SELF TESTING MAINTAINED EMERGENCY LUMINAIRIES WITH LEDs
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
LIGHT SOURCE INTENSITY (Mains/emerg.)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
VIEWING DISTANCE
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS (LxHxW)
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places
where emergency luminaires are needed.
Each luminaire must be permanently
connected to mains power supply. In
normal operation the led strip lights and
the battery is charging. In
m a i n s
p o w e r
l u m i n a i r e
w i l l
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
OPERATION
Battery Charging
The battery charging is completely
controlled by microprocessor and is
protected from completely discharge and
over charge.
Battery Cut-off
The luminaire enters in this operation
when the mains power supply fails and
battery has lost its energy. During this
operation the luminaire enters the idle
state
and
battery
negligible, in order to be protected from
Page 1 from 6
LLB-26/90 LLB-26/180
6W/6.4VA (PF=0.94)
4.8V/1.2Ah
Charge LED, Lamp fault LED, Battery Fault LED, TEST button
90 min
230lm / 300lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
26m
287 x 205 x 55 mm
876gr.
Thank you for your trust in our products
Olympia Electronics - European manufacturer
case
of
s u p p l y f a i l u r e
l i g h t t h e l e d s t r i p
consumption
(for
LED MODULE Specs. see page 3)
LLB-40/90
220-240V AC/50-60Hz
7W/7.4VA (PF=0.94)
4.8V/1.2Ah 4.8V/2.4Ah
From overcharge and deep discharge
180 min
90 min
White LEDs
230lm / 123lm
370lm / 300lm
5 to 40 C
Up to 95%
Aluminum, ABS/PC, PC, Plexiglass
435 x 280 x 55 mm
1396gr.
3 years (1 year for the battery)
deep discharge.
Manual Test
By pressing the test button briefly (less
than 5 seconds) an emergency operation
test is performed. The white LEDs will be lit
a
for approx. 3 seconds, the red LED will
t h e
flash during this test sequence.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Manual Autonomous Test
By pressing the test button for between 5
and 10 seconds a battery condition test is
performed. This test will last for the stated
duration and can only be performed when
the battery is fully charged (steady green
LED). The white LEDs will be lit and the red
LED will flash during this test sequence.
is
Automatic Autonomous Test
The Automatic Autonomous Test measures
LLB-40/180
LLB-64/90
9.3W/9.8VA (PF=0.94)
4.8V/2Ah
24 h
180 min
90 min
600lm / 500lm
IP 44
o
40m
673 x 400 x 55 mm
1503gr.
1650gr.
923064003_09_002
LLB-64/180
4.8V/4Ah
180 min
64m
2777gr.