NPM User Manual Ⅰ. NPM Introduction NPM can monitor, control and manage the power supply of many equipments in cabinets in data room all over the world through LAN or WAN. For meeting with the restrictions and requirements in different environment, NPM supplies many connection methods;...
Ⅲ. Applied Range 1. NPM 3100 can be applied to server cabinet, network cabinet etc. 2. The socket quantity (8 or 12) and socket standard (C13, C19, NEMA5-15R, NEMA5-20R) of NPM 3100 can be selected. 3. NPM 3100 conforms to RoHS instruction, suitable for 110VAC and 220VAC power supply, can meet the customers’...
NPM User Manual 15. Water: connect water sensor 16. Smoke: connect smoke sensor 17. T/H1, T/H2, T/H3: connect temperature/humidity sensor 18. Port2:RS485 spare port 20. Overload protection 21. Cable input Ⅴ. Mounting Method Horizontal installation. Ⅵ . Hardware Introduction 1. Power on & Self-check The buzzer makes a sound when NPM is connected with AC power source, LED screen lightening and sequentially display (it means digitron is normal, any different display means fault), software...
NPM User Manual Max., the NPM screen displays as (that means the load current of outlet No.1 is higher than the Max. value) A.1.. 6. Self-checking Parameter Monitoring Make the OUTLET N0.1 display - - - - - -, then press reset button, the NPM LED screen sequentially display the NPM self-checking parameter for one minute.
10.3 One end of the network wire connects to the LINK port of the master NPM, the other end connects to the RJ45 port of the HUB (special HUB for NPM link from CLEVER) 10.4 Use the end of another network wire connects to another in/out port of the HUB, the other end connects to the SER port of the slave.
NPM User Manual 11.4 The RJ45 end of the signal wire for upgrade software (special wire, it must from CLEVER) inserts to PORT1 on NPM, DB9 end inserts to the RS232 port of PC 11.5 Please select the correct series port in , make other selection according the picture 11.6 Click...
Page 9
NPM User Manual input the incorrect user name or password for three times consecutively. The administration interfa ce is made up of three parts: the system information interface、user guide menu and the device control interface. The system information interface: mainly contain the company Logo as well as the device current IP address; User guide menu: display the us er name and function menu, it helps and guides the user complete the operation conveniently and promptly;...
Page 10
NPM User Manual c) "Smoke alarm" displays the connection of smoke sensor, "Not found" means no smoke alarm is connected. The word "CLOSE" o r "OPEN" can be read on the screen if connected. The word "YES" in red will flash if smoke alarm happens.
Page 11
NPM User Manual below: a) Individual outlet current rate: 0~10(A), total current rate: 0~16(A) or 0~32(A), connecting to the load, the device will alarm when the current exceed the set limiting value of current. b) Temperature rate setting: -40~215(℃), Hu midity rate: 0~100(100%), the sensor will alarm when the temperature/humidity exceed the limiting value.
Page 12
NPM User Manual limitation, problem occurrence and the status information of sensor connection an d disconnection; b) "Select Device" to select and view the single device daily record information; c) Select "First", "Previous" "Next" to view the daily record; d) Select "WEB" or "EXCEL" to leading-out the daily record information; e) "clear all records"...
Page 13
NPM User Manual seconds. d) Set trap destination, input the SNMP management platform object address in the frame of Trap Destinati on, the Trap information will be sent to the corresponding address automatically, user ca n set 2 Trap Destinations. e) The system name of SNMP records the information of SNMP system name.
Page 14
NPM User Manual 16) Logout According to the prompt me ssage to close the software system interface` 2.2. SNMP Access Method SNMP(Simple Network Management Protocol), this software support the V2 version of SNMP with a MIB file which contain an enterprise number, network management system offer network management of device through SNMP, the user can chang e the output port name, view the device and sensor status, receive alarm information through SNMP approach.
Page 15
NPM User Manual Temperature Display the current connection status and temperature of temperature sens or 1 Humidity 1 Display the current connection status and humidity of humidity sensor 1 Temperature 2 Display the current connection status and temperature of temperature sens or 2 Humidity 2 Display the current connection status and humidity of humidity sensor 2...
Page 16
NPM User Manual "STATUS" command line can be used to view the basic information of devices, sta tus of total output, individual output and sensor; the format of command line: STATU【ADDRESS】 【OPTION】 ESS】 :the series number of connected device, view the current status of device according to the series 【ADDR number;...
Page 17
NPM User Manual 【ADDR ESS】: the series number of connect device, control the status of switch on/off according to this series number 【OPTION】: select the output No. to be controlled according to the options, as detail ed in figure 3-3: Figure 3-3 the description table of switch off option...
Page 18
NPM User Manual DEVICE View all the connected devices and corresponding serial number View the system information e.g software versi on, update time, MAC SYSTEM code, CPU occupancy rate, operation time View the network configuration e.g IP address, sub-net mask, default NETWORK gateway, main DNS and back up DNS SNMP...
Page 19
NPM User Manual Command line input format: SET HT TP 【OPTION】 【OPTION】as detailed in fi gure 3-6-b Figure 3-6-b the description tabl e of HTTP OPTION 【 OPTION】 Description ENABLE Set the HTTP enable DISABLE S et the HTTP disable PORT Set the HTTP port For instance: SET HTTP ENABLE: enable HTTP fun...
Page 20
NPM User Manual E. SNMP Command line input format: SET SNMP 【OPTION】 【OPTION】detail as figure 3 -6-e Figure 3-6-e the description table of SNMP OP OPTION】 Description 【 ENABLE Set the SNMP enable DISABLE Set the SNMP disable GETC getting the character string of commun SETC Set the character string of community TRAPC...
Page 21
NPM User Manual PASSWORD The pa ssword of e-mail sending a ddress E-mail receiving address -mail carbon copy addres FROM E-mail sending address REPTIME Setting the interval of e-mail alarm sending For instance: SET MAIL POP3=POP3.163.COM: Set POP3 server address to be POP3.163.COM Note: "NULL"...
Page 22
NPM User Manual Set the lowest value of the total load current of phase B TOTALB Set the highest value of the total load current of phase B Set the lowest value of the total load current of phase C TOTALC Set the highest value of the total load current of phase C For instance: SET THRESHOLD ABCDEF TEM1 L=0 Set the lowest value of temperature sensor 1 of NPM...
Page 23
NPM User Manual Y:daily timing repeat , Y means repeat, N means non-repeat ON:the status of switch on/off, ON means power on, OFF means power off =0912301456:the time of power on/off, format: year-month-day-hours-minute, each section with 2 digit, 24-hour clock. Note: "NULL"...
NPM User Manual 9) RESET "RESET" command line can be used to restore factory seting, e.g device name, output port name, HTTP configuration, SSH configuratio n, TELNET configuration, SNMP configuration, voice alarm setting, e-mail alarm setting and user management. Note: it will be va lid after system reboot 10) RESTART "RESTART"...
A: Press the knob of "OUTLET NO.2 for 30 seconds to restore it to factory setting, when restore complete the IP will be: 192.168.1.163; User name is clever; password is clever, these user name and passw ord can be used only once, other user administration will no t be affected when restore to the original factory setting.
Page 26
NPM User Manual 4. Ensure all the information filled in frame is accurate.