Summary of Contents for ERS AK 6000
Page 1
AK 6000 Maga Wood Gasifying Boilers Control System User Manual Elektronické riadiace systémy s.r.o. Polianky 18, 841 01 Bratislava www.ers.sk email: ers@ers.sk Tel: 421 2 693 07 000...
AK6000 - prevádzkový manuál Specification This document is intended for use with AK6000 – the electronic system for wood gasyfying boilers control. Terminology AK6000.X The modular electronic control system for wood gasyfying heat-water or heat-air boilers. On the basis of the choosed program effectively optimizes combustion procesess so the boiler is able to generate appropriate medium in heating system.
AK6000 - prevádzkový manuál Important Symbols Warning - danger or risk of injury Important note or statement Safety Instructions Please read these instructions carefully before using the AK6000 control unit Do not use the boiler until completely installed When the boiler is ON you can not do the following o remove enclosure from the electrical parts - for example electronic modules, fans, sensors, thermostat etc.
AK6000 - prevádzkový manuál CONTROL SYSTEM CONFIGURATION Basic Configuration AK6000.0 This automatic system is intended to control the producing of heat-water or heat-air in wood gasyfying boilers. Basic principle of the function is regulation of the water temperature by means of setting the amount primary air in combustion fireplace of boiler. Supply of air is controlled by continous influence to the suction fan operating speed.
AK6000 - prevádzkový manuál GUIDE TO THE CONTROL UNIT Operating Points AK6000.X - graphic display, 128 x 64 pixels, LED backlight for getting information - duoLED – total status OK ( green ) / Err ( red ) ▲ - button - increasing adjusted value or switching depiction of the measured values ◄...
AK3000 – User Manual Basic Modes AK6000.X Boiler is OFF ENTER Short pressing of the turns the boiler ON. ENTER Long pressing of the gets the operator into the parameter settings Start of the heating Fan is working with 100% top speed ◄...
AK3000 – User Manual Fuel supply ENTER Double click of the button ( function ) prepares the boiler to fuel supply– main fan goes to 100% top speed in suction version or to 0% in blower version Door opening Wait 10 seconds after door is depicted on the display - fan will absorb the combustion ...
Page 8
AK3000 – User Manual OPERATING Starting AK6000.X Boiler is turned ON by connecting the power cord into the AC outlet. In 10 seconds will the basic view displayed Basic view Required Boiler Temperature Setup AK6000.X ENTER Starting at basic view we must hold the button two seconds long: ENTER Basic view goes to the frame 1 where we use short click on the...
Page 9
AK3000 – User Manual User Parameter Setup AK6000.X ENTER Starting at basic view we must hold the button two seconds long: ▲ ENTER Basic view goes to the frame 1 where we use button till we get to the frame 2. Short click on the and we are in ▲...
Page 10
AK3000 – User Manual Current Time Setup AK6000.X ENTER Starting at basic view we must hold the button two seconds long: ▲ ENTER Basic view goes to the frame 1 where we double use button till we get to the frame 3. Short click on the and we ▲...
AK3000 – User Manual Version of software AK6000.X Sotware implemented in hardware modules we can verify in frame 6 „Info“. We can see a version and date with exact time of software generation here. ENTER Starting at basic view we must hold the button two seconds long.
Page 12
AK3000 – User Manual ▲ ENTER By means of the we can set the first flashing digit of the PIN xxxx and by button we confirm it. So we can ENTER enter rest of the PIN. With button we can get to the frame 2.8.1.1. : ▲...
Page 13
AK3000 – User Manual Service Parameter Setup 2 AK6000.X We can use service parameter setup 2 to configurate chosen „hardware“ properties of control unit. Improper setup of service parameters can result in risk of boiler incorrect behaviour or damaging some amount of boiler. Just the qualified service can properly act in this area. You need to TURN OFF the boiler before setting in this area.
Page 14
AK3000 – User Manual Component Service Activation AK6000.X In this section we can manually activate connected components as fans or water pump for service purpose. Improper setup of service parameters can result in risk of boiler incorrect behaviour or damaging some amount of boiler. Just the qualified service can properly act in this area. You need to TURN OFF the boiler before setting in this area.
Electric Parameters AK6000.X AK6000D Input voltage 7,5VDC Input current 0,06A Operating temperature max 45°C Case IP20 Connection with AK5000S 20-pin conector PFL AK5000S Input voltage 230VAC, 50Hz ±10% cord 3m, H05VV-F 3Gx0,75, PVC, temperature range -15 až +70°C Full load 1,6A Temperature range max 45°C...