SyxthSense RY-FL Manual

Wireless input output module

Advertisement

Quick Links

RY-FL Wireless Input / Output
Module
RYFL is a wireless locally powered 230 Vac transmitter using
868.30 MHz frequency and FSK modulation. It is for providing
building automation measurements and controls wirelessly.
RYFL can control two inputs and outputs. Individual input is
possible to set 0-10 V or potential free. For instance 0-10 V
transmitter can be used with 24 Vac auxiliary supply.
Individual output can be selected between 0-10 V (and PWM) or
230 Vac relay. There is a two-way communication between
transmitters and the base station. RYFL transmits the signals to
the FLTA every 6 s.
Each wireless transmitter, repeater and base station needs to
have a unique address. Each transmitter address consists of two
parts; SID (sensor ID) and MID (master / base station ID). These
addresses will be configured wireless by using FLSER service
tool.
The transmission area can be extended by using FLREP
repeaters between transmitters and the FLTA base station.
Model Type
Technical Data
Online store: www.syxthsense.com
Enquiries: T: 0870 20 80 100 F: 0870 20 80 200
Model
RY-FL
RY-FL-24
Power Supply
Frequency
Modulation
Range
Transmission Power
Reception Sensitivity
Addressing
Inputs (2 configurable)
Outputs (2 configurable)
Input / Output Accuracy
Ambient Temperature
Ambient Humidity
Enclosure
Dimensions
Description
Wireless Input / Output Module, 230Vac Power Supply
Wireless Input / Output Module, 24Vac Power Supply
230Vac 12VA
868.30 Mhz
FSK
Line of sight: Up to 500m
In buildings up to 20..100m depending on wall strcutures
Range can be extended up to 2 times with FLREP repeaters
+8 dBm
-109 dBm
Via FLSER Service Tool
Analogue, 0..10Vdc
Digital, Potential Free
Relay, 250Vac, 10A
Analogue, 0..10Vdc
Auxiliary Supply, 24Vac
Triac (PWM), 24Vac, 1A, seq., 20 s.
+/- 0.5 %
-40 .. + 50 degC
0..100% rH Non-Condensing
IP20 ABS Plastics
W150 x H210 x D110mm
NOTE: RY-FL requires FLTA version 2.2 or later and FLSER
service tool version 2.2 or later.
Product sheet SN1.125
RY-FL
Sensor type
PS SN1.125 - 1/5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RY-FL and is the answer not in the manual?

Questions and answers

Summary of Contents for SyxthSense RY-FL

  • Page 1 Enclosure IP20 ABS Plastics Dimensions W150 x H210 x D110mm NOTE: RY-FL requires FLTA version 2.2 or later and FLSER service tool version 2.2 or later. Online store: www.syxthsense.com Enquiries: T: 0870 20 80 100 F: 0870 20 80 200...
  • Page 2 In the RY-FL network due to extended network messaging the maximum number of FL-REP repeaters is limited to 2 and the maximum number of RY-FL input / output modules to 20 per network. The system can still have up to 99 sensors / transmitters (including RY-FL input/ouput modules) as a part of the solution.
  • Page 3 SyxthSense Ltd RY-FL Wiring The diagram below illustrates the wiring details for the RY-FL device. Each RY-FL can be configured to receive 2 input signals and control two output signals. The selection / configuration is done using FLSER (ver 2.2 or later) service tool.
  • Page 4 FLSER flashed "WAIT". Once the RY-FL has been succesfully addressed the LEDs on the RY-FL and FLSER flash in sequence for 5 times, and the FLSER display shows OK. The RY-FL is now operational.
  • Page 5 SyxthSense Ltd 6. Finally switch the FLSER switch to OFF position. Now the RY-FL returns to normal mode and starts to communicate to the FLTA receiver. LED Operation RY-FL has three LED on its printed circuit board to indicate the operation of the device.