Table of Contents 1 Introduction 2 Mechanical Installation 3 Electrical installation 4 Function table - for rate/frequency only display 5 Function table - for total only display 6 Function table - for both total and rate/frequecy display 7 Explanation of functions 8 Specifications 9 Guarantee and service 2 of...
Introduction This manual contains information for the installation and operation of the PM4-TR Monitor. The instrument may be set to operate as a ratemeter or totaliser or allow toggling between rate and total displays. The SEt OPER function (see section 7.66) allows selection of one of these three modes.
Mechanical Installation Choose a mounting position as far away as possible from sources of electrical noise such as motors, generators, fluorescent lights, high voltage cables/bus bars etc. An IP65 or IP67 access cover which may be installed on the panel and surrounds is available as an option to be used when mounting the instrument in damp/dusty positions.
Electrical installation Electrical installation The PM4 Panel Meter is designed for continuous operation and no power switch is fitted to the unit. It is recommended that an external switch and fuse be provided to allow the unit to be removed for servicing. The plug in, screw type, terminal blocks allow for wires of up to 2.5mm to be fitted.
Page 6
WS-03102 anemometer and Rotapulse flowmeter are commonly supplied with this model. Wiring and link settings are as shown below: WS-03102: Wiring - Anemometer WS REF terminal to PM4-TR GND terminal 8 and WS SIG terminal to PM4-TR IN terminal 11. Shield to LD-TR GND terminal 8.
Page 7
FREQ RNGE = Lo F, t.out SECS set as required. For kph scaling RAtE INPt = 30, RAtE SCLE = 82.0 For m/s scaling RAtE INPt = 30, RAtE SCLE = 22.8 Rotapulse: Colour code: Black - signal + (terminal 11), Brown - +18V (terminal 10 on AC powered models), Blue - ground (terminal 8).
Page 9
Notes HYST2 link should be in for signals between 1V and 5V amplitude (low level of the input pulse must be below 0.5V). HYST link should be in for signals greater than 5V amplitude (low level of the input pulse must be below 2V). If the input pulse amplitude is between 100mV to 1V both HYST and HYST2 links can be taken out but the input will be at its highest sensitivity and will be more prone to interference due to electrical noise and it therefore not normally recommended.
Page 10
Input circuit diagram 10 of PM4TRMAN-2.7-0...
Page 11
3.10 Configuring the input board Link settings are only required for mains synchronisation. Dismantle the instrument as described in “Input/output configuration”. Insert the links into the appropriate location on the pin header. PM4TRMAN-2.7-0 11 of...
Page 12
3.11 Input Output Configuration If you need to alter the input or output configuration link settings proceed as follows: 1. Remove the plug in terminals from the rear of the instrument 2. Remove the 4 x self tapping screws from the back cover then remove the back cover by pulling it away from the instrument 3.
Function table - for rate/frequency only display The function table below shows the functions which will be seen when the Set OPER function is set to FREQ. Note: the order in which the functions appear on the display may not be exactly as shown below. The availability and order of functions is determined by choice of function settings and options fitted.
Page 14
bAr, S.dot, Bargraph type for instruments 7.15 tYPE d.dot, with bargraph display (seen C.bAR or only on bargraph display r.dot instruments) dGOP bcd, b.SCL, bin2 Digital output option mode 7.16 bin or bin2 ( Optional) dG.OP AIo or AHi Digital output option polarity 7.17 ( Optional) 0, 1 or 2...
Page 15
INPt RISE or RISE Input edge 7.47 EdGE FALL dISP RAtE or RAtE Display rate or period 7.42 PERd dISP 0, 0.01, 0.02 Period display range 7.43 RNGE or 0.00.02 tout 1 or 9999 Rate display time out 7.44 SECS AUGE 1 or 9999 Average display seconds...
Page 16
bAUd 300, 600, 9600 Baud rate for serial 7.67 RAtE 1200, 2400, communications ( Optional) 4800, 9600, 19.2 or 38.4 PrtY NONE, EUEN NONE Parity for serial communications 7.68 or odd ( Optional) O.Put dISP, Cont, Cont Output for serial 7.69 POLL, A.buS communications ( Optional)
Function table - for total only display The function table below shows the functions which will be seen when the Set OPER function is set to totL. Note: the order in which the functions appear on the display may not be exactly as shown below. The availability and order of functions is determined by choice of function settings and options fitted.
Page 18
bAr_ Bargraph low value (seen only Any display 7.13 on bargraph display value instruments) bAr~ 1000 Bargraph high value (seen only Any display 7.14 on bargraph display value instruments) bAr, S.dot, Bargraph type for instruments 7.15 tYPE d.dot, with bargraph display (seen C.bAR or only on bargraph display r.dot...
Page 19
R.INP NONE, NONE Remote input function 7.48 P.HLd, d.HLd, Hi, Lo, HiLo, ZERO, SP.Ac, No.Ac, dISP, duLL or G.rSt P.but NONE, Hi, NONE P button function 7.49 Lo, HiLo, ZERO, dISP, FUNC or G.rSt ACCS OFF, EASY, Access mode 7.50 NONE or ALL SPAC A1, A1-2 etc.
Page 20
PrtY NONE, EUEN NONE Parity for serial communications 7.68 or odd ( Optional) O.Put dISP, Cont, Cont Output for serial 7.69 POLL, A.buS communications ( Optional) or M.buS Addr 0 to 31 Instrument address for serial 7.70 communications ( Optional) ( Optional)—this function will only be accessible if the relevant option is fitted Relay table Record your relay settings in the table below...
Function table - for both total and rate/frequecy display The function table below shows the functions which will be seen when the Set OPER function is set to both. When both mode is used the functions available allow for both the ratemeter and totaliser scaling and setup.
Page 22
Functions in this second table are available only in CAL mode or if ACCS is set to ALL Display Function Range Default Your Ref/Page record brGt 1 to 15 Display brightness level 7.10 duLL 0 to 15 Display remote brightness 7.11 switching bAr_...
Page 23
RAtE Rate scale factor Any display 7.30 SCLE value PErd 0, 0.00.02 Period display decimal point 7.31 dCPt selection etc. PERd Rate input scale factor Any display 7.32 INPt value PERd Period scale factor Any display 7.33 SCLE value tOtI 0 to number of Total display decimal point 7.34...
Page 24
R.INP NONE, NONE Remote input function 7.48 P.HLd, d.HLd, Hi, Lo, HiLo, ZERO, SP.Ac, No.Ac, dISP, duLL or G.rSt P.but NONE, Hi, NONE P button function 7.49 Lo, HiLo, ZERO, dISP, FUNC or G.rSt ACCS OFF, EASY, Access mode 7.50 NONE or ALL SPAC A1, A1-2 etc.
Page 25
dFIt RAtE, PERd RAtE Default display 7.65 dISP or totI S.Prd, FREQ Set display operation 7.66 OPER PERd, FREQ, totL or both bAUd 300, 600, 9600 Baud rate for serial 7.67 RAtE 1200, 2400, communications ( Optional) 4800, 9600, 19.2 or 38.4 PrtY NONE, EUEN NONE...
Explanation of functions The PM4 setup and calibration functions are configured through a push button sequence. The three push buttons located at the rear of the instrument (also at the front on some display options) are used to alter settings. Two basic access modes are available: FUNC mode (simple push button sequence) allows access to commonly set up functions such as alarm setpoints.
Page 27
This mode is chosen by selecting FREQ at the OPER function. The ratemeter mode can operate in one of 4 basic ways to give different display options namely: 1. Rate display, high frequency If HIF is selected at the FREQ RNGE function the instrument acts as a general purpose fre- quency/ratemeter/tachometer.
Page 28
Easy alarm relay adjustment access facility The display has an easy alarm access facility which allows access to the alarm setpoints simply by pressing the F button at the front or rear of the instrument. The first setpoint will then appear and changes to this setpoint may be made to this setpoint via the ^ or v buttons.
Page 29
2.0 with a A1PS value of 50 then the relay will remain energised for 2.0 seconds every time the display passes a multiple of 50. Note: If the pass time exceeds the time taken to reach consecutive pass values then the instrument will “store” any relay operations it does not have time to activate and will perform these activations when the total display update rate allows.
Page 30
value. To set a high alarm value go to the A Hi function and use the ^ or v push buttons to set the value required then press F to accept this value. The high alarm setpoint may be disabled by pressing the ^ and v push buttons simultaneously.
Page 31
Alarm relay trip time A tt Display: 0 to 9999 Range: Default Value: 0 Displays and sets the alarm trip time in seconds. The trip time is common for both alarm high and low setpoint values. The trip time provides a time delay before the alarm relay will activate when an alarm condition is present.
Page 32
Alarm relay setpoint or trailing operation A SP or A t1 etc. Display: A SP or A t1 etc. Range: Default Value: A SP Relay operation independent setpoint or trailing setpoint, this function only be seen where more than one relay is fitted. Each alarm relay, except relay 1, may be programmed to operate with an independent setpoint value or may be linked to operate at a fixed difference to another relay setpoint, known as trailing operation.
Page 33
Example: With duLL set to 4 and brGt set to 15 and the R.INP function set to duLL the display brightness will change from the 15 level to 4 when a switch connected to the remote input terminals is activated. 7.12 Preset value P.SEt...
Page 34
illuminated). May be independently set anywhere within the display range of the instrument. To set bargraph high level go to the bAr~ function and use the ^ or v push buttons to set the value required then press F to accept this value. 7.15 Bargraph type for instruments with bargraph display bAr tYPE...
Page 35
7.16 Digital output option mode dGOP Display: bcd, b.SCL, bin or bin2 Range: Default Value: bin2 Seen only with the 16 bit digital output option. Refer to the separate “PM4 Panel Meter Optional Output Addendum” booklet supplied when this option is fitted. Selections available are: bin2 (signed binary) i.e.
Page 36
7.20 Digital output option high value diG~ Display: Range: Any display value Default Value: 1000 Seen only with the 16 bit digital output option. Refer to the separate “PM4 Panel Meter Optional Output Addendum” booklet supplied when this option is fitted. Determines the high scaling point for the b.SCL mode and has no effect on other modes.
Page 37
7.23 Second analog output option low value REC_ Display: Range: Any display value Default Value: 0 See REC_ function 7.21 for description of operation. 7.24 Second analog output option high value REC~ Display: Range: Any display value Default Value: 1000 See REC~ function 7.22 for description of operation.
Page 38
7.27 Analog output PI control rec ctrI Display: on or OFF Range: Default Value: OFF Analog output mode - seen only when analog output option is fitted. This function allows selection of on or OFF for PI control analog output. If set to OFF the analog output operates as a retransmission output and uses the functions described in this chapter.
Page 39
work together as follows: RAtE SCLE Input frequency (Hz) Display = RAtE INPt Note: if either the rate input or rate scale factor are set to 0 the scaling will be 1:1 i.e. a 1Hz input will give a display of 1 i.e. it is assumed that there are no scaling factors. Example: If an encoder sensing revolutions of a shaft puts out 20 pulses per revolution a RAtE INPt of 20 and a RAtE SCLE of 60 will give a display in RPM.
Page 40
7.34 Total display decimal point selection tOtI dCPt Display: 0 to number of display digits minus 1 Range: Default Value: 0 Total decimal point selection - Displays and sets the decimal point position for the total display. For example selecting 0 will mean no decimal points (e.g. a display such as 25), 0.1 means 1 decimal point place (e.g.
Page 41
display will round up to the nearest total value. When set to on the display will not round up. For example with totL INPt set to 10 and totL SCLE set to 1 (i.e. 10 pulses for 1 count) and with the display just reset to zero if truncation is OFF then after 6 input pulses the display will round up to show 1.
Page 42
These modes allow a choice of how the grand total will be displayed. The total may be switched between up and down count via the “SET” input and the SINP function. Ensure that the “SET” link is in before attempting to use this input to change count direction. The following table illustrates each mode of operation.
Page 43
7.41 Input edge INPt EdGE Display: RISE or FALL Range: Default Value: RISE Displays and sets the pulse input edge on which triggering will occur. If set to RISE then the rising edge of the input pulse will trigger the input. If set to FALL then the falling edge of the input pulse will trigger the input.
Page 44
dISP RNGE PERd dCPt PERd INPt PERd SCLE Value displayed 1000 5000 0.003 0.00.01 0.500 0.01 0.00 1.00 500.0 0.00.02 0.00.02 0.00.01 0.05.00 0.00.02 0.00.02 0.01.00 0.50.00 With the PERd INPt function set to 1000 the display will time in seconds rather than milli seconds.
Page 45
counted over which the rolling average display will be calculated. For example if the AUGE SECS is set to 60 and the AUGE cnt is set to 10 then the rolling average displayed will be the average of the last ten 60 second averaged periods. 7.47 Input edge INPt EdGE...
Page 46
is set to P.SEt then the display will go to the preset value when reset. This function is not applicable to rate or period displays. SP.Ac - setpoint access only. This blocks access to any functions except the alarm setpoint functions unless the remote input pins are short circuited or entry is made via CAL mode.
Page 47
7.51 Setpoint access mode SPAC Display: A1, A1-2 etc. Range: Default Value: A1 Setpoint access - seen only if more than 1 relay fitted. Sets the access via FUNC mode and “easy alarm access” mode to the alarm relay setpoints. The following choices are available: A1 - Allows setpoint access to alarm 1 only.
Page 48
7.54 Second analog output operation mode rEC2 Display: rAtE or totL Range: Default Value: rAtE Seen only when the SEt OPER function is set to both. Sets the operation mode for the second optional analog retransmission. The output can be set to retransmit the total (totL) or rate (rAtE).
Page 49
7.58 High overrange visual warning limit value HIGH dISP Display: Any display value or OFF Range: Default Value: OFF High overrange limit value - the display can be set to show an overrange message if the display value rises above the HIGH dISP setting. For example if HIGH dISP is set to 1000 then once the display reading rises above 1000 the message -or- will flash on and off...
Page 50
7.61 Totaliser counter reset value c.rSt Display: ZERO or PSEt Range: Default Value: ZERO The reset terminal operation can be programmed to cause the display to reset to either zero or the selected preset value. Choose either ZERO or PSEt to select the required operation. PSEt is most commonly selected when the display is required to count down (S.INP set to Lo) from a preset value.
Page 51
then the display will reset when the display value reaches the pass value (set at A1PS) and the relay will activate and will remain activated for the time set at the A1Pt function. 7.65 Default display dFIt dISP Display: RAtE, PERd or totI Range: Default Value: RAtE Seen only in both mode.
Page 52
7.68 Parity for optional serial communications PrtY Display: NONE, EUEN or odd Range: Default Value: NONE Set parity - seen only with serial output option. Refer to the separate “PM4 Panel Meter Optional Output Addendum” booklet supplied when optional outputs are fitted. Select parity check to either NONE, EUEN or odd.
Page 53
turn off power to the instrument, wait a few seconds and then restore power. 7.72 Examples Example - RPM display A proximity sensor connected to a flywheel produces 20 pulses per revolution. The instrument is required to display in RPM with 1 decimal point place. In this example 20 pulses per second would equal 1 revolution/sec which equals 60 RPM.
Page 54
9. Use the ^ or v push button to change the setting to 3600. 10. Press F to accept the change then either press P to exit of continue pressing and releasing F until the FUNC End message is seen and the unit returns to normal measure mode. Example - Flow rate display See previous examples for detailed steps showing how to alter functions.
Page 55
7. Use the ^ or v push button to alter the previous scale value to the new scale value of 1. 8. Press F to accept the change then either press P to exit of continue pressing and releasing F until the FUNC End message is seen and the display returns to normal measurement mode.
Page 56
Total table for Rota Pulse flow meter with 36.5 pulses per metre flow Pipe dia. Litres Kilolitres or m totI INPt = 74316 totI INPt = 74316 25mm totI SCLE = 1000 totI SCLE = 1 totI INPt = 29029 totI INPt = 29029 40mm totI SCLE = 1000...
Specifications Technical specifications Total/Rate input: Link selectable for various sensor types, see section 3.7. Maximum input voltage is 48VDC or RMS with appropriate link settings. Totaliser functions: Scaleable up or down counter. Total and grand total memory. Ratemeter functions: Scaleable rate display. Period display available when low frequency input range is selected.
Physical Characteristics Bezel Size: DIN 48mm x 96mm x 10mm Case Size: 44mm x 91mm x 120mm behind face of panel Panel Cut Out: 45mm x 92mm +1mm/-0mm Connections: Plug in screw terminals (max. 2.5mm wire) Weight: 400 gms basic model, 450 gms with option card Guarantee and service The product supplied with this manual is guaranteed against faulty workmanship for a period of two years from the date of dispatch.
Need help?
Do you have a question about the PM4-TR and is the answer not in the manual?
Questions and answers