MIST TIME
Version MIS 1.4-LP
December 18, 2006
MICROFAN B.V.
Industriestraat 23 5961 PH Horst
P.O. Box 6022 5960 AA Horst
The Netherlands
Developing, manufacturing and marketing of MICROFAN
computers, measuring, control and monitoring equipment for
Tel.+31(0)77 3985648 Fax.+31(0)77 3986886
Agricultural purposes.
www.microfan.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DRAMM MIST TIME and is the answer not in the manual?

Questions and answers

Summary of Contents for Microfan DRAMM MIST TIME

  • Page 1 Version MIS 1.4-LP December 18, 2006 MICROFAN B.V. Industriestraat 23 5961 PH Horst P.O. Box 6022 5960 AA Horst The Netherlands Developing, manufacturing and marketing of MICROFAN computers, measuring, control and monitoring equipment for Tel.+31(0)77 3985648 Fax.+31(0)77 3986886 Agricultural purposes. www.microfan.com...
  • Page 3 Keep this manual at hand, so that you can use it as a reference book at all times. As our products are subject to continuous development and updating, MICROFAN B.V. is entitled to revise or modify its products without prior notice.
  • Page 4: Table Of Contents

    Alarm signalling ................................7 Installation rules ................................7 Wiring diagrams Prints ..............................8 Wiring data Prints ............................... 10 Wiring diagram pump with external contact switch ..................... 11 Specifications ................................12 MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 5: Description Mist Time

    When the controller establishes an alarm, the display will show a flashing code (e.g.: ‘-2-'). The alarm relay will be released activating an external alarm device. Pressing the SET key will cancel this alarm. If the alarm situation is still there after 1 minute, the controller will again release an alarm. MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 6: Measurements /Setting Procedure

    When the temperature is still rising, the cycle time will be shortened from maximum cycle time to minimum cycle time. This means the valve is switched on more often when the temperature becomes higher. MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 7: Installation Instructions

    The maximum pulse frequency will be reached as soon as the actual temperature reaches 30°C (set-temperature + P-band). The valve then is switched on for 30 seconds every 2 minutes. See table below. MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 8 Note I: This function has no meaning when you don't have selected the water pump control. The remaining functions have no meaning. The installer's program is concluded by switching the mains off and on again. After that the user's program will be started MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst...
  • Page 9: Alarm Signalling

    P-band temperature control. Now the installation is complete and the power supply can be switched off and on again to terminate the installer's program and to start up the user's program. MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst...
  • Page 10: Wiring Diagrams Prints

    MIST TIME Version MIS 1.4-LP Dec. 18, 2006 Manual Page 8 Wiring diagrams Prints MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 11 MIST TIME Version MIS 1.4-LP Dec. 18, 2006 Manual Page 9 MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 12: Wiring Data Prints

    Relay misting valve 8 or water pump (depending on setting) Potential free. Power supply 230Vac/115Vac 50/60Hz. L2/N = L2/Neutral L = Phase Fuse: T500mA. Attention! Check the powersupply switch on the main bottom board. MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 13: Wiring Diagram Pump With External Contact Switch

    MIST TIME Version MIS 1.4-LP Dec. 18, 2006 Manual Page 11 Wiring diagram pump with external contact switch MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...
  • Page 14: Specifications

    : +/- 0,5°C Resolution temperature measurement : 0,2°C Resolution temperature reading : 0,2°C Temperature range temperature sensor : 0 - 50°C Encasing : Plastic IP54 (*) = selectable MICROFAN B.V. Industriestraat 23 Tel.+31(0)77 398 5648 5961 PH Horst Fax.+31(0)77 398 6886...