Electrex ZEPTO D6 Installation Instructions

Energy analyzer

Advertisement

Quick Links

ZEPTO D6
INSTALLATION INSTRUCTIONS
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written authorization,
except when regulated accordingly by the Copyright Laws.

WARRANTY

This product is covered by a warranty against material and manufacturing defects for a
period of 24 months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence of a
negligent and improper use or an operating procedure not contemplated in this manual.

RETURN AND REPAIR FORMALITIES

Akse accepts the return of instruments for repair only when authorized in advance. The
transport costs are at customer charge.

RE-SHIPPING OF REPAIRED PRODUCT

The terms for re-shipment of repaired products are ex-works, i.e. the transport costs are
at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, will
be charged a fl at fee to account for checking and testing time irrespective of the warranty
terms.

SAFETY

This instrument was manufactured and tested in compliance with CEI EN 61010-1 CAT
III-300V, class 2, standards for operating voltages up to 300 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply with
the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it is
intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the mains
voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
!
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by qualifi ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrument
must be taken out of service and precautions taken againstits accidental use.
• Operation is no longer safe when:
1) There is clearly visible damage.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.

OPERATOR SAFETY

Warning: Failure to observe the following instructions may lead to a serious danger of
death.
• During normal operation dangerous voltages can occur on instrument terminals and
on voltage and current transformers. Energized voltage and current transformers
may generate lethal voltages. Follow carefully the standard safety precautions while
carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the installation.
The user should only be allowed to access the instrument front panel where the
display is located.
• Do not use the digital outputs for protection functions nor for power limitation functions.
The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by the
operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to the
instrument.
• The instrument is equipped with PTC current limiting device but a suitable external
protection fuse should be foreseen by the contractor.
• The outputs and the options operate at low voltage level; they cannot be powered by
any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damage
to the instrument.
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.

DECLARATION OF CONFORMITY

Akse hereby declares that its range of products complies with the following directives EMC
89/336/EEC
73/23CE
93/68 CE and complies with the following product's standard
CEI EN 61326 – IEC 61326
CEI EN 61010 – IEC 1010.
The product has been tested in the typical wiring confi guration and with peripherals
conforming to the EMC directive and the LV directive.

INFORMATION

Hold for 2 seconds the button "meas"
to display:
- Device name and fi rmware version
- Serial number
- Rs485 adress

READINGS DISPLAYED

(The parameters available vary according to instrument confi guration)
U
f
L-N
f
L-L
THD L-N
THD L-L
READINGS DISPLAYED
(The parameters available vary according to instrument confi guration)
Ea ∑
Er L ∑
Ea ∑ E2
Er L ∑ E2
TIME ∑
TIME E2

LEGEND OF PARAMETERS AND SYMBOLS

L-N
Phase Neutral
L-L
Phase Phase
THD
Total Harmonic Distortion
Avg
Average (rolling) value
MD
Maximum Demand
L
Inductive
C
Capacitive
TIME ∑
Life Time (total) (hour/100)
TIME E2 Life Time (partial) (hour/100)

MECHANICAL CHARACTERISTICS

Enclosure
Self-extinguishing plastic material class V0
Protection degree
IP40 on front panel, IP20 terminals side
Dimensions
105 x 90 x 58 mm (6 DIN modules)

VOLTAGE INPUT

Direct
Up to 300 Vrms phase-neutral or 519 Vrms phase to phase
With external PT(VT)
Primary: programmable (max. 400 kV)
Secondary: programmable (max. 300 V)
Overload: 900 Vrms phase to phase for 1 sec
Power supply
18-60 VDC
Self consumption
1.5 W +/- 10% (measures with Power Supply 60 VDC)

MODELS

PFA8611-08
ZEPTO D6 RS485 18-60VDC
ENERGY ANALYZER
PFA8611-18
ZEPTO D6 RS485 18-60VDC 1DI 2DO
ENERGY ANALYZER
I
P
Q
S
I
P
Q
S
In
P Avg
Q L Avg
S Avg
THD
P MD
Q C Avg
S MD
I Avg
Q L MD
I MD
Q C MD
Press to change readings
Er C ∑
Es ∑
Er C ∑ E2
Es ∑ E2
U
Voltage
I
Current
In
Neutral current
P
Active Power
Q
Reactive Power
S
Apparent Power
PF
Power Factor
Ea
Active Energy
Er
Reactive Energy
Es
Apparent Energy
f
Frequency
PF
PF

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZEPTO D6 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Electrex ZEPTO D6

  • Page 1: Declaration Of Conformity

    INSTALLATION INSTRUCTIONS COPYRIGHT Hold for 2 seconds the button “meas” Electrex is a trademark of Akse S.r.l. All rights reserved. to display: It is forbidden to duplicate, adapt, transcript this document without Akse written authorization, - Device name and fi rmware version except when regulated accordingly by the Copyright Laws.
  • Page 2 Note n° 1 CONFIGURATION SETUP Description Display visualization OPERATING KEYS 3W Delta (3 wire) 3PH-3W-2CT 4W Star (4 wire) 3PH-4W Click Change selected fi eld Change selected fi eld value Go to next fi eld value Click Go to next window Back to initial entry fi...
  • Page 4 VOLTAGE AND CURRENT CONNECTION Voltage connection Use cables with max cross-section of 2,5 mm if fl exible 4 mm if rigid and connect them to the terminals marked voltage input on the instrument according to the applicable diagrams that follow. Current connection It is necessary to use external CTs with a primary rating adequate to the load to be metered and with a 5A or 1A secondary rating.