGYSTORE SOLAR Safety Instructions Carefully read this manual in all its parts upon receipt of ENERGYSTORE SOLAR Batteries. Lead-acid Solar Batteries are components of a system and although they are maintenance free, they require suitable precautions and behavioural norms to guarantee safe working conditions and to ensure maximum performance of the battery during its entire life.
Page 3
Take all precaution when using the main supply. Make sure that the first aid kits and fire extinguishers are easily accessible. Used batteries contain recyclable materials. They must not be disposed with household waste but as a special waste. Methods of return and recycling must conform to the regulations in operation at the site where battery is located.
Page 4
2. Installation Battery Room WARNING The cells are already charged when delivered and should be unpacked with care. Avoid short circuiting terminals of opposite polarity. Before installing the cells, clean all parts. Remove the short circuit ABS protectors from the terminal posts and clean them with a soft clean cloth.
Page 5
Check tightness and cleanliness When all cells have been connected up check the terminal voltage, this should equal to the sum of all the individual cell voltages. If the total voltage is different to the calculated figure, some cells may have been installed correctly. Connect the positive terminal of the battery to the positive terminal of the charger and the battery negative to the charger negative.
Page 6
(b) Equalizing / Boost charge 2.35 – 2.4V Chargers usually have two adjustable charging voltages: one for the “floating” charge and one for the “equalizing” charge (also known as “boost”, “high rate” or “recharge”). The equalizing charge is generally required: When the total voltage spread between cells is greater than 0.04V under float charging conditions.
Page 7
6. Battery Maintenance ENERGYSTORE ESPV are sealed, maintenance-free, lead-acid batteries and need no water addition. The containers and lids must be kept dry and free from dust. Cleaning must be done only with a damp cotton cloth. Avoid static discharges generated during cleaning. Every 6 months Check for any evidence of damage to the battery and equipment.