Download Print this page

Technical Data - Gira 2167 00 Quick Start Manual

Knx ip-router

Advertisement

Mounting the device
Observe the ambient temperature. Ensure
sufficient cooling.
 Snap the device onto a top-hat rail accord-
ing to DIN EN 60715. See image for instal-
lation position.
 Connect the external power supply to the
connection terminal (3). Recommendation:
Use white-yellow connection terminal.
 Connect KNX line with red-black bus termi-
nal (2).
 Attach cover cap over the KNX/external
power supply connection.
 Establish network connection by plugging
RJ45 plug into RJ pin jack (7).
 Insert microSD card into the card reader (8)
(IP router).
Attaching the cover cap, Fig. 3
A cover cap must be attached to protect the
bus connection from dangerous voltages in
the connection area.
 Guide bus line to the rear.
 Attach cover cap over the bus terminal until
it engages.
Removing the cover cap, Fig. 4
 Press cover cap on the sides and remove.
Start-up
Load the physical address and application
software
Use as
Physical address
Line coupler
Area coupler
Data interface
Data logger/
Clock
Start-up software from ETS 4.2.
IP router/IP interface
 Briefly press the programming button (1) (<
4 seconds).
Programming LED (4) lights up red.
 Assign physical address.
 Programming LED (4) goes out.
 Label device with physical address.
 Load application software, filter tables,
parameters, etc.
IP-router as data logger/clock
 Press the programming button (1) longer (>
4 seconds).
Programming LED (4) lights up yellow.
 Assign physical address.
 Programming LED (4) goes out.
 Label device with physical address.
 Load application software and parameters.

Technical data

KNX medium
Start-up mode
KNX rated voltage
KNX current consumption Typically 85 mA
KNX connection
External supply
voltage
Power consumption
Connection
IP communication
IP connection
Supported protocols
microSD card
Ambient temperature
Storage temperature
Installation width
Warranty
The warranty is provided in accordance with
x.y.0
statutory requirements via the retailer.
Please submit or send faulty devices postage
x.0.0
paid and with an error description to your
sales representative (retailer/installation
x.y.a
company). They will forward the devices to
the Gira Service Center.
x.y.b
TP1
S mode
DC 21...30 V
SELV
Bus connection
terminal
DC 24...30 V
2 W (for DC 24 V)
Connection ter-
minal
Ethernet 10/100
BaseT
(10/100 Mbit/s)
RJ45 pin jack
ARP, ICMP,
IGMPv3, DHCP,
AutoIP, UDP/IP
(Core, Routing,
Tunnelling,
Device Manage-
ment)
Max. 32 GByte
(SDHC)
0 °C to +45 °C
-25 °C to +70 °C
36 mm (2 MW)

Advertisement

loading