PrimeVOLT G2000 Installation & Operation Manual page 16

Power limiter
Table of Contents

Advertisement

Wiring Diagram
Inverter
RS485 Connector
ON
1
Pin:Off
1. Connecting T/R1+ and T/R1- of inverter RS485 connector to the T/R+ and
T/R- of the data logger respectively.
2. Between two inverters, connecting T/R2+ of first inverter with T/R1+ of next
inverter, and connect T/R2- of first inverter with T/R1- of next inverter.
3. Set terminal resistor switch "ON" of the terminal-end inverter (the last
inverter of the row) only. The others should be set as "OFF".
Setting the Terminal Resistor
Each inverter has built-in terminal resistor, if RS485 is connecting to multiple
inverters or the total communication length is too long to cause the abnormal
communication, please set the terminal resistor switch to "ON" of the last inverter
in the row connection, all other remaining inverters shall switch to "OFF".
ON
1 (OFF)
Inverter
RS485 Connector
ON
1
Pin:Off
T/R -
T/R +
Terminal Resistor is active
Terminal Resistor is invalid
Inverter
RS485 Connector
G2000
Power Limiter
13
ON
1
Pin:On

Advertisement

Table of Contents
loading

Table of Contents