General
Compact Data Gathering Panel (often abbreviated as CDGP)
Model WY7208W is a terminal transmission device for
status/alarm
monitoring,
measurement/metering of equipment installed in commercial
and other buildings.
One CDGP manages a small number of inputs/outputs (two
to eight points), and its compact body fits inside the building
distribution panel/power control panel.
suitable for a small- and mid-sized building where the points
to monitor are decentralized.
Features
●
Economical:
Price per point is substantially reduced compared to the
price per point of our former remote stations.
●
Compact:
No additional remote panel is required to install CDGP at
remote locations. You can use available space in the
distribution panel or power panel.
Model Numbers
Model number
WY7208W1120
DIO model (Select from the following point configurations using the DIP switch.)
- Start/stop point (maintained contact output) x 2
- Starts/stop, status point (maintained contact output) x 2
- Start/stop, status point (momentary contact output, without unmatched alarm monitoring) x 2
- Start/stop, status point (momentary contact output, with unmatched alarm monitoring) x 2
- Start/stop, status, alarm point (maintained contact output) x 2
- Start/stop, status, alarm point (momentary contact output, without unmatched alarm monitoring) x 2
- Start/stop, status, alarm point (momentary contact output, with unmatched alarm monitoring) x 2
WY7208W2180
DI model (Select from the following functions using the DIP switch.)
- Status, alarm point x 4
- Status point x 8
- Alarm point x 8
- Status point x 4 + alarm point x 4
WY7208W3180
TOT model (totalizer pulse input x 8)
WY7208W4140
AI model (1–5 V DC input or 4–20 mA DC input x 4)
WY7208W5140
RRD model (remote control relay drive output x 4)
WY7208W6140
Pt model (Pt100 input x 4)
Measuring range: -20 °C to 80 °C * This model is connectable to SmartScreen™ / Infilex™ ZM.
Compact Data Gathering Panel
ON/OFF
operation,
and
CDGP is thus
●
Simple wiring:
LAN cable is used for the communication line SC-bus.
Its modular connection facilitates wiring and also
minimizes misconnection.
●
Easy setting:
Besides addressing with the rotary switch and functional
setting with the DIP switch, no other setting is required
for setup.
Description
1
AB-5702
Specifications/Instructions
Need help?
Do you have a question about the WY7208W Series and is the answer not in the manual?
Questions and answers