Receiver with pps2 interface
Hide thumbs Also See for DESIGO RXZ90.1:

Advertisement

Ordering
Compatibility
System expansion
Design
2/11
Siemens Building Technologies
Building Automation
When ordering, please specify the quantity, product name and type code.
Example:
20
Receivers with PPS2 interface
The RXZ90.1 receiver, in conjunction with wireless sensors, is suitable for use with all
room controllers with a PPS2 room unit interface (e.g. the DESIGO RX controllers).
Up to a maximum of 5 room units may be allocated to one receiver (see
Commissioning and establishing communication). If several room units are used, the
receiver determines the average of the temperature values received. The average
room temperature is then transmitted to the room controller.
In the case of room units with setpoint adjusters (QAX91.1), only one may be
assigned to each receiver. Other room units with setpoint adjusters are treated as
QAX90.1 units (room temperature only).
QAX91.1
QAX90.1
QAX90.1
The receiver is designed for mounting on walls or ceilings, or for installation in a flush
mounting box. The cables can be connected from the rear, top or bottom after
breaking out the perforated cable entry guide.
Basically the unit comprises the housing and the mounting plate. These can be
snapped together and apart.
The housing accommodates a printed circuit board and a tool socket (RJ45).
The housing and mounting plate are plastic.
RXZ90.1 – Receiver with PPS2 interface
Type RXZ90.1
RXZ90.1
868 MHz
QAX90.1
QAX90.1
00481
CA2N1644en
07.2001