Parameter Setting with HC8XINIT.EXE under MS-DOS........26 4.3.1 "HC8XINIT.EXE" DOS Option Window................ 26 4.3.2 Configuration Query of HC8X with HC8XINIT.EXE ..........27 Parameter Setting Example with HC8XINIT.EXE under MS-DOS ....28 Configuring the Control Channel as a Follower ............. 30 4.5.1 Example for "Channel Following"...
Page 5
HC8X Heat Control Retrofitting / Conductor Bar Configuration ............... 36 Retrofitting the HC8X......................36 7.1.1 Retrofitting the HC8X with an Even Number of Channels........36 7.1.2 Retrofitting the HC8X with an Odd Number of Channels........38 Configuring the Power Bars ...................39 Troubleshooting ........................41 Power Electronics Overload Protection ..............41...
Page 6
HC8X with the basic factory settings. All these activities are explained step by step. The configuration of the HC8X for the specific application usage is performed with the DOS 6.22-oriented HC8XINIT.EXE utility program or with the Windows-oriented SETHC8X.EXE utility program....
Page 7
Some information in this documentation is specially highlighted for faster access to this in- formation. Warning! A warning protects from bodily injuries or the HC8X heat control from serious damage. Always read and follow the warnings carefully. Electrical hazard! Warning of the danger of death by electrical shock when not complying with the relevant VDE and safety and control unit directives.
Technical Information HC8X Heat Control Intended Use The HC8X is an 8-channel heat control. It serves to regulate single and multi-phase heating circuits. The control unit is an extension of the modular MODIOS I/O system and can be installed in an existing I/O module box system.
This control unit may be connected to the mains only by authorized/qualified personnel. Only a SICK service engineer or similarly trained and authorized person should be per- mitted to service or repair the control unit. The control unit operates with high voltages. Even with the power switched OFF, high voltages can be present inside the control unit.
Note The HC8X can be retrofitted by the installation of the retrofit kits HC 4A, 8A, 16A with / with- out load relay (see Chapter 7.1 Retrofitting the HC8X, page 7-36).
Control unit damage caused by incorrect configuration! The control unit configuration may be changed only by SICK. The heat control is supplied configured. Changes to an existing configuration are normally not required. However, if a configuration needs changing, e.g. to create load symmetry, pro- ceed according to Chapter 7.2 Configuring the Power Bars, page 7-39.
Data / Temperatures, page 10-45) near the HC8X or in the MCS 100 E measuring system cabinet. HC8X Process Connection The process connection of the HC8X, e.g. to a MCS 100 E system, is shown in Fig. 3-1. MCS 100 E HOST Optical fiber Fig.
Do not install the control unit in a humid or dusty environment. Distance between HC8X and Measuring System PC The length of the optical fiber between the HC8X or an I/O module box and the measuring system PC may not exceed 60 m.
7. Pull all plugs from terminal strips X1 to X8. 8. Loosen the four attachment screws on the case base plate of the HC8X by a few turns and lift the HC8X from the attachment. 9. Change individual electrical or mechanical assemblies only after contacting SICK. A fur- ther disassembly of the HC8X heat control is not intended.
Provide all stranded individual wires with suitable connector sleeves before their con- nection to the respective terminal / terminal block. Fig. 3-1: Terminal-Side Overall View of the HC8X Socket for mains connection with fuse holder and system voltage switch-over 115 V/230 V, 50–60 Hz...
2. Connect connection MA (S) of HC8X with connection (E) of measuring system PC. When the HC8X is the last communications unit in the optical fiber group: 3. Close connection SL (E) of HC8X with a blank plug (see Fig. 3-2, HC8X 2). HC8X 1...
3.6.2 Connecting the Supply Voltage Destruction of control unit by overvoltage! The control electronics of the HC8X operate without additional mains switching immediately upon inserting the plug. Check the value of the preset supply voltage by visual inspection of the indicator win- dow in the fuse holder.
Overview for Parameter Settings Note The "HC8XINIT.EXE" and "SETHC8X.EXE" programs serve for the configuration and para- meter setting of the HC8X heat control. The software is not completely described and in- tended only for trained personnel. Steps for configuration and addressing: ...
The communication with HC8X in Prog mode runs always with 9600 Bd. Example: HC8XINIT /c3 /b1200 -t120.3 -a49 /n6305 /e123 uses the HC8X on COM3 at 9600 Bd, IRQ4, 8 data bits, 1 stop bit, no parity, sets HC8X address to 49 dec, control temperature to 120.3degC on channels 0,3,5 and 6, enables channels 1..3 only, sets 1200 Bd for normal...
Configuration Output of HC8XINIT.EXE Parameter Setting Example with HC8XINIT.EXE under MS-DOS In this example, the following parameters are to be transferred to the HC8X during the pro- gram execution of HC8XINIT.EXE: Enabling of channels 0, 1, 2, 3 and 5 (parameter: /E25013) ...
A disabled control channel is not shown in the address area of the HC8X and its control func- tion is disabled A control channel which is set as a follower is not shown in the address area of the HC8X, however, the power output is controlled by the previous control channel.
LED25 acknowledges with a single short blink. 4. Push the slide switch to position "A" again. After the successful transfer of the preset values to the EEPROM, the HC8X starts in the "Norm" operating mode with the parameters in table...
"B" for 1 s to 5 s min. When the slide switch is set to position "B" for less than 5 s, the HC8X re- mains in the "Norm" mode When the slide switch is in position "B" for more than 5 s, a switch-over to the "Idle"...
2. Unscrew two screws from the case cover. 3. Remove the case cover and pull off the ground conductor. 4. Set the HC8X to the "Norm" mode (see Chapter 5.1.1 Setting the HC8X Mode, page 5- 32). 5. If one or several control channels were set as followers, check the correct assignment of the temperature sensors (PT100) to the controlling channel ...
If the temperature T (see Fig. 5-1) is exceeded: ctrl ulim Acknowledge the error with the slide switch (see Chapter 5.1.1 Setting the HC8X Mode, page 5-32). – or – Perform a software reset via the measuring system PC.
Switching the HC8X on Again 1. Insert the plug in the mains socket of the HC8X and switch on the supply voltage of the control electronics. 1. Switch on the supply voltage of the power electronics (terminal strip X9).
HC8X in the basic configuration is equipped with an even number of channels: Select the retrofit kit with a load relay. When the HC8X in the basic configuration is equipped with an odd number of channels: Select the retrofit kit without a load relay.
19. Close and screw on the case cover. 20. Connect the supply voltage to all poles. 21. Put the HC8X in operation (see Chapter 5 Start-up, page 5-31). 7.1.2 Retrofitting the HC8X with an Odd Number of Channels ...
Retrofitting / Conductor Bar Configuration Chapter 7 HC8X Heat Control 4. Plug in all wires, as shown in the example (Chapter 7.1.1 Retrofitting the HC8X with an Even Number of Channels, page 7-36). 5. Check the correct assignment and firm seating of all connections.
Dispose of unusable or irreparable control units in an environmentally compatible manner and according to the specific waste disposal regulations of your country. The design of the HC8X allows for the separation into reusable secondary raw materials and special waste (electronics waste).
Page 46
Layout of LEDs and Slide Switches on the Printed Circuit Board ......17 Fig. 2-1: HC8X Attachment........................19 Fig. 3-1: Terminal-Side Overall View of the HC8X................21 Fig. 3-2: HC8X Optical Fiber Connection..................24 Fig. 4-1: HC8XINIT.EXE after the Call-Up without Additional Parameters ......27 Fig.
Page 50
HC8X SICK worldwide You will find our local subsidiary or agency at: www.sick.com Your local sales and service partner SICK AG | Waldkirch | Germany | www.sick.com...
Need help?
Do you have a question about the HC8X and is the answer not in the manual?
Questions and answers