London Electronics Fusion-L 4 digit version Manual

Large digit load/weight indicator/controller, connection details, scaling and general information

Advertisement

Quick Links

London Electronics Limited
Large digit load/weight indicator / controller
Fusion-L 4 digit version
Connection details, scaling and general information
www.london-electronics.com help@london-electronics.com
!
Rear case screws - please note
The rear panel is held in place with finger-screws, which
only need to be gently tightened.
Do not use tools to tighten or loosen the screws, as
this could cause damage to the internal threads.
Document Ref:pm65\manuals\Fusion_L_4digit
Thorncote Road, Near Sandy, Bedfordshire SG19 1PU
Tel +44(0)1767 626444
8.8.8.8.
dg
OK
Caution: There is a risk of electrical
shock if this instrument is not properly installed
Caution: Risk of danger: Read the whole
manual before you install this display
Fax +44(0)1767 626446
Software version F00.23
Revision:23 Dated: 21 Jan 2016
1

Advertisement

Table of Contents
loading

Summary of Contents for London Electronics Fusion-L 4 digit version

  • Page 1 Tel +44(0)1767 626444 Fax +44(0)1767 626446 www.london-electronics.com help@london-electronics.com Large digit load/weight indicator / controller Fusion-L 4 digit version Connection details, scaling and general information 8.8.8.8. Caution: There is a risk of electrical shock if this instrument is not properly installed...
  • Page 2: Warranty

    Warranty We warrant our products against defects in materials or workmanship for a period of three (3) years from the date of purchase. In the event of a defect during the warranty period, the unit should be returned, freight (and all duties and taxes) prepaid by the Buyer to the authorised distributor from where the unit was purchased.
  • Page 3: Table Of Contents

    Contents Warranty Warnings Introduction General Description Suspension Mounting Wall Mounting Panel Mounting Connections 10-11 Installation hints for best performance 12-13 Easy/Advanced menu mode Language Selection Display Brightness Display Calibration Modes Direct Calibration 18-19 Linearisation with Direct Calibration 20-21 Theoretical Calibration 22-23 Linearisation with Theoretical Calibration 24-25...
  • Page 4: Warnings

    Warnings Please carefully read this manual and all warnings. Install the display ONLY when you are sure that you’ve covered all aspects. Where the product is intended for “UL” installations, removal or addition of option boards is not permitted. Check that the model number and supply voltage suit your application before you install the display.
  • Page 5: Introduction

    Introduction Please contact us if you need help, if you have a complaint, or if you have suggestions to help us improve our products or services. If you contact us about a product you already have, please tell us the full model number and serial number, so that we can give you accurate and fast help.
  • Page 6: General Description

    General Description This series of displays accepts industrial sensors to allow various physical measurements to be made, such a weight, temperature, pressure, humidity etc. Different models are available for different sensor types. The main function of this series is to give a clear numeric readout of the variable being monitored.
  • Page 7: Suspension Mounting

    Suspension Mounting dimensions 15mmO 15mmO 6.35mmO 6.35mmO Plan View 25mm X mm Y mm Short-drop mounting holes Long-drop mounting holes W mm 77 mm 8.8.8.8.8.8. H mm H mm 25mm Cable Glands. Number of glands depends on installed options. Detail showing bracket You can order these displays with the cable glands in the bottom surface (as shown) the hardware fitting sequence...
  • Page 8: Wall Mounting

    Wall Mounting dimensions 98 mm W mm 60 mm 22mm 8.8.8.8.8.8. H mm 25mm Cable Glands. Number of glands depends on installed options. 80 mm 60 mm The 4 bracket holes are 5.2mm diameter 60 mm X mm 72.5 mm Detail showing bracket You can order these displays with the cable glands in the bottom surface (as shown) the...
  • Page 9: Panel Mounting

    Panel mounting dimensions 67mm 8.8.8.8.8.8. 25mm H mm A mm Neoprene Bezel W mm gasket Neoprene Cable glands gasket B mm Detail showing bracket hardware fitting sequence Bezel Panel cutout dimensions Neoprene gasket Panel A+3mm(h) x B+3mm(w) M8 x 15 bolt Spring washer Fit first Flat washer...
  • Page 10: Connections

    Connections Warning: Disconnect all power before removing the rear of the display There is a wide range of possible locations for the input board, output board and power supply board/s. Their locations depend on the height of digits, number of digits, brightness of digits and any installed options.
  • Page 11 Connections Warning: Disconnect all power before removing the rear of the display Output option board (if fitted) Connectors and options Analog Connectors may be Serial Data 0, 2 or 4 Alarm Relay output present even if output output option output options option options are not installed.
  • Page 12: Installation Hints For Best Performance

    Installation hints for best performance This section offers several suggestions which will help you get the best performance from your weighing system. Loadcells create very small signals which can easily be corrupted by electrical noise. These steps will ensure you get the best possible performance from your meter. Use good quality screened signal cable, with 3 twisted pairs.
  • Page 13 6 Wire Loadcell 4 Wire Loadcell...
  • Page 14: Easy/Advanced Menu Mode

    Easy or Advanced menu mode You can choose from two menu modes. 1. Easy Mode - This limits the menu to the most commonly required features, in order to make it less complex and easier to navigate. This is the default level. 2.
  • Page 15: Language Selection

    Language Selection for user interface You can select English or French menu prompts. This feature is available in Easy and Advanced Modes Set2 Output Set1 Alarms Lockout Switch must be OFF Digit Max/Min Reset Circuit board Press together, briefly Display shows Set2 Output Set1...
  • Page 16: Display Brightness

    Display Brightness You can adjust the display brightness at any time, provided the display is locked. This feature is available in Easy and Advanced Modes Set1 Set2 Output Alarms Digit Lockout Switch must be ON Max/Min Reset Circuit board Press 3 seconds Set1 Set2 Output...
  • Page 17: Display Calibration Modes

    Meter Calibration Modes You can choose from two main calibration methods. 1. Direct Calibration - this is when you connect the meter to your system and make the meter read what you want it to, at 2 different points. This is the preferred calibration method, because it allows you to calibrate the system as a whole.
  • Page 18: Direct Calibration

    Direct Calibration - Full Scale Setting This is when you connect the meter to your system and make the meter read what you want it to, at 2 different points. This is the preferred calibration method, because it allows you to calibrate the system as a whole. How to do direct calibration:- If you have not done so before, please select Direct Calibration mode from the previous page.
  • Page 19 Direct Calibration - Zero Setting How to calibrate the ZERO point. This feature is available in Easy and Advanced Modes Set2 Output Set1 Alarms Lockout Switch must be OFF Digit Max/Min Reset Circuit board Press 3 seconds Apply the lowest calibration signal Set1 Set2 Output...
  • Page 20: Linearisation With Direct Calibration

    Linearisation with Direct Calibration If your system is non linear, you can calibrate the meter and correct for this with the lineariser function. You will need to apply a series of known loads, starting at 0 and working up to full scale. You will then tell the meter what it should read for each applied load.
  • Page 21 Linearisation with Direct Calibration - cont’d. Set1 Set2 Output Alarms The display will show SE.01 Digit Apply your 1st known load to the system Max/Min Reset and press OK. The display will now show rd 01 You can now tell the meter what it should display for this load.
  • Page 22 Theoretical Cal. - Decimal Point & Full Scale This is when you type in the sensor’s theoretical signal level at the top and bottom of its range and the value to display, for each signal level. If you have not done so before, please select Theoretical Calibration mode from the Meter Calibration page AND choose whether your input is current or voltage.
  • Page 23: Theoretical Calibration

    Theoretical Calibration - Low end calibration This is when you type in the sensor’s theoretical signal level at the top and bottom of its range and the value to display, for each signal level. If you have not done so before, please select Theoretical Calibration mode from the Meter Calibration page.
  • Page 24: Linearisation With Theoretical Calibration

    Linearisation with Theoretical Cal. If your system is non linear, you can calibrate the meter and correct for this with the lineariser function. With this method, you can enter theoretical values for input signal and display values, with- out having to connect a sensor. First, you must select Theoretical Calibration Mode (see page on calibration Modes) Then, proceed as shown below...
  • Page 25 Linearisation with Theoretical Cal. - cont’d. Set1 Set2 Output Alarms The display will show In 01 followed by Digit an editing screen. Here you can enter your Max/Min Reset next calibration input signal level using DIGIT button to select each digit in turn. Increase or decrease the value of each digit using the UP or DOWN buttons.
  • Page 26: Sensor Drift Correction

    Sensor Drift correction If your system is normally reading 0, for example as is typical with platform scales or a torque meter, you may find a small amount of sensor drift caused by changes in temperature, ageing etc. We can automatically correct for slow, long term drift, by comparing your signal to 0 every 30 seconds, and re-calibrating to remove any detected movement.
  • Page 27: Logic Input Functions

    Logic input functions The three contact closure inputs on the rear of the meter have default functions which are:- Contact closure 1 = Tare Contact closure 2 = Peak/Valley display Contact closure 3 = Reset You can re-assign these to include :HOLD, Nett/Gross value display, Memory page address 1,2 or 4 (only if Multi-memory MEM option is installed) !! This feature is available in Advanced Mode only !! Lockout Switch must be OFF...
  • Page 28: Logic Input Connections & Front Buttons

    Logic input connections and front buttons The previous page explained how to select the functions of the 3 logic inputs. You can connect remote contact closures or open NPN collectors to activate these logic inputs. The logic input provides a 5V DC signal. When you connect this to common, a current of 1mA will flow.
  • Page 29: Factory Defaults

    Factory Defaults You can return the display to its factory default conditions whenever you wish. If you do so, you will permanently loose all your settings and will need to start from the beginning again. The calibration Audit Counter will NOT be reset, there is no way provided to reset this value, as it is intended as a secure record to indicate whether changes have been made to the display since it was last calibrated..
  • Page 30: Signal Filtering / Averaging (See Also Page 44)

    Signal Filtering / Averaging You can adjust the filtering time constant to reduce the effect of noise or instability on your input signal. A larger FIL value will give a more stable display, but the response to signal changes will be slower.
  • Page 31 Filter Jump value See the Easy/Advanced mode selection page near the beginning of this manual, and choose advanced mode. The Filter Jump value allows you to decide how the display will respond to a process step change. It does this by overriding the filtering, if the input signal moves by more than a chosen amount in one conversion.
  • Page 32: Last Digit Rounding

    Last Digit rounding up by 1, 2, 5, 10, 20 or 50 You can adjust the way the display rounds up, which is useful if you want to display a very large number, but do not want jitter on the last digit. The display can be set to round up to the nearest 1 (no rounding) 2, 5, 10, 20 or 50 This feature is available in Easy and Advanced Modes Set1...
  • Page 33: Scale Factor Adjustment

    Scale Factor adjustment After you have calibrated your meter, you can use the SCALE feature to make fine adjust- ments to calibration, without affecting the calibration itself. Examples 1.Changing weight units of measure from kg to pounds You could also use the SCALE to convert your readout from kg to pounds, without affecting the calibration.
  • Page 34: Offset Adjustment

    Offset adjustment After you have calibrated your meter, you can use the OFFSET feature to make fine addi- tions or subtractions to the reading, without affecting the calibration itself. For example if your weighing structure is altered after calibration and you want to subtract the effect of 37kg of extra metalwork which was welded to the hopper, you can easily do this by entering a value of -37 in the offset value.
  • Page 35: Menu Timeout Adjustment

    Menu timeout adjustment The display has a default timeout of 60 seconds, to allow you sufficient time to refer to the manual between key operations. You can make this period shorter, if you wish, once you become more familiar with the setup method.
  • Page 36: Reverse / Mirror Display Setting

    Reverse Display function (mirror image) If you need to be able to see a reflection of the display in a mirror or other reflective surface, for example in a simple heads-up system, or for drivers reversing into a bay, using mirrors only, you can set the display to show as a mirror image.
  • Page 37: Bootup Routine Choices

    Bootup routine and Tare save choices When you switch on your meter, it can be set to power up with 3 possible summary mes- sage combinations. The choices are:- bt 0 Segment test, followed by a full summary of software revision, calibration audit number, model number, installed options.
  • Page 38: Multi Memory Mem Option

    Multi-Program Memory option MEM The three contact closure inputs on the rear of the meter may be used to call up between 1 to 7 additional meter setup memories (pages), if the MEM option has been installed. This allows you to save up to 8 complete sets of independent calibrations, alarm settings, ana- logue output settings and serial comms settings.
  • Page 39: Error Codes

    Error codes and fault finding 1. Under Range. The meter is being asked to display a value which is more -Ur- negative than its limit of -1999 2. Over Range. The meter is being asked to display a value which is higher -Or- than its limit of 9999 If no loadcell is connected to the display, you will see one of these fault...
  • Page 40: Output Options - Installing

    How to install option boards Warning: Disconnect Where the product is intended for “UL” installations power before you expose removal or addition of option boards is not permitted. the internals of the display If you want to open your display to install or modify option boards, follow these steps... Switch off power to the display and unplug all connectors.
  • Page 41: Weee

    Waste Electrical Electronic Equipment (WEEE) In Europe, this equipment must be disposed of in accordance with European Parliamentary Directive 2002/96/EC This directive encourages recycling and the reduction of waste materials in the environment. This means it must be sent to an approved recycling plant if you want to dispose of it. It must not be thrown away with general rubbish.
  • Page 42: Equipment Specifications

    Equipment Specifications Case Material Heavy duty welded uPVC Connectors Internal detachable Screw Terminal connectors accessed via compression glands Environmental Storage Temperature range -20 to +70C, non condensing Operating temperature range 0 to 50C. Allow 30 minutes for this display to reach thermal equilibrium. Internal heater option available for use in conditions down to -25C Power 100-240 VAC, 48V AC, 45 to 60Hz or 11-30 VDC optional...
  • Page 43: Loadcell Connection Examples

    Loadcell connection notes Important - Sense + and Sense - must always be referred to the excitation voltage. Never leave these terminals open. Signal I/P & Excitation 4 wire connection for short cable runs Signal I/P & Excitation 6 wire connection for long or high resistance cable runs Cable and/or zener barrier resistance Cable and/or zener barrier resistance must not cause the excitation voltage to drop below 4V.
  • Page 44: Input Board Filter Configuration

    Input board filter configuration The new input board now offers a sharp cutoff active filter which rejects all vibrations above 7 Hz. This is idea in applications where mixing or vibration is common. For optimum rejection of noise, we recommend you set the Fil.J parameter to 99 and choose a value for FIL which offers adequate filtering.
  • Page 45 Notes...
  • Page 46 Notes...
  • Page 47 Notes...
  • Page 48: Declaration Of Conformity

    All signal cabling shall be screened. The screen shall only be terminated to the power earth terminal at the meter end of the cable. Declared as true and correct, for and on behalf of London Electronics Ltd. J.R.Lees Director...