CIO 308 installation and commissioning guide 4189341078 UK 1. Introduction 1.1. Warnings, legal information and safety....................3 1.1.1. Warnings and notes ........................3 1.1.2. Legal information and disclaimer ....................3 1.1.3. Safety issues ..........................3 1.2. About the installation and commissioning guide..................3 1.2.1.
Notes provide general information, which will be helpful for the reader to bear in mind. 1.1.2 Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator etc. controlled by the specific extension, the company responsible for the installation or the operation of the extension must be contacted.
CIO 308 installation and commissioning Introduction guide 4189341078 UK The general purpose of this document is to give the user important information to be used in the installation of the unit. Please make sure to read this document before starting to work with the CIO module and the controller.
Inspect for damage, and if there is evidence of such, immediately file a claim with the carrier and notify the regional DEIF sales office, your sales representative or a sales representative at DEIF's head office in Skive, Denmark.
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK 2.3 Common functions LED1 LED2 CANbus Supply Status Max 1A PT100/1000 2-wire RMI 2-wire or 3-wire Current 4-20 mA Digital Input LED1: DEIF Red – Device failure Green – Status output...
Page 7
CIO 116 can use IDs from 1 to 15 CIO 208 can use IDs from 1 to 15 CIO 308 can use IDs from 1 to 15 5. USB for firmware update The firmware of the CIO modules can be updated via the USB port.
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK 2.4 Wiring and terminals 2.4.1 Terminal overview CIO 308 LED1 LED2 CANbus Supply Status Max 1A PT100/1000 2-wire RMI 2-wire or 3-wire Digital Input Current 4-20 mA LED1: DEIF Red –...
Page 9
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK Terminal Name Description Comment +12/24 V DC Power supply 0 V DC Status Common Status output (configurable) Normally open CAN-High CAN bus interface CAN-Common CAN-Low Input A Multi-input 8...
Page 10
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK Input LED Each multi-input has its own LED, and the table below illustrates when the LED is on/off. Input type Description Digital input Input is active Input is inactive...
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK 2.4.2 CIO 308 wiring 12/24 V DC Sensor Sensor Sensor Sensor LED1 LED2 CANbus Supply Status Max 1A PT100/1000 2-wire RMI 2-wire or 3-wire Current 4-20 mA Digital Input...
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK 2.4.3 CAN bus The CIO module(s) can be configured as the only device on the CAN bus or together with an engine control- ler (ECU) on the same CAN bus as shown in the below example. CIO module(s) can be placed together with all the different engine protocols which are available in the AGC (both J1939 and CANopen), because the CIO module will adapt to the baud rate on the CANline.
Page 13
CIO 308 installation and commissioning Installation, mounting and wiring guide 4189341078 UK Option H7 is not available for use with CIO modules. Terminal Function Description CAN H CAN port C CAN L CAN H CAN port D CAN L CAN L...
CIO 308 installation and commissioning Communication guide 4189341078 UK 3. Communication 3.1 Communication setup A few parameters revolving around communication to the CIO can be accessed through the display. Through the CIO tab in the USW, full access to all the CIO parameters is available. The CIO configuration menu is accessed from the top menu bar of the USW.
The first time you open the menu, the buttons will be inactive and it is necessary to read the configuration from the controller. If the communication to a CIO 116 or CIO 308 module is lost, the AGC will continue with the last received input value.
CIO 308 installation and commissioning I/O setup guide 4189341078 UK 4. I/O setup 4.1 CIO info tab 1. Module info This section gives an overview of the specific module's ID and the software and hardware version of the mod- ule. This information is important if support is needed for the product.
Page 17
CIO 308 installation and commissioning I/O setup guide 4189341078 UK Power cycling the CIO module while there is no communication to the AGC will reset the set- tings results, and the relay will be set as a status relay until communication is established. The CIO configuration is stored in the AGC, and this means that the CIO module will be configured when the communication to the AGC is available.
Page 18
CIO 308 installation and commissioning I/O setup guide 4189341078 UK An output relay should be configured as a limit relay, otherwise an alarm will be raised when the output is activated. To use the relay in M-Logic, it must be configured as a limit relay.
CIO 308 installation and commissioning I/O setup guide 4189341078 UK 4.3 Multi-input 4.3.1 Setting up a multi-input Below is the functionality generally described. The screen changes depending on the input type (item 1 on the picture). 1. Input type This setting determines the type of signal that the sensor sends to the input. Among the options are: Pt100, Pt1000, 0-10 V, RMI, 0-20 mA, thermocoupler types and binary.
0.7 kW in 1 second. 4.3.2 Thermocoupler with cold junction compensation The CIO 308 module compensates for the cold junction. This can be done with the internal temperature measurement if the thermocoupler is connected to the CIO 308 module terminals.
Page 21
CIO 308 installation and commissioning I/O setup guide 4189341078 UK If there is a long distance to the measured object, a conductor is often used from the CIO module to a junc- tion box, where the thermocoupler is connected. In this case, it is possible to compensate by using a temper-...
4.3.3 Wire fail detection The CIO 308 module can detect wire fail if the signal goes outside the working range. It depends on the sig- nal type and working range if a short circuit or a broken cable will be detected.
Page 23
CIO 308 installation and commissioning I/O setup guide 4189341078 UK Input Wire failure low area Normal range Wire failure high area 0-10 V 1 V below lowest value Configurable 1 V above highest value in the working range in the working range...
- X.XX N.A." if needed. As example, "CIO-1.17 ###.##" would relate to CIO 308 module no. 1 input 17 with scaling "No unit 1/100" and could be changed into "Fuel tank ###.## L". The hash symbol (#) represents the digits from the measure- ment.
Page 25
CIO 308 installation and commissioning I/O setup guide 4189341078 UK AGC 200 The displayed text can be edited in the translations section, and an example of this is shown in the picture below. The unit of the measurement can also be changed in the translation setting, but the text field for the units are shared among all text fields.