Testing regime
Luminaires incorporate fully automatic selt testing and will regularly
test for correct lamp (LEDs) functioning and for battery functioning in
accordance with a predefined test programme that exceeds the
requirements of BSEN50172 / BS5266 Pt.8: 2004.
See separate FASTEL test regime description.
Where stand alone self testing versions are installed, it is necessary
at least monthly to record the indicator LED status.
Remote control and monitoring (SRM units only)
All SRM version luminaires incorporate remote control and monitoring
capability. Luminaires may be connected via collector boxes and
interface boxes either to a local computer or to a LAN or internet
connection and remotely controlled and monitored. All SRM
luminaires are assigned individual addresses before leaving the
factory and should be installed in accordance with the installation
plans. Details of the remote control and monitoring operation may be
found in a separate sheet.
Technical Specification KLIPPA LED Bulkhead
Supply Voltage
230V +10% -10%, 50/60Hz
Mode of Operation
Non Maintained or Maintained
K-LED/N/M3 - 0.6kg
Weight
K-LED/N/M3-SRM - 0.6kg
Duration
3 hours
24 hours for full duration
Recharge period
(14 hours for 1 hour)
Light sources
High Efficiency white LEDs
Battery
2.4V 1600mAh Ni-Cd
Ambient temperature
Standard - IP40
Degree or Protection
KLIPPA IP65 Kit - IP65
Conformity
BSEN 60.598-2-22
Technical Specification KLIPPA 8W Bulkhead
Supply Voltage
230V +10% -10%, 50/60Hz
Mode of Operation
Non Maintained or Maintained
K8/N/M3 - 0.6kg
Weight
K8/N/M3-SRM - 0.6kg
Duration
3 hours
24 hours for full duration
Recharge period
(14 hours for 1 hour)
Light sources
8W Fluorescent Lamp
Battery
3.6V 4000mAh Ni-Cd
Ambient temperature
Standard - IP40
Degree or Protection
KLIPPA IP65 Kit - IP65
Conformity
BSEN 60.598-2-22
P4 Limited
1 Wymans Way, Fakenham, Norfolk NR21 8NT
T: 01328-850555
F: 01328-850559
E: info@p4fastel.co.uk
www.p4fastel.co.uk
2014 copyright all rights reserved
Details correct at time of publication P4 reserve the right to change specification at any time.
Leading the way in self testing emergency lighting
Installation and Operating Instructions for
KLIPPA LED Bulkhead & KLIPPA 8W Bulkhead
K-LED/N/M3, K-LED/N/M3-SRM
K8/N/M3 & K8/N/M3-SRM
BHF150-10 Issue 1. July 2014
Drawn By T. Skevington - Approved By

Advertisement

loading

Summary of Contents for P4 KLIPPA Bulkhead Series

  • Page 1 KLIPPA IP65 Kit - IP65 2014 copyright all rights reserved BHF150-10 Issue 1. July 2014 Conformity BSEN 60.598-2-22 Details correct at time of publication P4 reserve the right to change specification at any time. Drawn By T. Skevington - Approved By...
  • Page 2 The KLIPPA Bulkhead housing contains dimples for various Applying Mains Supply Installation Instructions differentconduit sizes. Choose the size that relates to your conduit box and drill out a suitable sized hole (see Fig 5.) for the fixing screws (not KLIPPA Bulkhead luminaires are fully automatic self testing emergency supplied) and a centre hole for the cable.

This manual is also suitable for:

Klippa bulkhead k-led/n/m3Klippa bulkhead k-led/n/m3-srmKlippa bulkhead k8/n/m3Klippa bulkhead k8/n/m3-srm