foreign matter, rust or other obstructions that might interfere with the proper operation of the AG-1250E.
NOTICE: Cleaning solutions or dirty probes may not allow the HVAC unit to come on. If such, remove probe sensor and/or secondary pan sensor, clean, and dry.
WIRING THE AG-1250E:
(To ensure proper performance of product, instructions must be followed.)
1. Ensure the power is disconnected to the HVAC unit at the main electrical panel prior to moving to step 2. Refer to the appliance manufacturer's installation
and operating instructions and also review the wiring diagram in their instructions.
For Breaking "Wall Thermostat" Power Wire (see Figure 1)
2. In HVAC Unit locate 24 VAC Power wire going to "Wall Thermostat", (Typically RED). Break/Disconnect 24 VAC Power wire going to "Wall Thermostat".
A. Connect "RED", "Input: 24 VAC (Hot)" wire of AG-1250E to 24 VAC (Hot) secondary side of 24 VAC Transformer.
B. Connect "PURPLE", "Normally Closed" wire of AG-1250E to Thermostat's "R" Terminal.
NOTE: "PURPLE" wire must be connected to "THERMOSTAT". Maximum capacity 24VAC/5Amp.
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON) secondary side of 24 VAC Transformer or Thermostat's
"C" Terminal.
Work Safe, READ THIS!
D. "WHITE", "Normally Open" wire of AG-1250E must be connected to AquaGuard, AG-9100 External Alarm (see Figure 1) or Home Alarm System,
Work Safe, READ THIS!
or Communicating System, etc..
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION
MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
CAUTION: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
STOP/READ: The AG-1250E must be installed in accordance with manufacturer's instructions. The AG-1250E must be installed in accordance with all applicable
Note: When AG-1250E is wired correctly, the HVAC unit will shut-off upon condensate detection.
STOP/READ: The AG-1250E must be installed in accordance with manufacturer's instructions. The AG-1250E must be installed in accordance with all applicable
local plumbing, drainage and electrical codes.
Optional Wiring: For Breaking Compressor Wire
local plumbing, drainage and electrical codes.
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER TO THE HVAC UNIT BEFORE INSTALLING THE AQUAGUARD AG-1250E to
3. In HVAC Unit locate "Compressor wire going to "Wall Thermostat", typically (YELLOW). Break/Disconnect Compressor wire going to "Wall Thermostat".
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER TO THE HVAC UNIT BEFORE INSTALLING THE AQUAGUARD AG-1250E to
avoid electrical shock and/or equipment damage. Do not use on circuits exceeding 24 VAC to avoid damage to sensor, shock or fire hazard.
A. Connect typically "YELLOW" wire, going to "Wall Thermostat" to "RED", "Input: 24 VAC (Hot)" wire of AG-1250E .
avoid electrical shock and/or equipment damage. Do not use on circuits exceeding 24 VAC to avoid damage to sensor, shock or fire hazard.
B. Connect "PURPLE", "Normally Closed" wire of AG-1250E to Compressor's typically "YELLOW" wire going to Compressor.
CAUTION: In some situations the sensor may cause the unit to rapidly cycle on and off as water level rises slowly in pan. After a brief period the HVAC unit will
CAUTION: In some situations the sensor may cause the unit to rapidly cycle on and off as water level rises slowly in pan. After a brief period the HVAC unit will
turn off completely. Condensation drain must be serviced if this occurs.
NOTE: "PURPLE" wire must be connected to COMPRESSOR "YELLOW" Wire. Maximum capacity 24VAC/5Amp.
turn off completely. Condensation drain must be serviced if this occurs.
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON) secondary side of 24 VAC Transformer or Thermostat's
CAUTION: In any installation where property damage and/or personal injury might result from an inoperative sensor due to power outages, a back-up system(s)
CAUTION: In any installation where property damage and/or personal injury might result from an inoperative sensor due to power outages, a back-up system(s)
"C" Terminal.
and /or alarm should be installed.
D. "WHITE", "Normally Open" wire of AG-1250E must be connected to AquaGuard, AG-9100 External Alarm (see Figure 1) or Home Alarm System,
and /or alarm should be installed.
NOTICE: The AG-1250E must only be installed by a licensed contractor. Condensation pan must be properly maintained after installation and be kept free of
or Communicating System, etc..
NOTICE: The AG-1250E must only be installed by a licensed contractor. Condensation pan must be properly maintained after installation and be kept free of
foreign matter, rust or other obstructions that might interfere with the proper operation of the AG-1250E.
CAUTION: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
foreign matter, rust or other obstructions that might interfere with the proper operation of the AG-1250E.
NOTICE: Cleaning solutions or dirty probes may not allow the HVAC unit to come on. If such, remove probe sensor and/or secondary pan sensor, clean, and dry.
NOTICE: Cleaning solutions or dirty probes may not allow the HVAC unit to come on. If such, remove probe sensor and/or secondary pan sensor, clean, and dry.
Note: When the AG-1250E is wired correctly, (ONLY) the Compressor will shut-off upon condensate detection. Air Handler will continue to run.
WIRING THE AG-1250E:
WIRING THE AG-1250E:
4. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC unit is on and functioning correctly. See installation of
(To ensure proper performance of product, instructions must be followed.)
the AG-1250E:
(To ensure proper performance of product, instructions must be followed.)
1. Ensure the power is disconnected to the HVAC unit at the main electrical panel prior to moving to step 2. Refer to the appliance manufacturer's installation
1. Ensure the power is disconnected to the HVAC unit at the main electrical panel prior to moving to step 2. Refer to the appliance manufacturer's installation
and operating instructions and also review the wiring diagram in their instructions.
and operating instructions and also review the wiring diagram in their instructions.
For Breaking "Wall Thermostat" Power Wire (see Figure 1)
For Breaking "Wall Thermostat" Power Wire (see Figure 1)
2. In HVAC Unit locate 24 VAC Power wire going to "Wall Thermostat", (Typically RED). Break/Disconnect 24 VAC Power wire going to "Wall Thermostat".
2. In HVAC Unit locate 24 VAC Power wire going to "Wall Thermostat", (Typically RED). Break/Disconnect 24 VAC Power wire going to "Wall Thermostat".
A. Connect "RED", "Input: 24 VAC (Hot)" wire of AG-1250E to 24 VAC (Hot) secondary side of 24 VAC Transformer.
A. Connect "RED", "Input: 24 VAC (Hot)" wire of AG-1250E to 24 VAC (Hot) secondary side of 24 VAC Transformer.
B. Connect "PURPLE", "Normally Closed" wire of AG-1250E to Thermostat's "R" Terminal.
B. Connect "PURPLE", "Normally Closed" wire of AG-1250E to Thermostat's "R" Terminal.
Mounting Clip
NOTE: "PURPLE" wire must be connected to "THERMOSTAT". Maximum capacity 24VAC/5Amp.
NOTE: "PURPLE" wire must be connected to "THERMOSTAT". Maximum capacity 24VAC/5Amp.
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON) secondary side of 24 VAC Transformer or Thermostat's
Standard HVAC Installation w/ optional external alarm or accessory
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON) secondary side of 24 VAC Transformer or Thermostat's
"C" Terminal.
"C" Terminal.
D. "WHITE", "Normally Open" wire of AG-1250E must be connected to AquaGuard, AG-9100 External Alarm (see Figure 1) or Home Alarm System,
D. "WHITE", "Normally Open" wire of AG-1250E must be connected to AquaGuard, AG-9100 External Alarm (see Figure 1) or Home Alarm System,
or Communicating System, etc..
or Communicating System, etc..
CAUTION: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
CAUTION: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
Note: When AG-1250E is wired correctly, the HVAC unit will shut-off upon condensate detection.
Note: When AG-1250E is wired correctly, the HVAC unit will shut-off upon condensate detection.
Optional Wiring: For Breaking Compressor Wire
Optional Wiring: For Breaking Compressor Wire
3. In HVAC Unit locate "Compressor wire going to "Wall Thermostat", typically (YELLOW). Break/Disconnect Compressor wire going to "Wall Thermostat".
3. In HVAC Unit locate "Compressor wire going to "Wall Thermostat", typically (YELLOW). Break/Disconnect Compressor wire going to "Wall Thermostat".
A. Connect typically "YELLOW" wire, going to "Wall Thermostat" to "RED", "Input: 24 VAC (Hot)" wire of AG-1250E .
A. Connect typically "YELLOW" wire, going to "Wall Thermostat" to "RED", "Input: 24 VAC (Hot)" wire of AG-1250E .
B. Connect "PURPLE", "Normally Closed" wire of AG-1250E to Compressor's typically "YELLOW" wire going to Compressor.
B. Connect "PURPLE", "Normally Closed" wire of AG-1250E to Compressor's typically "YELLOW" wire going to Compressor.
NOTE: "PURPLE" wire must be connected to COMPRESSOR "YELLOW" Wire. Maximum capacity 24VAC/5Amp.
NOTE: "PURPLE" wire must be connected to COMPRESSOR "YELLOW" Wire. Maximum capacity 24VAC/5Amp.
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON) secondary side of 24 VAC Transformer or Thermostat's
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON) secondary side of 24 VAC Transformer or Thermostat's
"C" Terminal.
"C" Terminal.
D. "WHITE", "Normally Open" wire of AG-1250E must be connected to AquaGuard, AG-9100 External Alarm (see Figure 1) or Home Alarm System,
D. "WHITE", "Normally Open" wire of AG-1250E must be connected to AquaGuard, AG-9100 External Alarm (see Figure 1) or Home Alarm System,
or Communicating System, etc..
or Communicating System, etc..
CAUTION: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
CAUTION: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
Note: When the AG-1250E is wired correctly, (ONLY) the Compressor will shut-off upon condensate detection. Air Handler will continue to run.
Note: When the AG-1250E is wired correctly, (ONLY) the Compressor will shut-off upon condensate detection. Air Handler will continue to run.
4. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC unit is on and functioning correctly. See installation of
4. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC unit is on and functioning correctly. See installation of
the AG-1250E:
the AG-1250E:
*Note:
Probe Wire Not Included
On Model AG-1250E
Figure 1
Mounting Clip
Mounting Clip
In HV AC Unit locate H
In HV AC Unit locate H
Standard HVAC Installation w/ optional external alarm or accessory
Standard HVAC Installation w/ optional external alarm or accessory
INSTALLATION OF SENSOR:
A. Connect "RED", "Input 24 VAC (Hot)" and "Gray" "Common" wire of AG-1250E to 24
(To ensure proper performance of product, instructions must be followed.)
1. Clean desired mounting surface thoroughly with included alcohol pad.
VAC (Hot) secondary side of 24 VAC Transformer.
2. Using the double sided tape, a x the mounting clip to the desired surface in pan. Next, snap AG-1250E to mounting clip.
4. Test sensor: Place sensor in secondary pan and add enough water to the pan to cover contacts (approximately ¼ inch). LED will illuminate and HVAC
unit will stop running if wired correctly
D. Optional: Connect "WHITE", "Normally Open" wire of AG-1250E to the "WHITE" wire of
LIMITED WARRANTIES AND LIMITATION OF
LIABILITY
AquaGuard, AG-9100 External Alarm or Home Alarm System, or Communicating System, etc...
REGISTER YOUR PRODUCT ONLINE: www.rectorseal.com
1 YEAR SWITCH AND SENSOR LIMITED WARRANTY AND LIMITATION OF LIABILITY
The limitations of liability set forth below include body and all component parts as well as the product itself as a whole.
Rectorseal warrants to the original consumer purchaser ("Purchaser) of its AquaGuard switch and sensor products, that they are free from
defects in material or workmanship for a period of one (1) year from the date of purchase. If this product shall prove to be defective within the
one (1) year period from the date of purchase, it shall be repaired or replaced, at Rectorseal 's option, subject to the GENERAL TERMS and
AG-1250E
CONDITIONS set forth below.
EXCLUSIONS
This warranty does not cover damages resulting from use of components or accessories not approved by Rectorseal. 3, and 10 YEAR SEC-
NOTE: When AG-1250E is wired correctly, the HVAC unit will shut-off upon condensate
ONDARY DRAIN PAN LIMITED WARRANTY AND LIMITATION OF LIABILITY
detection.
This warranty applies only to secondary drain pans installed in the United States and Canada.
Rectorseal warrants to the original consumer purchaser ("Purchaser") of its AquaGuard secondary drain pan products, that they are free from
defects in material or workmanship for a period of three (3) years for Titan pan models, ten (10) years for Goliath and Goliath Furnace
models, from the date of purchase. If this product shall prove to be defective within the three, five or ten (3, or 10) year period from the date of
purchase, it shall be repaired or replaced, at Rectorseal's option, subject to the GENERAL TERMS and CONDITIONS set forth below. This
warranty extends only to the original consumer purchaser and is nontransferable.
EXCLUSIONS

Installation Instructions:

Installation Instructions:
Metal contacts
Metal contacts
Metal contacts
HVAC
AG-1250E to
AG-1250E
AG-1250E
AG-1250E
AG-1250E
24 VAC,
5.0 Amps Carry
Moisture detection LED
AG-1250E
AG-1250E
24 VAC,
5.0 Amps Carry
24 VAC,
5.0 Amps Carry
Moisture detection LED
Moisture detection LED
AG-1250E to
wire
.

Advertisement

loading
Need help?

Need help?

Do you have a question about the AG-1250E and is the answer not in the manual?

Questions and answers

Summary of Contents for RectorSeal AG-1250E

  • Page 1: Installation Instructions

    WIRING THE AG-1250E: WIRING THE AG-1250E: 4. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC unit is on and functioning correctly. See installation of (To ensure proper performance of product, instructions must be followed.) the AG-1250E: (To ensure proper performance of product, instructions must be followed.)
  • Page 2 System, etc... NOTE: “WHITE”, “Normally Open” wire maximum capacity, 24VAC/1Amp. 2. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the HVAC unit is on and functioning correctly. See installation of the AG-1250E: NOTE: When the AG-1250E is wired correctly, (ONLY) the Compressor unit will shut-off upon condensate detection.
  • Page 3 PURCHASER MUST PAY ALL LABOR AND SHIPPING CHARGES NECESSARY TO REPLACE PRODUCT COVERED BY THIS WAR- RANTY. This warranty shall not apply to acts of God, nor shall it apply to products which, in the sole judgment of Rectorseal have been subject to negligence, abuse, accident, tampering, misapplication, alteration;...