Testing Of The Overcurrent Measuring Transformers; Testing Of The Overcurrent Stages - ABB REJ 525 Operator's Manual

Combined overcurrent and earth-fault relay
Table of Contents

Advertisement

1MRS 752137-MUM
5.3.1.
5.3.2.
Combined Overcurrent and Earth-Fault Relay
Operator's Manual
*
REJ525B 415BAA:
2 = 5 A
3 = 1 A
REJ525B 412BAA:
2 = 1 A
3 = 0.2 A
)LJ  6HFRQGDU\ LQMHFWLRQ WHVW FLUFXLWU\
When the test circuit has been completed and the switchgroups have been set, the
auxiliary voltage may be connected to the relay. The operation of the test circuit can
be verified using a multimeter.

Testing of the overcurrent measuring transformers

Test each used current transformer input separately. Apply a pure sinusoidal voltage
to the relay and compare the current value indicated on the display of the relay with
that shown by the ammeter. The measurements can be made at the rated current of
the relay, for instance. Note that the relay shows the measured current as a multiple
of the rated current, I
, of the energizing input used.
n

Testing of the overcurrent stages

The test is carried out as a single-phase test.
Before the test is started:
• Record the currently used SGR settings for later restoring.
∆I
• Check that stage
is inhibited.
• Set the relay switchgroups as follows:
Table 5.3.2-1
Switchgroup settings
Setting
SGR
I> to SO1
SGR1=4
t> to PO1
SGR2=1
I>> to SO2
SGR3=8
t>> to PO2
SGR4=2
∆I>
SGR9=0
t∆>
SGR10=0
The setting values can be those currently in use.
D
D
REJ 525
29