Download Print this page

Baso L62AA Installation Instructions Manual

Safety shutoff device

Advertisement

Quick Links

L62AA BASO® Safety Shutoff Device
Installation
!
WARNING: Risk of Fire or Explosion.
Do not use the L62AA in Liquefied Petroleum
(LP) gas applications. The L62AA is for use with
natural gas only. Pilot gas is not 100% shut off
and will continue to flow with the loss of pilot
flame. Use of LP gas may cause gas accumulation
and may result in severe personal injury or death.
IMPORTANT:
Only qualified personnel
should install or service BASO® Gas Products.
These instructions are a guide for such personnel.
Carefully follow all instructions in this document
and all instructions for the appliance.
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the L62AA.
Failure to shut off the gas supply can result in the
release of gas during installation or servicing,
which can lead to an explosion or fire, and may
result in severe personal injury or death.
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
IMPORTANT:
Make all gas installations in
accordance with applicable local, national, and
regional regulations.
IMPORTANT:
Do not loosen or tighten the
brass hex nut that fastens the brass terminal
bushing to the switch housing. The machined flats
on the terminal bushing must be parallel to the
flats on the switch housing. If not, the switch power
unit may distort and cause the safety switch to fail.
© 2017 BASO Gas Products
Part No. BASO-INS-L62AA, Rev. F
To install the L62AA.
1. Turn off power to the appliance.
2. Turn off gas at the main manual shutoff valve
adjacent to the appliance.
3. Remove the L62AA cover by loosening the
screws at the side of the device (not the brass
hex nut).
4. Mount the L62AA in any convenient position
using the mounting holes provided. See Figure 1
for mounting hole locations.
5. Push the circuit wires through the conduit
opening on the bottom of the L62AA, strip the
ends of the wires just enough to put the bare
wire under the terminal screws, and attach them
to the two wire terminals (see Figure 1).
6. Replace the cover (do not loosen the brass hex
nut).
7. Attach the thermocouple securely to the pilot
burner, and screw the terminal end to the BASO
power unit terminal on the L62AA (see Figure 1
and Figure 2). Make sure that this connection is
clean. Tighten the thermocouple lead nut finger
tight plus a maximum of 1/8 turn. Do not
overtighten.
!
Do not attach both wires to one terminal on the
L62AA. Doing so bypasses and eliminates all
safety features provided by the L62AA, can lead to
an explosion or fire, and may result in severe
personal injury or death.
!
Verify that this device is wired in series electrically
with thermostats and other appliance operating
controls. Wiring the device in parallel with such
controls will defeat the safety features of this
device and may result in severe personal injury or
death.
L62AA BASO® Safety Shutoff Device
Installation Instructions
Issue Date
WARNING: Risk of Explosion or Fire.
WARNING: Risk of Explosion or Fire.
L62AA
September 14, 2017
1
www.baso.com

Advertisement

loading

Summary of Contents for Baso L62AA

  • Page 1 Do not use the L62AA in Liquefied Petroleum 2. Turn off gas at the main manual shutoff valve (LP) gas applications. The L62AA is for use with adjacent to the appliance. natural gas only. Pilot gas is not 100% shut off 3.
  • Page 2 Do not loosen brass hex Mounting Hole nut. Must be tight to BASO Power Conduit maintain continuity. Unit Terminal Opening Figure 1: View of the L62AA Without the Cover L62AA Safety Shutoff Device Pilot Valve Main Manual Power Source (”B” Valve)
  • Page 3: Setup And Adjustments

    Before leaving the installation, 7. Disconnect the thermocouple from the L62AA. The verify that the L62AA functions properly and that the main valve should close immediately. If it does not system has no gas leaks. Gas leaks can lead to an close, check for wiring errors.
  • Page 4: Repairs And Replacement

    Repairs and Replacement Check the millivoltage output of the thermocouple and milliampere dropout range at the BASO power unit terminal to see that they meet the values in Table 1 and Table 2. If the readings do not meet these values, replace the thermocouple and/or the safety shutoff device.
  • Page 5 Repairs WARNING: Risk of Explosion, Fire, or Field repairs must not be made to the L62AA safety Electric Shock. Label all wires before they are shutoff device. If the thermocouple meets the output disconnected when replacing the L62AA. Wiring...
  • Page 6: Technical Specifications

    Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original equipment manufacturer or end user is responsible for the correct application of BASO products.