3.12 $AAF

Name:Read Firmware Version
Description:The command requests the module at address
Syntax:$AAF (cr)
$ delimiter character.
AA address of reading module(00~FF)
F identifies the version command.
(cr) is the terminating character, carriage return (ODh)
Response:!AA(data)(cr) if the command is valid.
?AA (cr) if an invalid command was issued.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of response module(00~FF)
Data is the version code of the module's firmware.
Example:
Command:$01F Receive:!01050101
Read address 01 firmware version,return version 050101
Command:$02F Receive:!01040101
Read address 02 firmware version,return version 040101
RemoDAQ-8017S User's Manual
AA to return the version code of its firmware.