Technical description

11 Technical description

11.1 Control panel

The control panel explained below is the only dryer user interface.
1
ON-OFF Switch
2
Electronic instrument
3
Air and refrigerant flow diagram

11.2 Functional description

Operating principle – The dryer models described in this manual all operate on the same principal. First the very hot
moisture laden air directly from the compressor enters the aftercooler (copper tube / aluminum fin cooling surface) where
it is cooled to within 18-20°F (10-12°C) of the ambient air temperature. It leaves the aftercooler with entrained condensed
water droplets which are separated by the 1 micron bulk liquid filter separator element and drained away by the first drain
system. The partially cooled moisture laden air next enters an air to air heat exchanger to pre-cool it. The compressed
air next goes through the evaporator, also known as the air to refrigerant heat exchanger. The compressed air
temperature is reduced to approximately 41°F (5°C), causing additional water vapor to condense to liquid. The liquid is
continuously coalesced and collected in the dryer separator for automatic removal by the second condensate drain. The
cool moisture free compressed air then passes back through the air to air heat exchanger to be reheated to within the
ambient temperature as it exits the dryer.
Refrigeration cycle – Refrigerant gas is cycled through the compressor and exits at high pressure to a condenser where
heat is removed causing the refrigerant to condense to a high-pressure liquid state. The liquid is forced through a capillary
tube where the resulting pressure drop allows the refrigerant to boil off at a predetermined temperature. Low-pressure
liquid refrigerant enters the heat exchanger where heat from the incoming air is transferred causing the refrigerant to boil;
the resulting phase change produces a low pressure, low temperature gas. The low-pressure gas is returned to the
compressor, where it is re-compressed and begins the cycle again. During those periods when the compressed air load
is reduced the excess refrigerant is by-passed automatically back to the compressor via the Hot Gas By-pass Valve circuit.