PowPak
| Installation
®
Relay Module
Part of the Energi TriPak
Family
®
RMJS-16R-DV-B | URMJS-16R-DVB
120 / 277 V~ 50 / 60 Hz 16 A
With Softswitch
1/2 HP at 120 V~ 1
®
UL 2043 Plenum Rated
RMJS-16RCCO1DV-B | URMJS-16RCCO1DVB
With Softswitch
and Occupancy-Status CCO
®
RMJS-5R-DV-B
120 / 277 V~ 50 / 60 Hz 5 A
1/6 HP at 120 V~ 1/3 HP at 277 V~
RMJS-5RCCO1-DV-B
UL 2043 Plenum Rated
With Occupancy-Status CCO
*
For set-up, programming, and troubleshooting with a Vive
system, please refer to the installation instructions included
with the Vive
hub or at www.lutron.com
TM
Note for Replacement:
RMxS and URMxS - the "S" model can replace the non-"S" model
Important Notes:
Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
Note: Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely
before installation.
Operate between 32 °F (0 °C) and 131 °F (55 °C).
0% to 90% humidity, non-condensing.
For indoor use only.
WARNING
Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
PowPak
®
Relay Module
Install in center of room to
maximize RF coverage.
Radio Powr Savr
TM
Occupancy
Sensor
30 ft (9 m)
Maximum
Pico
®
Remote
Control
40 ft (12 m)
All Wireless Transmitters must be installed within
30 ft (9 m) of the PowPak
Relay Module.
®
FCC / IC Information:
This device complies with part 15 of the FCC Rules and Industry Canada licence-exempt
RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause undesired
operation.
Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user's
authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Required Components
For each system ensure you have:
At least one PowPak
Relay Module.
041504
®
Rev. A
(Occupancy-Status CCO Option Shown)
09/2015
Load
Status
1
HP at 277 V~
2
LED
Relay Toggle
Advanced
Operations
Contact
Relay Module
Closure
without
Output
occupancy-status
(CCO)
CCO also
TM
(Class 2)
available.
PowPak
Relay Module
®
Start Here
R
1
Install PowPak
Relay Module
R
When installing a PowPak
Relay Module,
use the supplied conduit nut and wire the module
as shown.
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakrelay
2
Associate Wireless Transmitters to PowPak
Before beginning this step, make sure that there are no other PowPak
from other systems can be incorrectly associated to this system.
A
3
Permanently Install
Wireless Transmitters
Note: Please consult individual component
installation guides for information.
Link
Test
Need Help? www.lutron.com or call the Lutron Technical Support Center, at 1.800.523.9466
At least one Wireless Transmitter.
+
Link
Test
Radio Powr Savr
Radio Powr Savr
Occupancy
Daylight Sensor
TM
Sensor (10 maximum)
(1 maximum)
120/277 V~
50/60 Hz
Red
(Switched
Line/Hot)
COM
(Common)
NC
NC
NO
(Normally Closed)
(Normally Closed)
(Normally Open)
CCO operation affected only by
associated occupancy or vacancy sensors.
Room Occupied:
NO = Close NC = Open
Room Unoccupied: NO = Open NC = Close
R
20 A Relay Module
modules being set up within the same building. It is possible that Wireless Transmitters
®
B
Hold the Relay Toggle
Hold the indicated button on a Wireless Transmitter for
button on the PowPak
6 seconds to associate the device.*
®
Relay Module for 6 seconds
Repeat for any additional Wireless Transmitters.
to enter association mode.
* If no g button, hold "Lights Off" button.
C
Hold the Relay Toggle button on the PowPak
Note: The load will flash once after each
step to confirm successful completion.
Relay Module for 6 seconds to save association(s).
*
4
Daylight Sensor setup
Calibration
A
Turn lights in room on using the Relay
Toggle button on the PowPak
Relay
®
Module or an associated Pico
.
®
B
Press & hold "Cal." on the associated
Daylight Sensor for 6 seconds.
C
Exit room for 5 minutes to allow
calibration to be completed.
Note: When calibration has completed, all
lights will flash and the system will begin
daylighting.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For
warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
Pico
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase.
®
This warranty does not cover the cost of installtion, removal or reinstallation, or damage resulting from misuse, abuse, or damage from
Remote Control
improper wiring or installation. This warranty does not cover incidental or consequential damages.
(10 maximum)
LUTRON'S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE
MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE
PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow
Cal.
the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above
limitations may not apply to you.
TM
Lutron, Energi TriPak, Pico, PowPak and Softswitch are registered trademarks and Radio Powr Savr and Vive are trademarks of Lutron
Electronics Co., Inc. ©2012-2015 Lutron Electronics Co., Inc.
White
(Neutral)
To Load
Black
(Line/Hot)
Conduit Nut
To 3rd Party Equipment
Note: When wiring a CCO model to 3rd-party
systems, use 20 AWG to 16 AWG (0.5 mm
1.5 mm
2
) solid or stranded wire.
*
Link
®
Tuning (Optional)
Link
Cal.
Test
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
(using multiple Relay Modules with one
Daylight Sensor) follow the Tuning
procedure described in the Daylight Sensor
(LRF2-DCRB) installation instructions.
Use the Relay Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
CCO Information
• Some PowPak
Relay Modules include a dry contact closure
®
output that provides occupancy status to 3rd-party equipment
such as building management systems, HVAC, and VAV
controllers.
• CCO provides both normally open (NO) and normally closed (NC)
maintained-type outputs.
• CCO rated to switch resistive loads at
Switching
Resistive
Voltage
Load
voltages up to 24 V only. To properly
control inductive load types such as
0-24 V-
1.0 A
0-24 V~
0.5 A
relays, solenoids, or motors, refer to
Application Note #434.
Unaffected Mode
Unaffected Mode allows a system with an Occupancy Sensor
associated to multiple Relay Modules to be set up such that only
selected loads turn on automatically. Other loads will require a
R
manual turn-on with a Pico
Remote Control. All loads will turn off
2
to
automatically when the room is vacated.
A On a Relay Module, press and hold both the Relay Toggle and
Advanced Operations ("ADV") buttons for 6 seconds until the
LED begins flashing quickly.
B On the associated Occupancy Sensor, press and hold the
"Test" button* for 6 seconds until the lens flashes.
C Unaffected mode will be exited automatically. This Relay
Module will now be unaffected by occupancy commands.
Repeat procedure for any additional devices.
* If no "Test" button, hold "Lights On" button.
Note: The CCO cannot be made unaffected.
Reset Factory Defaults
Note: In some instances it may be necessary to reset the
PowPak
Relay Module back to factory default settings.
®
Test
A Triple-tap the "CNTRL" button on the Relay Module and hold
until the LED begins to flash slowly.
B Within 3 seconds of flashing, release and triple-tap the button
again and the LED will flash rapidly indicating that the unit has
been reset to factory defaults.
Note: Any associations or programming previously set up with
the unit will be lost and will need to be re-programmed.
*
Troubleshooting
www.lutron.com
Load does
• Ensure breaker to the PowPak
Relay Module
®
not respond
is on.
to Wireless
• Ensure the load has been properly wired to the
Transmitter(s)
PowPak
Relay Module.
®
• Ensure Wireless Transmitter is properly
associated to PowPak
Relay Module.
®
• Ensure Wireless Transmitter's battery is installed
correctly.
Wireless
• The maximum number of Wireless Transmitters
Transmitter(s)
have been associated to the PowPak
Relay
®
cannot be
Module. To remove a previously set up Wireless
associated
Transmitter, tap the button used for association
to PowPak
on the Wireless Transmitter three times, on the
®
Relay Module
third tap hold for three seconds and then tap
three more times.
R

Advertisement

loading

Summary of Contents for Lutron Electronics TriPak PowPak Series

  • Page 1 (2) this device must accept any interference, including interference that may cause undesired Permanently Install Daylight Sensor setup operation. Troubleshooting www.lutron.com Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s Wireless Transmitters Calibration Tuning (Optional) authority to operate this equipment. Link Cal.
  • Page 2 Dépannage * Configurez le capteurs de lumière du jour fonctionnement. www.lutron.com Les modifications non expressément approuvées par Lutron Electronics Co., Inc. pourront annuler sans fil de façon permanente le droit de l’utilisateur à faire fonctionner cet équipement. Étalonnage Mise au point (optionnelle) La charge •...
  • Page 3 Configuración del sensor fotoeléctrico problemas de funcionamiento no deseados. Solución de problemas www.lutron.com Las modificaciones que no estén expresamente aprobadas por Lutron Electronics Co., Inc. podrían inalámbricos de forma Calibrado Ajuste (Opcional) anular la autorización del usuario para operar este equipo.
  • Page 4 Solução de problemas www.lutron.com um funcionamento indesejável. os transmissores sem fio As modificações não aprovadas expressamente pela Lutron Electronics Co., Inc. podem invalidar a Calibração Ajuste (Opcional) A carga não • Certifique-se de que o disjuntor do módulo de relé...

This manual is also suitable for:

Tripak powpak rmjs-16rcco1dv-bTripak powpak rmjs-16r-dv-bTripak powpak urmjs-16r-dvbTripak powpak urmjs-16rcco1dvbTripak powpak rmjs-5r-dv-bTripak powpak rmjs-5rcco1-dv-b