Summary of Contents for Digital Equipment 2T-HA10F-CD
Page 1
2T-HA10F-CD 3.6 kVA Uninterruptible Power System Operating Information Order Number: EK-HA10F-OP.B01 Revised August 1992. Revision Update Information: Digital Equipment Corporation...
Preface OVERVIEW This manual is intended for users of the 2T-HA10F-CD 3.6 kVA Uninterruptible Power System (UPS). It provides a general introduction to the UPS; specifications; detailed information on system controls and operation; deinstallation procedures; and maintenance, troubleshooting, battery testing, and storage information.
Page 6
CONVENTIONS This section describes the special symbols used in this manual. NOTES: Calls attention to information in text that may be of special importance. CAUTIONS: Calls attention to information in text that is essential in avoiding system or equipment damage. WARNINGS: Calls attention to information in text that is essential to the safety of personnel.
Introduction 1.1 General Description The 2T-HA10F-CD UPS is a 208 Vac, 60 Hz, 3.6 kVA UPS that provides back-up power to prevent interruptions in the ac power. The UPS protects sensitive equipment against problems associated with poor quality ac power or a complete loss of ac power.
Introduction 1.2 Digital Modifications The 2T-HA10F-CD UPS is a Deltec UPS that has been modified by Digital Equipment Corporation to enhance its value and ease of use. The UPS unit and the battery unit have both been modified by Digital.
Specifications 2.1 UPS Electrical Input Voltage: 208 Vac +10%/-15% Maximum Input Current: 20.0 A at 208 Vac Frequency: 60 Hz Current Distortion: Less than 10% (typically 5%) with full, nonlinear load 2.2 UPS Electrical Output Voltage: 208 Vac 2% Frequency: 60 Hz Regulation: 2%, steady state Voltage Distortion: Less than 3%, total harmonic distortion Overload Rating: 150% of full-load for 30 seconds...
Specifications 2.5 Battery Unit Physical Battery Unit Dimensions: Width: 42.24 cm (16.63 in.) Height: 16.84 cm (6.63 in.) Depth: 63.83 cm (25.13 in.) Battery Front Panel Dimensions: Width: 48.26 cm (19.00 in.) Height: 17.78 cm (7.00 in.) Battery Weight: 67 kg (148 lb) 2.6 Assembly Requirements in an H9702 Cabinet Width: 48.26 cm (19.00 in.) Height: 48.89 cm (19.25 in.)
Operation 3.1 Controls and Indicators The 2T-HA10F-CD UPS uses four controls and two indicators for routine operation. Controls • AC input circuit breaker • Battery circuit breaker • Audio alarm silence button • Battery unit circuit breaker Indicators • Status lights...
Page 13
Operation Figure 3–1 2T-HA10F-CD UPS Front Panel Battery Status Lights Ventilation Alarm Silence Circuit Breaker Button BATTERY Normal Bypass On Battery Fault Low Battery ALARM AC Input SILENCE Circuit Breaker AC INPUT MKV 040000216 03 91 RAGS 3.1.1 UPS Controls The following sections describe the controls for the UPS unit.
Page 14
Operation 3.1.1.2 Battery Circuit Breaker The battery circuit breaker on the front panel must be ON before the UPS can charge the batteries or receive battery back-up power. It opens and closes the circuit between the battery unit and the UPS. If the ac input circuit breaker is OFF or tripped and the battery circuit breaker on the front panel is ON, the UPS will drain the batteries until the batteries reach a predetermined low-voltage level.
Operation 3.1.1.3 Alarm Silence Button When the audio alarm is activated, it can be silenced by pushing the alarm silence button. This button is located next to the ac input circuit breaker. Pressing the alarm silence button does not silence the audio alarm permanently. The audio alarm will be activated again the next time the UPS has an alarm condition.
Operation If the battery voltage continues to drop, the UPS will eventually stop operating and the load will be dropped. After the UPS stops operating, it will wait 3 hours for the return of the normal ac line power. If the normal ac line power returns within 3 hours, the UPS will turn on automatically.
NEMA 6-15R (15 A, 208 V) receptacles. 3.3 Emergency Shutdown Plug The 2T-HA10F-CD UPS is shipped with an emergency shutdown plug installed in the emergency shutdown jack on the rear of the UPS (see Figure 3–2). The UPS will not operate if the emergency shutdown plug is not installed or if the circuit between the terminals of the emergency shutdown plug is broken.
Page 18
Operation Figure 3–2 2T-HA10F-CD UPS Rear View with FCC Shielding Removed Distribution Panel Emergency Shutdown Plug Battery Unit Battery Unit Circuit Breaker MKV 040000216 02 91 RAGS Operation 3–7...
Operation 3.4 Operating Procedures The following sections contain the operating procedures for the 2T-HA10F-CD UPS. 3.4.1 Normal UPS Powerup Use the following procedure to power up the UPS: 1. Ensure that all circuit breakers are turned OFF and that the system power cord is plugged into the proper electrical outlet.
Operation Typically, the UPS logic trips the battery circuit breaker on the front panel if there is a failure in the UPS, or if the battery system needs protection. Tripping the battery circuit breaker on the front panel causes the UPS to automatically transfer the load to the bypass line.
The UPS unit and battery unit contain high voltage. Use extreme care, remove all jewelry, and observe all safety precautions when removing or working on the 2T-HA10F-CD. Use the following procedure to remove the UPS and battery unit from the H9702 cabinet: 1.
Removal and Replacement 8. Disconnect the three-wire (red, green, black) plastic connector pair that connects the battery unit to the UPS unit by pulling them straight apart. 9. Disconnect the standard L6-30R/L6-30P twistlock connector pair that connects the system power cord to the UPS unit by untwisting them and pulling them apart.
Maintenance 5.1 Preventive Maintenance The user can expect long, trouble-free operation from the 2T-HA10F-CD UPS with a minimum of preventive maintenance. Keep the area around the unit, especially the air inlet, clean and free of dust and moisture. This is the best preventive measure.
Page 24
Maintenance Is the audio alarm sounding? 2. If the load does not seem to be receiving power from the UPS (no lights lit on the load(s) or sounds coming from the load(s)), check the following: a. Ensure that the UPS is correctly connected to an electrical outlet. b.
Maintenance Table 5–1 Troubleshooting Status Lights Lit Status Light Indication Corrective Action Normal (green) Normal operation. The UPS is drawing power from None the ac input line and the ac input power meets input specifications. The UPS is in Normal mode when the ac line voltage is 208 Vac (+10%/-15%) and the output voltage is 208 Vac ( 2%) and locked to the line frequency.
Compare these results with future tests. 5.5 Storage Procedures If the 2T-HA10F-CD UPS is going to be stored, the following guidelines must be followed to protect the batteries: 1. Charge the batteries fully before the UPS is stored by connecting the UPS to an ac source and operating it for 12 hours with all three circuit breakers in the ON position.