LG MULTI V HYDRO KIT ARNH963K2A4 Installation Manual page 45

Medium temperature
Table of Contents

Advertisement

The water circuit guidelines and diagrams are for illustrative purposes and are to be used for references only; not all components and accessories
local, state, and federal codes.
Space Heating / Cooling
Figure 27: Space Heating / Cooling System Diagram.
Wi-Fi Module
LG Supplied
Field Supplied
Balancing
Valve with
Flow Meter
Automatic Air
Separator
Hydro Kit
Strainer
Water Pump
Drain
• Hydro Kit PCB DIP Switch Group 2 must be set correctly for space heating / cooling applications. (Refer to the Hydro Kit PCB DIP Switch
Settings pages in the Pre-Commissioning section.)
• For sensing air temperature at a specific area, choose a remote temperature sensor or a wired remote controller, depending on the Hydro
Kit PCB DIP Switch Group 3 setting. (Refer to the Hydro Kit PCB DIP Switch Settings pages in the Pre-Commissioning section.)
• When installing a floor heating system, to measure room temperature, use the Hydro Kit controller or a remote temperature sensor (sold
separately).
• See the Indirect Water Storage Tank Sensor Well and Sensor Installation information.
• To prevent condensation from forming in floor cooling applications, set minimum / maximum cooling temperatures.
• For two-way valve control, see the Wiring section.
Table 18: Two-Way Valve Control Application.
Mode
Cooling
Heating
INSTALLING THE WATER CIRCUIT
Relief Valve
Shut-Off
Meter
Valve
Water Tank
Temperature
Check
Valve
Service Port
Water Tank
Magnetic Dirt
Shut-Off
Separator
Valve
Service Port
Water Supply
Shut-Off
Valve
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Wired Remote
Remote
Temperature
Controller
Fan Coil
Unit
Floor Heating
Shut-Off
Shut-Off
Valve
Valve
Water Pump
Description
Fan Coil Unit - Not Use
Fan Coil Unit - Use
None
Application Options
(recommended) to ensure that nominal
the plate heat exchanger could freeze
and burst, or system capacity could be
reduced.
Two-Way Valve Operation
Open
Close
No Control
45