Power Supply
The LP150/LP250 is a power-limited power supply and battery charger that will convert 120 VAC / 60Hz input into field-selectable 12 VDC
or 24 VDC Class 2 rated outputs (one continuous, one switchable). It is intended for use in applications with UL listing requirements (see
specifications below for specific listings).
This instruction covers:
LP150
PS cabinet + board (1.5A), battery wire kit, keylock
LP250
PS cabinet + board (2.5A), battery wire kit, keylock
LP250RDB4
PS cabinet + board (2.5A), battery wire kit, keylock,
RDB4 board *
Power Supply
with hinged cover
PS150/250 Specifications:
Input
LP150: 120 VAC, 1A, 60Hz
Output
LP150: 12 VDC (13.2V nominal) or 24 VDC (26.4V nominal), 1.5A, Class 2 rated
LP250 (LP250RDB4): 12 VDC (13.2V nominal) or 24 VDC (26.4V nominal), 2.5A, Class 2 rated
Output Protection
DC OUT and CONTROL OUT are protected from overload or shorts via self-resetting electronic protection circuit
Battery Protection
PTC
Environment
32°-120° F (0°- 49° C), up to 85% relative humidity, indoor use only, protected area
Compliance
UL294, UL603, Access control performance levels: Attack: I, Line security: I, Endurance: IV, Standby power: III
(LP150) and II (LP250/LP250RDB4), CSA22.2 NO. 205, CSFM, FCC
Battery Backup
Requires 12V, 7AH max. rechargeable sealed lead acid battery: (1) for 12V, (2) for 24V output.
Battery maximum dimensions: 3-3/4" H x 6" W x 3" D
See typical backup times in Section 2
See Section 8 for maintenance of battery
Control Input / Output
Input: Normally closed, requires dry contact rated at 24 VDC, 10mA
Output: Powered NC/NO contacts rated at 24 VDC, 2.5A
AC Status
Indicator: Green LED
Relay contacts: NO/NC contacts rated at 24 VDC, 1A
DC Output Status
Indicator: Red LED
Battery Status
Indicator: Red LED
Relay contacts: NO/NC contacts rated at 24 VDC, 1A
Enclosure
13" H x 12-5/8" W x 3-1/4" D (8 knockouts, 1/2" or 3/4")
LP150, LP250
LP150B, LP250B
LP250RDB4
Keylock
PS150/250
Enclosure
+ Board
Battery Wire Kit
LP150B
LP250B
LP250: 120 VAC, 1.2A, 60Hz
Installation Instructions
PS board only (1.5A), 4 mounting screws
PS board only (2.5A), 4 mounting screws
PS board
RDB4 board included
*
with LP250RDB4 only
and is covered in
separate instruction

Advertisement

Table of Contents
loading

Summary of Contents for Locknetics LP150

  • Page 1 LP250RDB4 The LP150/LP250 is a power-limited power supply and battery charger that will convert 120 VAC / 60Hz input into field-selectable 12 VDC or 24 VDC Class 2 rated outputs (one continuous, one switchable). It is intended for use in applications with UL listing requirements (see specifications below for specific listings).
  • Page 2: Installation Overview

    WARNING To avoid risk of electric shock, turn off AC power before installing or servicing LP150/LP250 power supply. 1. Mount unit in a protected area per Section 2. 2. Select voltage (12 or 24 VDC) per Section 3.
  • Page 3: Mounting Hole Dimensions

    Battery mounting to be as shown 3¹⁄₄" Battery Backup Time LOAD BACKUP TIME (HOURS) CURRENT (AMPS) LP150 LP250 1.25 Calculated battery backup time based on charging time of 48 hours at a temperature of 77° F (25° C).
  • Page 4 Battery connected and red LED charging or providing battery backup BAT STATUS NC to C: open Battery not connected or LP150 NO to C: closed battery low LP250 Battery connected and STATUS NC to C: closed charging or providing battery...
  • Page 5 Typical Wiring FS & FSE device connected to PS board with FACP override FACP CONTROL MAGLOCK CONTROL LP150/250 E-STRIKE CONTINUOUS DC OUTPUT Operation: 1. CONTROL IN controls the operation of devices connected to the NO or NC terminals. 2. Opening of the FACP contacts will unpower the CONTROL OUT NC contacts and power the NO contacts.
  • Page 6 PS150B and PS250B Installation Enclosure cutaway shown for clarity Interior of enclosure 6-32 x 1/4" (4) Wire run lengths • Use the following table to estimate the gauge of wire required for the application. • Wire length based on 15% voltage drop at 12 or 24V using stranded copper wire. •...
  • Page 7 Secure enclosure door If No Keylock If Keylock Enclosure will be secured with 2 Remove knockout and insert key cylinder and secure with nut as shown screws as shown (done as last step) exterior of door #6 x 3/8" (2) interior of door AC Status indicator...
  • Page 8: Maintenance

    Maintenance Unit should be tested at least once a year for proper operation as follows: Voltage Output: • Verify the proper DC output voltage by measuring the DC+ and DC- terminals. Fire Alarm Release (if used): • Verify proper operation by opening the wiring to the CONTROL IN input. Confirm that the locks controlled by the CONTROL OUT output unlocked properly.
  • Page 9 LP250RDB4 Le LP150/LP250 est un bloc d’alimentation limitée en puissance et un chargeur de batterie qui convertissent l’alimentation de 120 V/60 Hz en puissance nominale de classe 2 de 12 ou 24 VCC sélectionnables sur site (continue et commutable). Il est destiné à être utilisé...
  • Page 10 ATTENTION Pour éviter tout risque de décharge électrique, mettez l’appareil hors tension avant d’installer ou de réparer l’alimentation LP150/LP250. 1. Installez l’appareil dans une zone protégée conformément à la section 2. 2. Sélectionnez la tension (12 ou 24 V) selon la section 3.
  • Page 11 COURANT DE TEMPS DE SAUVEGARDE (HEURES) CHARGE (AMPS) LP150 LP250 1.25 Le temps de sauvegarde calculer de la batterie basé sur un temps de charge de 48 heures à une température de 77 ° F (25 ° C).
  • Page 12 LED rouge  Batterie connectée et en activé charge ou fournissant une batterie de secours BAT STATUS LP150 Batterie non LP250 Normalement fermé à C : ouvert connectée ou Normalement ouvert à C : fermé ÉTAT batterie faible...
  • Page 13 Câblage typique Dispositif FS et FSE connecté à la carte PS avec neutralisation FACP FACP ENTRÉE DES CONTRÔLES MAGLOCK SORTIE DES LP150/250 GÂCHE CONTRÔLES ÉLECTRIQUE FSE SORTIE CC SORTIE CONTINUE Opération : 1. CONTROL IN contrôle le fonctionnement des appareils connectés aux bornes NO ou NC.
  • Page 14 Installation de PS150B et PS250B Vue en coupe du boîtier pour plus de clarté Intérieur de l'enceinte 6-32 x 1/4 po (4) Longueurs de fil • Utilisez le tableau suivant pour estimer le calibre de fil requis pour l’application. • Longueur de fil basée sur une chute de tension de 15 % à...
  • Page 15 Porte sécurisée Si pas de serrure Si une serrure est présente Le boîtier sera fixé avec 2 vis Retirez la découpe, insérez le barillet et fixez-le avec l'écrou comme indiqué comme indiqué (à la dernière étape) extérieur de la porte # 6 x 3/8 po (2) intérieur de la porte...
  • Page 16: Dépannage

    Entretien L’unité doit être testée au moins une fois par an pour vérifier son bon fonctionnement, comme suit: Tension de sortie: • Vérifiez la tension de sortie CC appropriée en mesurant les bornes DC + et DC-. Déclenchement d’alarme incendie (si utilisé): •...

This manual is also suitable for:

Lp250Lp150bLp250bLp250rdb4

Table of Contents