Thank you, and congratulations on your purchase of an American Panel Intelligent Control. We take great pride in engineering and manufacturing each of our products. With the goal of providing the highest accuracy and quality possible, our state-of-the-art manufacturing and quality control facility enables us to continually explore new technologies so that we can provide you with the finest equipment in the industry.
INDEX Introduction and Features ..........................2 Temperature Monitoring ........................... 2 Temperature Alarms ..........................2 Electronically Controlled Light Switch and Automatic Light Off ............3 User Interface ............................. 4 Parameter Programming ..........................
1.1 Temperature Monitoring IC monitors the walk-in cabinet temperature via a probe mounted in the warmest part of the cabinet which is near the door. The alarm delay will ensure that the alarm does not go off during normal door openings.
LED light to display the ON/OFF status of the light. The Automatic Light Off feature of IC enables the user to save energy. The amount of time the light will stay on can be set from 1 minute to 60 minutes or can be set for manual shut off only. As default, the automatic light off feature is disabled.
3 Parameter Programming On powering up, IC will run through a procedure to adjust its settings based on the type of room it is installed within, user input is not required. The procedure may take up to 12 hours of continuous operation, during this time the controller will not display any temperature alarm.
Page 8
PROGRAMMING Door Frame Heater and Window Heater Settings The display will alternate between and the value This setting will enable or disable the door frame and window heaters. 1 – heaters enabled 0 – heaters disabled Note: If you set the flashing value to “0”, the heaters will be disabled and the controller will skip the heater settings.
4 Air Temperature Probe Offset As standard, the air temperature probe is located on the door frame, inside the walk-in. The IC will display the air temperature at that location ONLY. However, IC can be adjusted to estimate the temperature of a remote location inside the walk-in.
PROGRAMMING 5 Load Standard Settings Press and hold UP and DOWN buttons, simultaneously, for ten seconds. The display will alternate between and the value Use UP button to set this value to “1” then press ENTER to confirm. The display will show: Enter the access code 055, use UP or DOWN button to change the blinking character then press ENTER to confirm.
TROUBLESHOOTING 6 Troubleshooting Issue Possible Cause Action IC controller display is flashing on IC controller detected cabinet Make sure all the doors are closed and off a number. temperature higher or lower than and check the temperature after few the preset limits. The flashing...
If an electrical stub-out construction was requested, all the connection wires will be stubbed-out thru the ceiling. In this case, the field connections will be made in a junction box provided by the installer. 7.1 Remote Light Button Connection Note: Check the blue print to find out which IC controller connects to the remote button.