Damar D450 Installation And Operating Instructions Manual

Emergency fluorescent lighting ballast

Advertisement

Quick Links

Worldwide 4 LLC
Important Safeguards
When using electrical equipment, basic safety precau-
tions should always be followed including the
following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
All servicing should be performed by qualified personnel only.
To prevent high voltage from being on red & yellow output
leads prior to installation, battery connector must be open. Do
not join battery connector until installation is complete and AC
power is supplied to the emergency ballast.
Do not use this equipment outdoors.
This product is designed for use in UL Listed indoor fixtures
except in air handling, heated air outlet or hazardous locations.
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Do not mount near open flames or sparks.
Do not install equipment in areas of excessive moisture.
Do not use this equipment for other than intended use.
Do not attempt to service battery. Contact manufacturer for
information on service.
This product is for use with most 20W through 40W single pin
or bipin fluorescent lamps, including standard, energy saving,
circline, U-shaped, and most 26W-39W rapid-start (4pin), long
compact fluorescent lamps.
An unswitched AC power source is required. (120 or 277 VAC)
The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
This emergency ballast is for factory or field installation in
either the ballast channel or on top of the fixture.
To reduce the risk of electrical shock, disconnect both normal
and emergency power supplies before servicing by discon-
necting all AC inputs to the fixture and by disconnecting the
battery.
U
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR
DISPOSED OF PROPERLY
D450
BY
®
LISTED
LISTED
L
Ni - Cd
.
EMERGENCY FLUORESCENT
INSTALLATION AND OPERATING
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
To prevent high voltage from being present on red and
yellow output leads prior to installation, battery connector must
be open. Do not join battery connector until installation is
complete and AC power is supplied to the emergency ballast.
NOTE: Make sure that the necessary branch circuit
wiring is available. An unswitched source of power is required.
The emergency ballast must be fed from the same branch cir-
cuit as the AC ballast.
1. Disconnect AC power from the fixture. Remove the
ballast channel cover and install the emergency ballast either
in the ballast channel (see illustrations 1&2) or on top of the fix-
ture. *(See illustration 3).
2. Select the appropriate wiring diagram to
connect the emergency ballast to the AC ballast and lamp.
Make sure all connections are in accordance with the National
Electrical Code and any local regula
ILLUSTRATION 1
CHARGING INDICATOR
TEST SWITCH
BALLAST CHANNEL
COVER
PAGE 1
LIGHTING BALLAST
INSTRUCTIONS
WARNING
tions.
LIGHT
EMERGENCY
BALLAST
Item No. 00418I

Advertisement

loading

Summary of Contents for Damar D450

  • Page 1 D450 EMERGENCY FLUORESCENT LIGHTING BALLAST ® INSTALLATION AND OPERATING INSTRUCTIONS Worldwide 4 LLC SAVE THESE INSTRUCTIONS Important Safeguards When using electrical equipment, basic safety precau- INSTALLATION INSTRUCTIONS tions should always be followed including the following: WARNING READ AND FOLLOW ALL...
  • Page 2 D450 EMERGENCY FLUORESCENT LIGHTING BALLAST ILLUSTRATION 2 ILLUSTRATION 3 WIRE BUNDLE COVER EMERGENCY BALLAST CHARGING INDICATOR EMERGENCY LIGHT BALLAST 1/2" STD KNOCKOUT DRILL 1/8" TEST 7/8" HOLE W/BUSHING HOLE FOR SWITCH MOUNTING SCREWS 3. Install the test switch through the ballast channel...
  • Page 3: Operation

    D450 EMERGENCY FLUORESCENT LIGHTING BALLAST NOTE: After installing the charging indicator light and MAINTENANCE test switch, mark each with appropriate label. Although no routine maintenance is required to keep the 6. After installation is complete, supply AC power to the emergency ballast functional, it should be checked peridical- emergency ballast and join the battery connector.
  • Page 4: Wiring Diagrams

    D450 EMERGENCY FLUORESCENT LIGHTING BALLAST WIRING DIAGRAMS C. ONE (1) LAMP INSTANT START SLIMLINE BALLAST TO UNSWITCHED AC USE PROPER TAP INSULATE USED LEADS BLUE ORANGE BLACK BLUE 277V LINE WHITE BLACK 1 LAMP BLUE/WHITE 120V EMERGENCY INSTANT START WHITE...
  • Page 5 D450 EMERGENCY FLUORESCENT LIGHTING BALLAST WIRING DIAGRAMS F. TWO (2) LAMP INSTANT START ELECTRONIC BALLAST TO UNSWITCHED AC USE PROPER TAP INSULATE USED LEADS ORANGE BLACK BLUE BLUE 277V LINE WHITE BLACK BLUE BLUE/WHITE 120V EMERGENCY YEL/GREEN WHITE BALLAST BALLAST...
  • Page 6 D450 EMERGENCY FLUORESCENT LIGHTING BALLAST WIRING DIAGRAMS I. THREE (3) LAMP RAPID START ELECTRONIC BALLAST TO UNSWITCHED AC USE PROPER TAP INSULATE USED LEADS BLUE BLUE ORANGE BLACK 277V BLUE BLUE/WHITE LINE WHITE BLACK BLUE/WHITE 120V BLUE/WHITE EMERGENCY YEL/GREEN WHITE...