Page 3
3 hexagonal screws. If the assembly parts must be turned over than 90°, or if the position is already amended since the delivery by Georgin, it's necessary to remove the electronic unit from the housing and disconnect the flatcable from the electronic measuring cell before turn the housing.
The specifications of the transmitter will be changed without prior notice for further product im- provement. Modification of the transmitter without permission is strictly prohibited. Georgin will not bear any responsibility for a trouble caused by such a modification. This instruction manual should be kept by a person who is actually using the transmitter.
EN 61000-4-6 Surge 2 kV Ligne à la masse du boîtier IEC61000-4-6 EN 61000-4-6 Conducted RF disturbances 3 V (150 kHz à 80 MHz) IEC61000-4-6 Performance criteria (A et B) : According EN 61326-1, EN 61326-2-3 subclauses 6.4. fu-processx-en www.georgin.com...
Risk of death or sever injury if the safety instructions are not followed. ATTENTION In case of wrong handling probable injury or physical damage can happen. PRECAUTION Important instructions to be respected. General observations concerning the product, product handling and cor- INDICATION rect use of the transmitter. fu-processx-en www.georgin.com...
Site at location large enough to allow maintenance and checking. Mounting position Mount to a pipe horizontally or vertically. Attention to overload Do not apply a pressure outside the specified range. Others Besides the above, be sure to observe the cautions given in this manual. fu-processx-en www.georgin.com...
4 to 20 mA DC Sensor Unit Electronics Unit (option) EEPROM Transmitters ® Parameters EEPROM Sensor parameters Micro Processor 4-20 mA signal Analog to Digital to Analog Digital Converter Converter Control system Zero/Span (option) 25.0 8.00 kPa fu-processx-en www.georgin.com...
Used to select the function (zero/span) to be adjusted by the external adjusting lector switch screw. Terminals Symbol Description Connects the output cable. Used for checking the output or connecting an analogic indicator or a remote indicator An external terminal used for grounding. fu-processx-en www.georgin.com...
Page 11
Digital indicator LIN display output LIN output Fixed current mode Measurement mode The transmitter is in operation The transmitter is not in operation. (blinking). Absolute pressure Gauge pressure Output value < Zero (a part of unit indicator) fu-processx-en www.georgin.com...
Page 12
Main function Mode key Switches between the normal and setting modes. Minus key Changes an item No. or item name to the minus (decrease) direction. Plus key Changes an item No. or item name to the plus (increase) direction. fu-processx-en www.georgin.com...
Refer to "technical data sheets" about details of process temperature limits of the transmitters. Protect the transmitter with a security device when the existing application INDICATION conditions require it. The transmitter should be installed remote from the measuring point in the case that the process temperature is too high. fu-processx-en www.georgin.com...
- Membrane are very sensitive. Be careful during the manipulation. - Do not bend excessiviely the capillary Mount the bracket on the transmitter as shown below. Transmitter Transmitter Process flange Bracket Bracket Plain washer Plain washer Spring washer Spring washer Mounting bolt Mounting bolt (M8x12) fu-processx-en www.georgin.com...
Page 15
(1) Fasten the transmitter to a vertical or horizontal pipe using the supplied U-bolt (Tightening (2) Use a pipe of outside diameter ø60.3 mm Transmitter Position the remote seal of the transmitter in front Spring washer boltings Plain washer Bolt fu-processx-en www.georgin.com...
Page 16
If the transmission unit has been turned excessively without removing the elec- which connects the electronics unit in the transmission unit and the detecting unit, and set the transmission unit again. Avoid the following procedure in an explosionproof area. DANGER plug. fu-processx-en www.georgin.com...
Page 17
Ensure a space of about 500 mm against the cover in order to facilitate he maintenance. Unscrew slowly grasp the hexagon part of vent/drain plug with an allen key. Put a new seal tape (4 to 8 rounds) and mount the vent/drain plugs in the position you want applying the tightening torque : fu-processx-en www.georgin.com...
Tightening torque of 7/16-20UNF mounting bolt should be 30 to 40 Nm (3 to 4 kgf m). (2) If a manifold is not used, the impulse pipes can directly be screwed into the transmitter. be 30 to 40 Nm (3 to 4 kgf m). fu-processx-en www.georgin.com...
Page 19
Installation of a drain is necessary Place the transmitter above the process pipe. If the pro- Manifold cess temperature is high, please use a condensate cham- ber like for steam Impulse pipe Isolating valve Process pipe Orifice plate fu-processx-en www.georgin.com...
Page 20
The reference column (connected to the high- ρ Condensate chamber Max. liquid level Level calculation formula Min. liquid level ρ ρ Manifold LRV : Low limit of measurement (0% point) High pressure pressure side side : Density : Liquid level, Liquid level change fu-processx-en www.georgin.com...
Page 21
Do not exceed the temperature limits (measuring cell: 120°C maxi and transmitter: 85°C). Even when the installations shut down the heat must be maintained, if not the transmitter and impulse pipes must be drained to prevent freezing. fu-processx-en www.georgin.com...
Page 22
Pressure tap Place the transmitter below the process pipe. Make piping so that gas in the impulse pipe is not delivered to Process pipe the transmitter and incorporate gas reservoir as required. Isolating Impulse pipe valve Vent valve fu-processx-en www.georgin.com...
Page 23
Do not exceed the temperature limits (measuring cell: 120°C maxi and transmitter: 85°C). Even when the installations shut down the heat must be maintained, if not the transmitter and impulse pipes must be drained to prevent freezing. fu-processx-en www.georgin.com...
Page 24
Process pipe Pressure tap Place the transmitter below the the process pipe. Isolating valve Make piping so that gas in the impulse pipe is Impulse pipe not delivered to the transmitter, and incorporate gas reservoirs as required. Vent valve fu-processx-en www.georgin.com...
Page 25
Do not exceed the temperature limits (measuring cell: 120°C maxi and transmitter: 85°C). Even when the installations shut down the heat must be maintained, if not the transmitter and impulse pipes must be drained to prevent freezing. fu-processx-en www.georgin.com...
Page 26
Be careful to a potential leak who can effect the measure. Standard dimension of the diaphragme seal are : Flange size Ø diaphragm seal (mm) DN80 / 3" Stainless steel : 73 special material : 89 DN100 / 3" Stainless steel : 96 special material : 89 fu-processx-en www.georgin.com...
Page 27
Max. liquid level Level calculation formula : LRV: Min. liquid level URV: + h) LRV : Low limit of measurement (0%) : Measuring liquid density h : Liquid level change (2) Level measurement on close tank fu-processx-en www.georgin.com...
Page 28
Do not exceed the temperature limits (measuring cell: 120°C maxi and transmitter: 85°C). Even when the installations shut down the heat must be maintained, if not the transmitter and impulse pipes must be drained to prevent freezing. fu-processx-en www.georgin.com...
Page 29
Ø diaphragm seal (mm) DN80 / 3" SS : 73 Special material : 89 DN100 / 4" SS : 96 Special material : 89 cycles using the tightening torque corresponding to the screw used and according to the fu-processx-en www.georgin.com...
Page 30
Min. liquid level LRV : Low limit of measurement (0%) ρ Low pressure High pressure side side The transmitter body should be installed below the remote seal unit. This PRECAUTION is mandatory where process pressure may become vacuum. fu-processx-en www.georgin.com...
Page 31
Instruction manual - ProcessX The oil density of the diaphragm seal can be found on the data sheet of the transmitter. Otherwise, for better accuracy, please contact Georgin France Silicone 0,934 générales 1,07 et vaccum service, high temperature and absolute vaccum service...
Page 32
Ø diaphragm seal (mm) DN80 / 3" SS : 73 Special material : 89 DN100 / 4" ISS : 96 Special material : 89 cycles using the tightening torque corresponding to the screw used and according to the fu-processx-en www.georgin.com...
Page 33
It is recommanded to install the transmitter below the remote seal(s). it PRECAUTION becomes necessary if process pressure is less than atmospheric pressure. In order to prevent vibration of the transmitter body and capillary from in- terfering with output, the transmitter body should be installed at a vibration fu-processx-en www.georgin.com...
“+” and “–” terminals may result damage to the transmit- ter. (2) Use a shielded cable for the transmission line where possible. (3) Avoid installing signal and power cable in thev same conduit or cable tray in order to avoid electromagnetic interferences.. fu-processx-en www.georgin.com...
20mA DC + − nect the “+” and “– Converter CK– of the transmitter as shown below. 10.5 to 45 V DC Output DC 4 to 20mA INDICATION Take care to respect the polarity when connecting the terminals fu-processx-en www.georgin.com...
Page 36
Make sure the load resistance of the wiring connected to the loop is within the range shown below. 1533 Note) Operating zone 10.5 16.1 Power voltage (VDC) is required fu-processx-en www.georgin.com...
By any of the methods given below, ground the transmitter in compliance with the relevant stipulation in the standard on explosion proof installation (for example, grounding resist- Grounding of transmitter casing Grounding from ground terminal Terminal unit External grounding terminal for grounding. fu-processx-en www.georgin.com...
(approximately 5sec per turn) Refer to to chap.6.3 "Adjustment with hand held Rough adjustment : turning quickly communicator" (approximately 1sec per turn) After adjustment, the transmitter must be kept energized for at least 10 INDICATION seconds data recording completion into memory. fu-processx-en www.georgin.com...
Open close isolating valve on the Make sure the equalizing valve is open and Equalizing make the zero adjustement (0%) valve Open Close the equalizing valve. Close Open the isolating valve on the LP side slowly Open fu-processx-en www.georgin.com...
Page 40
Close the stop valve on the high pressure Close Open the equalizing valve.. Open Close Close the stop valve on the low pressure side (LP side) slowly PRECAUTION the transmitter.This is to protect the transmitter from freeze, corrosion, etc... fu-processx-en www.georgin.com...
LCD Rough adjustment : turning quickly (approximately 1sec per turn) lamp “ZERO” is ON. After adjustment, the transmitter must be kept energized for at least 10 INDICATION seconds data recording completion into memory. fu-processx-en www.georgin.com...
Page 42
(approximately 1sec per turn) (4) Then return to applying input pressure of zero again and make sure output is 4 mA. After adjustment, the transmitter should be kept energized at about 10 INDICATION seconds to write the adjustment results into memory. fu-processx-en www.georgin.com...
Do not adjust the transmitter with the external screw if you adjust it with the 3 push but- ton of LCD display. In the setting mode, you can input commands during the item name selection screen. fu-processx-en www.georgin.com...
*6: This item is valid only if polygonal line correction is invalid. If the polygonal line correction is valid or the equipment is defective, the item name is not displayed. *8: In the multidrop mode, this item is invalid and the item name is not displayed. fu-processx-en www.georgin.com...
L-2. Display of span calibration data for users L-3. HisCLEAR L-3. Clearing of zero/span calibration data L-4. Display of min/max of amplifier temperature history information L-4. HisAMP L-5. HisCELL L-5. Display of min/max of cell temperature history information fu-processx-en www.georgin.com...
TAG No. setting. Press the key to cancel the setting. * Description of the displays on the first line on the item name selection screen ( : Differential pressure transmitter : Pressure (gauge pressure) transmitter : Absolute pressure transmitter fu-processx-en www.georgin.com...
Page 47
Press the key to cancel the setting. * Description of the displays on the first line on the item name selection screen ( : Differential pressure transmitter : Pressure (gauge pressure) transmitter : Absolute pressure transmitter fu-processx-en www.georgin.com...
Page 48
③ To display the seventh and following characters, scroll the characters to the left by pressing key. (The cursor position (far right) is displayed as a number.) ), press the key on the screen ④ ⑤ fu-processx-en www.georgin.com...
Page 49
< Torr > < atm > ① ② only. Indicates the maximum measuring range of this trans- mitter. ), press the on the screen Note) If “setERROR” is displayed as a URL value, the unit is not supported. fu-processx-en www.georgin.com...
Page 50
To move the decimal point position to left key: To move the decimal point position to right screen Press the key to save the zero point range setting. Press the key to cancel the setting. fu-processx-en www.georgin.com...
Page 51
After changing the range in this menu, it is neces- sary to change the range in the LCD indicator (menu G). Using an analog indicator and the transmitter range is changed, replacement of the analog indicator is required. fu-processx-en www.georgin.com...
Page 52
2) Damping setting appropriate damping time constant. The following table shows the effect of damping on the vibration of Damping set value [sec] Damping of output oscillation Remarks 1/3 or lower 1/5 or lower 19.2 1/10 or lower fu-processx-en www.georgin.com...
Page 53
( ⑦ the numerical values with the keys on the screen Settable range: 0.00 to 20.0% screen Press the key to save the cut point setting. Press the key to cancel the setting. fu-processx-en www.georgin.com...
Page 54
( ). with the key and press the key. the screen Press the key to save the low cut point setting. Press the key to cancel the setting. fu-processx-en www.georgin.com...
Page 55
(Cancel the setting) on the screen Press the key to save the burnout current setting M for OVERSCALE. (Save the setting) ⑦ Press the key to cancel the setting. See the next page for the procedure when UNdER is selected. fu-processx-en www.georgin.com...
Page 56
DER) =< 3.6 mA ⑩ on the screen . Press the key to save the burnout current setting for UNDERSCALE. Press the key to cancel the setting. Note) ⑪ You can change the saturation current value (lower of saturation current.” fu-processx-en www.georgin.com...
Page 57
Press the key to cancel the setting and return to the screen tended. Press the key to perform a zero calibration again. Press the key to move to the next screen for item name selection. fu-processx-en www.georgin.com...
Page 58
SPAN Press the key to cancel the setting and return to the screen ⑨ tended. Press the key to perform a span calibration again. Press the key to move to the next screen for item name selection. ⑩ fu-processx-en www.georgin.com...
Page 59
FIX. Select the setting mode again. Select “FIX cur” on the display in the items of “6-3. FIX cur” and press the key to terminate the constant current output. fu-processx-en www.georgin.com...
Page 60
T. ALm Transmitter temperature is normal- CEL TMP T. ALm Cell temperature error ized. Input pressure: J-2, saturation cur- OVER Correction of input pressure Input pressure: J-1, saturation cur- UNDER Correction of input pressure rent (Lo) or lower fu-processx-en www.georgin.com...
Page 61
List of adjustment functions locked/unlocked A-1. ZERO A. Zero/span calibration A-2. SPAN b-1. 4mA Adj B Output circuit calibration b-2. 20mA Adj I-1. LRV Adj I. Input/Output range ad- justment I-2. URV Adj fu-processx-en www.georgin.com...
Page 62
To move the decimal point position to left ④ key: To move the decimal point position to right saved on the screen Press the key to save the indicated value setting. Press the key to cancel the setting. fu-processx-en www.georgin.com...
Page 63
⑪ Display range DP=0 See note below DP=1 -9999.9 ~ 9999.9 DP=2 -999.99 ~ 999.99 DP=3 -99.999 ~ 99.999 DP=4 -9.9999 ~ 9.9999 Press the key to save the DP setting. Press the key to cancel the setting. fu-processx-en www.georgin.com...
Page 64
[in increments of 0.1%] Alternate display (Display set at G1 to G4 and % ⑰ display [in increments of 0.01%] screen . Press the key to save the option setting. Press the key to cancel the setting. fu-processx-en www.georgin.com...
Page 65
Press the key to cancel the setting and return to the screen as intended on the screen Press the key to perform a zero adjustment again. Press the key to move to the next screen for item name selection. fu-processx-en www.georgin.com...
Page 66
The following are the setting conditions for the adjust- ment point: per limit) Note 1: Output adjustment value (%) corresponding to the input pressure for the LRV adjustment Note 2: Output adjustment value (%) corresponding to the input pressure for the URV adjustment fu-processx-en www.georgin.com...
Page 67
Press the key to save the upper limit setting. Press the key to cancel the setting. * You can change the burnout current setting at “9: Di- ⑧ rection and value of burnout.” fu-processx-en www.georgin.com...
Page 68
(upper limit) to 21.6 mA The values in the table above can be set in increments of 0.1 mA. the screen . Press the key to save the NoRMAL/EXP setting. Press the key to cancel the setting and return to the screen fu-processx-en www.georgin.com...
Page 69
Press the key to cancel the setting and return to the screen Note: push buttons and the item name of “K. GUARD” does not appear. function of set value (GUARD) with the 3 push but- fu-processx-en www.georgin.com...
Page 70
Press the key to return to the screen with- out clearing the data. Note that if you clear the zero/span PRECAUTION calibration data, the adjusted zero/ span calibration value is deleted and reset to the factory default. fu-processx-en www.georgin.com...
Page 71
( ). with the keys. Select “Cmin” to display the min value of the cell temperature history. Select “Cmax” to display the max value of the cell ④ temperature history. key on the screen to return to “TAG No.” fu-processx-en www.georgin.com...
DC power supply 16.1 to 45V DC Load resistor 250 or more Note) See 7.2 “Power voltage and load resistance. Georgin HHC Georgin HHC Non-explosion-proof area Explosion-proof area Remarks : + and " of the transmitter. terminals + or of the transmitter or on the wires of the loop).
To delete caracters, please use the clear key < tion a second time by replying on the question " second time on the enter < ENT At this moment the new programmed information are written in the transmitter memory, "WRITE fu-processx-en www.georgin.com...
Page 74
Programmable linearization H : LINEARIZE function DATA Rerange I : RERANGE (Set LRV/URV calibration) DATA Saturation current value J : SATURATE CUR and specification setting DATA Write protect K : WRITE PROTCT DATA History information L : HISTORY fu-processx-en www.georgin.com...
Page 75
CHNG OK?< ENT/CL > display after setting Using < 2-2: TYPE WRITE moved. FKCXXXXX-XXXXX key and a prompt is displayed check entry under To Menu 3 : SERIAL No. and Software version display the initial image is displayed. Otherwise press display fu-processx-en www.georgin.com...
Page 76
Important When NOT SUITABLE is displayed upon changing the unit of industrial value, output cannot be dis- played in the engineering unit selected. In this case, press the key and change the engineering unit to a different one. fu-processx-en www.georgin.com...
Page 77
After changing the range in this menu, it is necessary to change the range in the LCD Important indicator (menu G). Using an analog indicator and the transmitter range is changed, replacement of the analog indicator is required. fu-processx-en www.georgin.com...
Page 78
Selectable time constant value : 7-2: DAMP WRITE 1.2SEC Note 1) In the case of ProcessX series transmit- ters with safety function, when there are To menu 8 : OUTPUT MODE no damping, then 0.12 sec is appeared Note 2) The above damping constants are used only for the electronics unit.
Page 79
8-7: MODE CHANGE LINEAR ZERO CHNG OK? < ENT/CL > CHNG OK? < ENT/CL > cut mode 8-8: MODE WRITE 8-8: MODE WRITE LINEAR ZERO , linear or zero output is se- lectable for output below the cut point. fu-processx-en www.georgin.com...
Page 80
Lower limit) is changeable according to the Menu "J : Saturation current value" The ower limit value ofsaturation valuer is set- mA to 4.0 mA) Display symbol of Menu 9 is : "9 : BURNOUT fu-processx-en www.georgin.com...
Page 81
Span adjustment : Within ±20% of calibrated span 3.When the adjustment point does not meet the following condition, –1.000%CS (Lower adjustment point) - LRV PL = × 100 URV - LRV URV - LRV (*) : CS (Calibrated Span) is equal to measuring range. fu-processx-en www.georgin.com...
Page 82
It will rectify in the D/A converter. display to cancel with the initial display of menu B. OUTPUT ADJ Important <INC> <CHANGE> is turned OFF when the constant current output has been set, the transmitter output is retained at the constant current output. fu-processx-en www.georgin.com...
Page 83
(–40 to 85°C). FL-1 (*1) OVER XMTR FAULT Input pressure is 105% or higher of setting range. Properly controlled. ZERO Under (*1) Input pressure is –1.25% or lower of setting range. Properly controlled. ZERO (*1) Real indication fu-processx-en www.georgin.com...
Page 84
INHIBIT < ENT > < CL > all adjustment function of the transmitter by LCD (ENABLE). F-2: XMTR EXT. SW CHANGE INHIBIT CHNG OK? < ENT/CL > F-3: XMTR EXT. SW WRITE INHIBIT F : XMTR DISPLAY fu-processx-en www.georgin.com...
Page 85
G-4: DISP. CHANGE 0.00-100.00% Note : in case of pressure transmitter, absolute X.XX-XXX.XX%LIN X.XX-XXX.XX%FLOW or 0.0-100.0% or 0-100% pressure transmitter and level transmitter, CHNG OK?<ENT/CL> CHNG OK?<ENT/CL> G-4: DISP. WRITE G-4: DISP. WRITE X.XX-XXX.XX%LIN X.XX-XXX.XX%FLOW value on the digital indicator. fu-processx-en www.georgin.com...
Page 86
Indication of the transmitter digi- B ( ) (UNIT=PRESS. LEVEL) (UNIT=FLOW) inHg tal indicator may have ±1 digit (Torr) bbl/s CAUTION (atm) bbl/min bbl/h ( ) is available bbl/d for GP and AP. (C) is available for DP. fu-processx-en www.georgin.com...
Page 87
Fig. B: With zero output selected in low cut mode selected in low cut mode G-D : MODE CHANGE G-B : MODE CHANGE LINEAR ZERO CHNG OK?<ENT/CL> CHNG OK?<ENT/CL> to cancel. G-D : MODE WRITE G-B : MODE WRITE LINEAR ZERO fu-processx-en www.georgin.com...
Page 88
2 to 14. Set each linearization option point (LP*) cor- rectly, and write them. Change of compensated point for LP Set each compensation value (CV*) cor- rectly, and write them. LP14 Set linearization option into EFFECTIVE and write. fu-processx-en www.georgin.com...
Page 89
OUT =SQR XMTR DISP = FLOW (Note 1) or the following is displayed. Note 1) XMTR DISP = FLOW means the settings of % Set OUTPUT MODE FLOW in % display or of FLOW units in actual scale LIN-LIN or display. fu-processx-en www.georgin.com...
Page 90
If RERANGE URV is implemented : lowing is displayed. Only URV (spam) of measurment range changes. Zero POint (LRV) remains the same. 1-1: RERANGE Set Linearize In this case, press the CL key and set in INVALID on fu-processx-en www.georgin.com...
Page 91
< 3 >SPEC XXXXXX < INC> < ENT> < CL> Refer to "J-3" in "J. Saturation current value and speci- SPEC Menu No.K details. NORMAL J-1: SATURATE CUR SELECT SPEC XXXXXX EXP. CHNG OK?< ENT/CL> XXXXXX part: NORMAL=Standard spec. EXP.=Extended spec. fu-processx-en www.georgin.com...
Page 92
_ <ENT> <CL> <ENT> <CL> After keying PASSWORD (new) K-4: WRITE PROTCT NEW PASSWORD XXXXXXXX If error of CHNG OK?<ENT/CL> PASSWORD If PASSWORD is correct K-5: WRITE WRITE K: WRITE PROTCT NEW PASSWORD WRITE PROTECT XXXXXXXX XXX WRITE ERROR<CL> <INC> <CHANGE> fu-processx-en www.georgin.com...
Page 93
ZERO means ZERO calibration value (4 mA). <2>TEMPERATURE SPAN -XXX.XX%CS <INC><1><2> <1.RESET><CL> SPAN means SPAN calibration value (20 mA). L-2: HISTORY ZERO -XXX.XX%URL SPAN -XXX.XX%CS RSET OK?<ENT/CL> L-1: HISTORY L-2: HISTORY temperature <1>AMP. TEMP <2>CELL TEMP for MIN/MAX cell tempera- <1><2><CL> <CL> ture L-2: HISTORY <CL> fu-processx-en www.georgin.com...
Check that no foreign matters are stuck on the cover treads and grease them before remounting Using soapy water or the like, check the all process connections for leakage of process If necessary, drain the moisture which has accumulated in the transmitter and process pipe.housing covers are not damaged fu-processx-en www.georgin.com...
Minimize the temperature change. error. widely. Readjust according to chapter 6. (4, 20mA) has deviated. When the indicator is (1) An error display is appeared. Refer to “Contents of message” abnormal. If remedy is impossible, contact Georgin service department. fu-processx-en www.georgin.com...
Assemble all parts in the reversing way than de- scribed before. Check all the screws are correctly tightened, and screw the electronics housing cover on the transmitter Zero adjustment PRECAUTION Groove PRECAUTION (6) After completion of replacement, perform zero and span adjustments. fu-processx-en www.georgin.com...
Page 97
(4) Check if the O-ring of the cell neck and all the surfaces in contact between the electronics housing and the cell neck not damaged. Assemble measuring cell and electronics housing. Tighten the 2 screws (7) After assembly, perform zero and span adjustment PRECAUTION fu-processx-en www.georgin.com...
Page 98
15 minutes, and make sure that there is no leakage. To avoid any damage of the measuring cell, do not exceed the test pressure Caution of the different cells (please refer to the technical datasheets of the concerned Remember ! transmitter) fu-processx-en www.georgin.com...
Page 99
15 minutes, and make sure there is no leakage. To avoid any damage of the measuring cell, do not exceed the test pressure Caution of the different cells (please refer to the technical datasheets of the concerned Remember ! transmitter) fu-processx-en www.georgin.com...
Page 100
15 minutes, and make sure there is no leakage. To avoid any damage of the measuring cell, do not exceed the test pressure of Caution different cells (please refer to the technical data sheets of the concern transmitter) Remember ! fu-processx-en www.georgin.com...
Page 101
(3) Pull out the connector extending from the analog indicator. (4) Connect the connector of a new analog indicator to the electronics section. (5) Mount the analog indicator by reversing the dissembling procedure. (6) Assemble the electronics housing cover. fu-processx-en www.georgin.com...
Page 102
(4) Connect a new digital indicator following the reverse order of disassembly procedure. Digital indicator plugin port Pin plug Before tightening, make sure a small recess on the surface is positioned at the top as shown below. (6) Assemble the electronics housing cover. fu-processx-en www.georgin.com...
Page 103
K : WRITE PROTCT (P92) Check data as necessary tion (2) After replacement of detecting unit (including replacement of internal parts) Zero/span A-1 : ZERO Implement span calibration after zero (P68) A : CALIBRATE (P81) calibration A-2 : SPAN calibration. fu-processx-en www.georgin.com...
Page 104
Grounding terminal must be used, in case of the explosion proof or intrinsic safety type trans- mitter. INDICATION Avoid common grounding with a lightning rod. In case of a transmitter with arrester, maximum power supply is 32 V DC. fu-processx-en www.georgin.com...
Page 105
* Disconnect the wire from the – (minus) terminal and connect the measurement device a shown below. To (–) terminal Digital voltmeter To (+) terminal To (+) side wiring DC power supply To (–) side wiring Standard resistance (1 or 10 ) fu-processx-en www.georgin.com...
Note 2) In both the differential pressure transmitter (Type: FKC) and remote seal type (Type: FKD), the output current mode is set in linear unless it is designated. Note 3) “Hold” is selected for “Burnout” unless otherwise specified by the order. fu-processx-en www.georgin.com...
ProcessX ® communicator. ® ® communicator, the func- ® communicator, it can be used in Generic mode ® communicator. Note2) ® communi- cator. In this mode, functions which can be sued are limited to general-use functions fu-processx-en www.georgin.com...
Page 110
Be sure to connect individually. INDICATION power for the communicator after changing from one to another, then restart the communication. At this time, old data may be left in the communicator. DANGER the junction box located outside the hazardous area. fu-processx-en www.georgin.com...
Page 111
Instruction manual - ProcessX 3. Function and operation (example) ® fu-processx-en www.georgin.com...
Page 112
7 O ring matl 2 Lower Disp. 8 Drain vent Value matl 3 Digit DP 9 Num remote 4 LCD Unit seal 5 LCD Opt. 5 Self test 10 RS type 11 RS isoltr matl 12 RS fill fluid fu-processx-en www.georgin.com...
Page 113
Instruction manual - ProcessX SPARE PARTS For more details about these parts, please contact Georgin France. fu-processx-en www.georgin.com...