Enertech Nu-way MULTIPLEX ENERGYSTREAM ES Series Installation, Commissioning & Maintenance Instructions

Nozzle-mix gas burner

Advertisement

Quick Links

Installation, Commissioning & Maintenance
MULTIPLEX
ENERGYSTREAM nozzle-mix gas burner

GAS SUPPLY

Ensure that the gas pressure is the correct type and is available at a suitable pressure. Standard valve trains
will accept gas at pressures up to 70 mbar (28 in wg). For higher pressures, please consult Nu-way.
The burner assembly should not be used to support the gas supply pipework, suitable brackets or hangers
should be used for this purpose. Care should be taken to ensure that the supply pipework is large enough to
prevent excessive pressure drops and that connections are gas-tight. The gas line should be purged and
pressure-tested in accordance with any local legislation or gas authority requirements.

ELECTRICAL SUPPLY

The electrical supply must be provided with an isolator adjacent to the burner; if a separate control panel has
been supplied by NU-WAY LIMITED the isolator included in this is acceptable.
Wiring of the burner should be in accordance with the appropriate wiring standards, and the final electrical
connections to the burner should be in flexible conduits. It is vital that the live and neutral wires are connected
to their appropriate terminals as reversal could present a hazard; also the earth bonding must be checked to
ensure a good connection (poor earth connections are often the cause of faulty burner operation when using
flame probe detection). GAS PIPING MUST NOT BE USED FOR EARTHING.
All electrical interlocks should have been installed and tested for correct operation before commissioning.

COMMISSIONING

The procedure below is given as a guide to commissioning, which must be undertaken by a trained and
experienced combustion engineer. This procedure should be followed not only on first lighting the burner, but
also when any repairs have been carried out, or it has been out of commission for any length of time.

INSPECTION

1.
Ensure that all mechanical and electrical drawings relating to the plant are available.
2.
Check that all gas and electrical supplies to the burner are turned off.
3.
Check the whole of the plant in which the burner is operating to ensure it is safe to light the burner and
that any safety interlocks are in the 'safe' position.
4.
Check that no moving part of the plant will damage any part of the burner or its gas or electrical
supplies, and that no passing traffic will come into contact with it.
5.
Check that gas is available at the burner stop valve.
page 1
SERIES
ES

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Nu-way MULTIPLEX ENERGYSTREAM ES Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Enertech Nu-way MULTIPLEX ENERGYSTREAM ES Series

  • Page 1 Installation, Commissioning & Maintenance MULTIPLEX SERIES ENERGYSTREAM nozzle-mix gas burner GAS SUPPLY Ensure that the gas pressure is the correct type and is available at a suitable pressure. Standard valve trains will accept gas at pressures up to 70 mbar (28 in wg). For higher pressures, please consult Nu-way. The burner assembly should not be used to support the gas supply pipework, suitable brackets or hangers should be used for this purpose.
  • Page 2 ACTIVATION Before gas is admitted to the burner, at least two faultless ‘dry runs’ must have taken place. No interlock may be by-passed during these runs. Dry Run 1. By means of pressure test nipples and with both manual isolating valves closed, using air or inert gas, test the burner valvetrains for leaks, and the safety shut-off valves for pressure tightness.
  • Page 3 FAULT FINDING Fault Possible Cause Remedy 1. Combustion air fan does not a. No air pressure in duct (positive a. Switch on main duct fan. start. or negative). b. Combustion air switch set too b. Reset switch low. c. Duct air pressure switch c.
  • Page 4 FAULT FINDING (cont…) Fault Possible Cause Remedy 7. Main flame goes out after a. Low gas pressure switch (if a. Reset Pressure switch. lighting. fitted) set too high. b. High gas pressure switch (if b. Reset pressure switch. fitted) set too low. c.
  • Page 5 Enertech Limited, P O Box 1, Vines Lane Droitwich, Worcestershire, WR9 8NA Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: info@nu-way.co.uk Web: www.nu-way.co.uk...