Lithonia Lighting LVS Series Installation Instruction Supplement

Emergency exit signs, fi option-fire alarm flashing interface, 120/277 eln fi

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS SUPPLEMENT
FI OPTION-FIRE ALARM FLASHING INTERFACE
LVS/LVS2 120/277 ELN FI EMERGENCY EXIT SIGNS
NOTE:
This exit fixture is provided with a FIRE ALARM
(FLASHER) interface to be cycled on and off by an external fire
alarm control panel and is intended for installations where
permitted by local codes.
FLASH RATE: 66 CPM
DUTY CYCLE: 50/50
INSTALLATION
1
. Follow installation instructions provided with exit fixture, but
for all wiring connections refer to wiring diagrams Fig. A,
Fig. B, Fig. C, or Fig. D.
2. From F.I. Board connect fire alarm input wiring as follows:
Blue lead: Common
Red/white lead: 24V D.C.
FIGURE A 120V SINGLE LAMP FI OPTION
FIGURE C 120V DUAL LAMP FI OPTION
IMPORTANT SAFEGUARDS
1.READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
2. Do not use for other than intended use.
3. Before wiring to power supply, turn off electricity at fuse or circuit
breaker.
4. All servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS
INSPECTION
1. Normal Operation: When unit is functioning properly,
with A.C. power supplied, the green ready light and lamps
will be continuously illuminated.
2. Fire Alarm Operation: When fire alarm system
(24VDC) Is engaged the lamps will flash approximately
once per second.
FIGURE B 277V SINGLE LAMP FI OPTION
FIGURE D 277V DUAL LAMP FI OPTION

Advertisement

loading

Summary of Contents for Lithonia Lighting LVS Series

  • Page 1 INSTALLATION INSTRUCTIONS SUPPLEMENT FI OPTION-FIRE ALARM FLASHING INTERFACE LVS/LVS2 120/277 ELN FI EMERGENCY EXIT SIGNS IMPORTANT SAFEGUARDS NOTE: This exit fixture is provided with a FIRE ALARM (FLASHER) interface to be cycled on and off by an external fire 1.READ AND FOLLOW ALL alarm control panel and is intended for installations where SAFETY INSTRUCTIONS permitted by local codes.
  • Page 2 INSTALLATION INSTRUCTIONS SUPPLEMENT F OPTION (DC FLASHER) LVS/LVS2 120/277 ELN F EMERGENCY EXIT SIGNS INSTALLATION INSPECTION 1. Refer to IMPORTANT SAFEGUARDS (opposite side) 1. NOTE: Emergency lighting systems should be tested as often as local codes require, or at least monthly to acertain before proceeding.