ProtoNode RER and ProtoNode LER
Startup Guide
For Interfacing Product: Thermal Solutions Boiler Controller 
To Building Automation Protocols: 
 BACnet MSTP, BACnet IP and LonWorks 
 
 
APPLICABILITY & EFFECTIVITY
Explains the ProtoNode RER and LER hardware and how to install it.
The instructions are effective for the above as of April 2012
Document Revision: 2

Advertisement

Table of Contents
loading

Summary of Contents for Thermal Solutions ProtoNode LER

  • Page 1 ProtoNode RER and ProtoNode LER Startup Guide For Interfacing Product: Thermal Solutions Boiler Controller  To Building Automation Protocols:   BACnet MSTP, BACnet IP and LonWorks      APPLICABILITY & EFFECTIVITY Explains the ProtoNode RER and LER hardware and how to install it. The instructions are effective for the above as of April 2012 Document Revision: 2...
  • Page 2 Thermal Solutions ProtoNode Start Up guide Page 2 of 32 THIS PAGE INTENTIONALLY LEFT BLANK ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 3: Table Of Contents

    Connecting TSBC Boiler Controllers to the ProtoNode’s RS485 ............11     Wiring the ProtoNode RER to RS-485 Field Protocol ................12     Wiring the ProtoNode LER Field Port to a LonWorks network ..............13     Power-Up the ProtoNode RER or LER ....................... 13    ...
  • Page 4 Thermal Solutions ProtoNode Start Up guide Page 4 of 32 LIST OF FIGURES   Figure 1: A0 – A7 DIP Switches ........................... 7   Figure 2: B0 – B3 DIP Switches ............................ 8   Figure 3: S0 – S3 DIP Switches ............................ 8  ...
  • Page 5: Introduction

    ProtoNode is an external, high performance Building Automation multi-protocol gateway. The ProtoNode can support multiple Thermal Solutions’ TSBC boiler control systems. It has been preprogrammed to Auto-Discover any of the TSBC boilers connected to the ProtoNode and automatically configures them for BACnet®...
  • Page 6: Bacnet/Lonworks Setup Through Protocessor Protonode Rer/Ler

    Thermal Solutions ProtoNode Start Up guide Page 6 of 32 BACNET/LONWORKS SETUP THROUGH PROTOCESSOR PROTONODE RER/LER Installation steps for the customer 1. Record the information about the unit. (See Section 2.2) 2. Set the BAUD rate to 19200 on the TSBC boiler controllers.
  • Page 7: Configure The A, B, And S Bank Of Dip Switches

    All the boilers need to be set for odd parity, 8 date bits, and 1 stop bit.  All of the Thermal Solutions TSBC Boilers connected to the ProtoNode need to have their own unique Modbus Node address. They need to be set between 1 and 255.
  • Page 8: Setting The Serial Baud Rate (Dip Switch B0 - B3) For Bacnet Ms/Tp

    (BACnet MS/TP, BACnet/IP, Modbus TCP and/or Metasys N2). See the chart below for the DIP switch settings.  The S0 – S2 bank of DIP switches on the ProtoNode LER are disabled.  The S3 DIP switch is used to enable Auto-Discovery of known devices attached to the ProtoNode RER and LER (LonWorks), as well as save the recently discovered configuration.
  • Page 9: Configuration File

    Thermal Solutions ProtoNode Start Up guide Page 9 of 32 2.3.6 Auto-Discover Thermal Solutions Boiler Controllers, Build Automatically Loads Configuration File The following chart describes S3 DIP Switch setting for the Enabling Auto-Discovering of known devices attached to the ProtoNode RER or LER.
  • Page 10: Interfacing The Protonode To Thermal Solutions Tsbc Boiler Controller

    Thermal Solutions ProtoNode Start Up guide Page 10 of 32 INTERFACING THE PROTONODE TO THERMAL SOLUTIONS TSBC BOILER CONTROLLER ProtoNode RER and LER showing connection ports RS-485 Port for LonWorks Port Serial Field Protocol LonWorks Service Pin 10/100 BaseT (1) Modbus RTU to TSBC...
  • Page 11: Connecting Tsbc Boiler Controllers To The Protonode's Rs485

    Thermal Solutions ProtoNode Start Up guide Page 11 of 32 3.2.1 Connecting TSBC Boiler Controllers to the ProtoNode’s RS485  Connect TSBC’s RJ‐11 Pin 1 A (+) Black (RS485+) to ProtoNode’s pin 1 (RS485+) on the Phoenix 6 pin  connector.   Connect TSBC’s RJ‐11 Pin 2 B (‐) Red (RS485‐) to ProtoNode’s pin 2 (RS485‐) on the Phoenix 6 pin  connector.   Ground between TSBC and the ProtoNode does not need to be connected.  ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 12: Wiring The Protonode Rer To Rs-485 Field Protocol

    Thermal Solutions ProtoNode Start Up guide Page 12 of 32 Wiring the ProtoNode RER to RS-485 Field Protocol  Connection from ProtoNode RER to BACnet MS/TP and Metasys N2 networks  See Section 4 for information on connecting the ProtoNode RER to a BACnet/IP network.
  • Page 13: Wiring The Protonode Ler Field Port To A Lonworks Network

    Thermal Solutions ProtoNode Start Up guide Page 13 of 32 Wiring the ProtoNode LER Field Port to a LonWorks network  Connect the ProtoNode to the field network with the LonWorks terminal using a twisted pair non- shielded cable. LonWorks has no polarity.
  • Page 14: Commissioning The Protonode Ler On A Lonworks Network

    To commission the ProtoNode LER LonWorks port, insert a small screwdriver in the commissioning hole on the face of the LER’s enclosure to access the Service Pin. See the illustration on the ProtoNode LER as to which way to toggle the screw driver during commissioning.
  • Page 15: Connect The Protonode's Web Gui To Setup Ip Address For Bacnet/Ip

    Thermal Solutions ProtoNode Start Up guide Page 15 of 32 CONNECT THE PROTONODE’S WEB GUI TO SETUP IP ADDRESS FOR BACNET/IP Connect the PC to the ProtoNode via the Ethernet port Ethernet Port Figure 6: Ethernet port location of ProtoNode ...
  • Page 16: Use The Protonode Web Gui To Connect To The Protonode

    Thermal Solutions ProtoNode Start Up guide Page 16 of 32 Use the ProtoNode Web GUI to Connect to the ProtoNode  Open PC web browser enter the default IP address of the ProtoNode 192.168.1.24 determine if the ProtoNode is up and communicating.
  • Page 17 Thermal Solutions ProtoNode Start Up guide Page 17 of 32 ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 18: Appendix A. Troubleshooting Tips If The Unit Is Not Working

    Thermal Solutions ProtoNode Start Up guide Page 18 of 32 Appendix A. Troubleshooting Tips if the Unit is Not Working Appendix A.1. Take Log With Our FieldServer Utilities  Once the log is complete, email it to support@protocessor.com. The log will allow us to rapidly diagnose ...
  • Page 19 Thermal Solutions ProtoNode Start Up guide Page 19 of 32  For Windows XP and Windows 7, select: Use the following IP address  Click twice  Double click on the FST Diag Utility.  Step 1: Select a Field Server IP Address.
  • Page 20 Thermal Solutions ProtoNode Startup Guide Page 20 of 32  Push the ‘Locate Folder’ button to launch explorer and have it point directly at the correct folder. The file upload.zip must be sent to support@fieldserver.com.  Step 4: Close the Program ...
  • Page 21: Appendix A.2. Led Diagnostics For Modbus Rtu Communications Between The Protonode And The Tsbc

    The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on the ProtoNode LER. If this occurs, immediately report the related “system error”...
  • Page 22: Appendix B. Vendor Information

    Thermal Solutions ProtoNode Startup Guide Page 22 of 32 Vendor Information Appendix B. Appendix B.1. Thermal Solutions TSBC Modbus RTU COM Settings Serial Port Setting TSBC Boiler 1 Baud Rate 19200 Data Bits None Stop Bits Parity Modbus Node ID Appendix B.2.
  • Page 23 Thermal Solutions ProtoNode Startup Guide Page 23 of 32 Address ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 24 Thermal Solutions ProtoNode Startup Guide Page 24 of 32 Address ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 25 Thermal Solutions ProtoNode Startup Guide Page 25 of 32 Address ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 26 Thermal Solutions ProtoNode Startup Guide Page 26 of 32 Address ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: support@protocessor.com...
  • Page 27: Appendix B.3. Tsbc Modbus Rtu Mappings To Bacnet Mstp And Bacnet Ip

    Thermal Solutions ProtoNode Startup Guide Page 27 of 32 Address Appendix B.3. TSBC Modbus RTU Mappings to BACnet MSTP and BACnet IP. BACnet Object BACnet Object Point Name Type Outdoor Air Reset Enable/Disable Domestic Hot Water Priority Local/Remote Remote On/Off Modbus Command...
  • Page 28 Thermal Solutions ProtoNode Startup Guide Page 28 of 32 Operating or High Limit Low Combustion Air Flow Fuel Valve Energized Flame Safeguard Alarm Call For Heat (CFH) General Alarm Vent Inducer Boiler Pump System Pump Spare Output (Programmable) State Boiler Disabled...
  • Page 29: Appendix B.4. Tsbc Modbus Rtu Mappings To Lonworks

    Thermal Solutions ProtoNode Startup Guide Page 29 of 32 Appendix B.4. TSBC Modbus RTU Mappings to LonWorks. Point Name Lon Name Lon SNVT Type Outdoor Air Reset Enable/Disable nvoOAResEn_Disbl SNVT_switch Domestic Hot Water Priority nvoDomHotWtrPri SNVT_switch Local/Remote nvoLoc_Rem SNVT_switch Remote On/Off Modbus...
  • Page 30 Thermal Solutions ProtoNode Startup Guide Page 30 of 32 Annunciator Memory Failure nvoAnnMemFailure SNVT_switch Boiler Outlet Water Temp nvoBlrOtltWtrTmp SNVT_temp_p Boiler Inlet Water Temp nvoBlrInltWtrTmp SNVT_temp_p Outside Air Temp nvoOutsideAirTmp SNVT_temp_p Boiler Actual SP nvoBlrActualSP SNVT_temp_p Remote System Temp nvoRemSystemTmp...
  • Page 31: Appendix C. Reference

    Thermal Solutions ProtoNode Startup Guide Page 31 of 32 Reference Appendix C. Appendix C.1. Specifications ProtoNode RER ProtoNode LER One 6-pin Phoenix connector, one RS-485 One 6-pin Phoenix connector, one RS-485 +/- ground port, power +/- frame ground port +/- ground port, power +/- frame ground port...
  • Page 32: Appendix D. Limited 2 Year Warranty

    Thermal Solutions ProtoNode Startup Guide Page 32 of 32 Limited 2 year Warranty Appendix D. FieldServer Technologies warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. FieldServer Technologies will repair or replace any equipment found to be defective during the warranty period.